background image

En-6

Breaker should be installed at every refrigerant system. Do not use a breaker in a different 

refrigerant system.

Refer to the table for the breaker specifications of each installation condition. Perform 

the power crossover wiring within the range of the same refrigerant system. When the 

crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 

below.

A. Current breaker requirements

Model

MCA

MFA

AUXB004GLEH

0.20 A

20 A

AUXB007GLEH

0.20 A

AUXB009GLEH

0.20 A

AUXB012GLEH

0.24 A

AUXB014GLEH

0.29 A

AUXB018GLEH

0.30 A

AUXB024GLEH

0.75 A

MCA: Minimum Circuit Ampacity

MFA: Maximum Fuse Ampacity

When the power crossover wiring is done, make it 

so that the total of the MCA of the connected RB 

units and indoor units does not exceed the 15 A. 

For RB unit MCA, refer to the RB unit installation 

manual.

If the capacity of connected RB units and indoor 

units exceeds the upper limit, either add breakers 

or use a breaker with a greater capacity.

B. Ground Fault Equipment Breaker requirements

Breaker capacity

* Maximum connectable “indoor units” or “indoor 

units + RB units”

30 mA, 0.1 sec or less

44 or less

100 mA, 0.1 sec or less

45 to 148 **

*  Heat pump type: indoor units, Heat recovery type: indoor units and RB units.

**  If the 100 mA capacity breaker is not provided, split the quantity of the indoor units into 

small groups of 44 units or less and provide a breaker with capacity of 30 mA for each 

group.

6.1.1. Cable specifications

Recommended 

cable size (mm

2

)

Cable type

Remark

Power supply 

cable

2.5

Type60245 IEC57 or 

equivalent

2 Cable + earth 

(ground)

Transmission 

cable

0.33

LONWORKS com-

patible cable

22 AWG LEVEL 4 

(NEMA) non-polar 2 

core, twisted pair solid 

core diameter 0.65 mm

Remote control-

ler cable (2-wire 

type)

0.33 to 1.25

Sheathed PVC 

cable*

Non-polar 2 core, 

twisted pair

*: Use shielded cable in accordance with local rules for remote controller cable.

6.2.  Wiring  method

Example

*2

*2

*2

*3

*3

*3

Outdoor unit or RB unit *1

Transmission

Transmission

Indoor unit

Remote controller 

(Master)

Power supply

Indoor unit

Indoor unit

Power supply

Remote 

 control

Breaker

Breaker

Breaker

Remote controller 

(Slave)

Remote controller

*1:  When connecting to the Heat Recovery System, refer to the installation manual of the 

RB unit.

*2:  Earth (Ground) the remote controller if it has an earth (ground) cable.

*3:  The 3-wire type remote controller is not used.

(Crossover wiring of power supply)

Indoor unit

Pull box

Pull box

Power supply

Power supply

Power supply

Indoor unit

Indoor unit

Breaker

Power supply

6.3.  Unit  wiring

Before attaching the cable

 to terminal block.

6.3.1. Power supply cable

Adjust the length of power supply 

cable to avoid excessive tension 

with referring the figure.

Earth (Ground) 

cable

20 mm

50 mm

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable. 

(2)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. 

Do not use a screwdriver that is too small, otherwise, the screw heads may be dam-

aged and prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws 

may break.

(5)  See the table for the terminal screw tightening torques.

(6)  Please do not fix 2 power supply cables with 1 screw.

Strip 25 mm

Loop

Screw with 

special washer

Screw with 

special washer

Cable end (Loop)

Cable end (Loop)

Cable

Cable

Terminal block

 WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 

cables with the ring terminal, the ring terminal's pressure bonding may malfunction and 

cause the cables to abnormally heat up.

B. For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the figure below to connect to 

the ter

minal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. 

Do not use a screwdriver that is too small, otherwise, the screw heads may be dam-

aged and prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may brea

k.

(6)  See the table for the terminal screw tightening torques.

(7)  Please do not fix 2 power supply cables with 1 screw.

Strip 10 mm

 Sleeve

Screw with 

special washer

Screw with 

special washer

Ring terminal

Cable

Cable

Terminal block

Ring terminal

Ring terminal

 WARNING

Use ring terminals and tighten the terminal screws to the specified torques, otherwise, 

abnormal overheating may be produced and possibly cause heavy damage inside the 

unit.

Tightening torque

M4 screw (Power supply /L, N, GND)

1.2 to 1.8 N•m (12 to 18 kgf•cm)

9371022635-01_IM.indb   6

08/02/2019   17:03:18

Содержание AIRSTAGE AUXB004GLEH

Страница 1: ...ersonnel only INSTALLATIONSANLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВ...

Страница 2: ...ny substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leakage make sure that it does not exceed the concentration limit If a refrigerant leakage exceeds the concentration limit it can lead to accidents such as...

Страница 3: ...lorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be ge...

Страница 4: ...nging bolt position 540 Hanging bolt position 570 Indoor unit 135 250 150 to 200 Min 450 Service access 75 Min 450 A Cassette grille Unit mm Fig C B Ceiling openings Cassette grille Standard type Grid type A 700 620 B 580 to 660 580 to 610 40 102 99 30 58 123 30 40 146 245 262 Drain pipe O D ø25 4 Unit mm Fig D Ceiling Control box Liquid pipe Gas pipe Special nut A Special nut B Hook Hanging bolt ...

Страница 5: ...them anymore Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection When the flare nut is tightened properly by your hand hold the body side coupling with a separate spanner then tighten with a torque wrench See the table below for the flare nut tightening torq...

Страница 6: ...r Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoo...

Страница 7: ...over wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring the figure Earth Ground cable 20 mm 50 mm A For solid core wiring 1 To connect the electri...

Страница 8: ...AUTION Do not bundle the remote controller cable or wire the remote controller cable in parallel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 6 5 Optional parts wiring 6 5 1 Layout of the indoor unit PCB CAUTION Do not operate any switches other than prescribed as it can cause the unit to operate improperly or malfunction Use...

Страница 9: ...ress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected...

Страница 10: ...oor unit fan stop DC 12 V Indoor unit fan operation 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU ...

Страница 11: ... 1 02 Adjust 2 Heat air temperature trigger 31 00 Standard Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 To lower the trigger temperature by 4 degrees C use setting 02 To raise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage ...

Страница 12: ...ple ADDRESS 24 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0...

Страница 13: ...s and outlets free of any obstacles No cooling No heating Does start and stop air conditioner op eration by remote control unit or external device No operation After installation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote ...

Отзывы: