En-11

(2) 

Open the intake grille and remove.

8.2.  Install cassette grille to indoor unit

(1)  Install the cassette grille on the indoor unit.

“DRAIN” mark

“PIPE” mark

Align the stamped marks on the cassette grille against the pipe and the drain of the 

indoor unit.

 CAUTION

Use only the supplied screws to install the cassette grille.

Indoor unit

Ceiling

No gap between ceiling and cassette 

grille around entire periphery

5 to 7 mm

Cassette grille

Sealant 

(2)  Connect the connector.

Cable (louver): WHITE

Cable (display): WHITE

Cable (louver): RED

Indoor unit side

• Arrange the cables as illustrated below.

(3)  Attach the connector cover.

Screw

Connector cover

7.3.2. Checking the function settings

Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check 

the function settings. It is necessary to disconnect the power in order to return to normal 

operation mode.

(1) Indoor unit and refrigerant address indication

Indication pattern

Indicator lamp name

Indication pattern

Indoor unit address

Refrigerant address

OPERATION (Green)

ON

Flash (1.0s ON/1.0s OFF)

TIMER (Orange)

Address: tens place (0.5s ON/0.5s OFF)

FILTER (Red)

Address: ones place (0.5s ON/0.5s OFF)

• Indoor unit address example

(Example) ADDRESS : 24

OPERATION 

indicator lamp 

(Green)

TIMER 

indicator lamp 

(Orange)

FILTER 

indicator 

lamp (Red)

10 sec

1 cycle 12 sec

8 sec

ON

OFF

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

ON

• Refrigerant address example

(Example) ADDRESS : 30

OPERATION 

indicator lamp 

(Green)

TIMER 

indicator lamp 

(Orange)

FILTER 

indicator 

lamp (Red)

9 sec

1 cycle 12 sec

ON

OFF

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

OFF

• Setting details

Function number

Item

Setting number

01

Indoor unit address

00 to 63

02

Refrigeration address

00 to 99

For use with a remote controller, set all rotary switches to 0, and refer to “7.1. Setting the 

address” for details.

All switches are set to 0 at the factory.

(2) Others

Indication pattern

Indicator lamp

Indication pattern

OPERATION (Green)

Function number; tens place (0.5s ON/0.5s OFF)

TIMER (Orange)

Function number; ones place (0.5s ON/0.5s OFF)

FILTER (Red)

Setting number: (0 to 9) (0.5s ON/0.5s OFF)

(Example) Function : 31, Setting number : 2

OPERATION 

indicator lamp 

(Green)

TIMER 

indicator lamp 

(Orange)

FILTER 

indicator 

lamp (Red)

11 sec

10 sec

9 sec

1 cycle 12 sec

ON

OFF

0.5s 0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s 0.5s 0.5s

ON

OFF

ON

OFF

8.  CASSETTE GRILLE INSTALLATION

8.1.  Remove the intake grille

(1) 

Slide the 2 grille hook

Grille hook

Grille hook

Standard type

Grid type

9371022635-01_IM.indb   11

08/02/2019   17:03:31

Содержание AIRSTAGE AUXB004GLEH

Страница 1: ...ersonnel only INSTALLATIONSANLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВ...

Страница 2: ...ny substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leakage make sure that it does not exceed the concentration limit If a refrigerant leakage exceeds the concentration limit it can lead to accidents such as...

Страница 3: ...lorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be ge...

Страница 4: ...nging bolt position 540 Hanging bolt position 570 Indoor unit 135 250 150 to 200 Min 450 Service access 75 Min 450 A Cassette grille Unit mm Fig C B Ceiling openings Cassette grille Standard type Grid type A 700 620 B 580 to 660 580 to 610 40 102 99 30 58 123 30 40 146 245 262 Drain pipe O D ø25 4 Unit mm Fig D Ceiling Control box Liquid pipe Gas pipe Special nut A Special nut B Hook Hanging bolt ...

Страница 5: ...them anymore Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection When the flare nut is tightened properly by your hand hold the body side coupling with a separate spanner then tighten with a torque wrench See the table below for the flare nut tightening torq...

Страница 6: ...r Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoo...

Страница 7: ...over wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring the figure Earth Ground cable 20 mm 50 mm A For solid core wiring 1 To connect the electri...

Страница 8: ...AUTION Do not bundle the remote controller cable or wire the remote controller cable in parallel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 6 5 Optional parts wiring 6 5 1 Layout of the indoor unit PCB CAUTION Do not operate any switches other than prescribed as it can cause the unit to operate improperly or malfunction Use...

Страница 9: ...ress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected...

Страница 10: ...oor unit fan stop DC 12 V Indoor unit fan operation 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU ...

Страница 11: ... 1 02 Adjust 2 Heat air temperature trigger 31 00 Standard Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 To lower the trigger temperature by 4 degrees C use setting 02 To raise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage ...

Страница 12: ...ple ADDRESS 24 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0...

Страница 13: ...s and outlets free of any obstacles No cooling No heating Does start and stop air conditioner op eration by remote control unit or external device No operation After installation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote ...

Отзывы: