En-5

When lifting up drain:

• Height of inclined pipe should be less than 700 mm from the ceiling. A rise dimension 

over this range will cause leakage.

• Lift up the pipe vertically at the position of 300 mm or less from the unit.

VP25 (O.D. 32 mm) 

local arrangement

VP30 (O.D. 38 mm) or more 

Downward gradient 1/100 to 1/50

Downward gradient 

1/100 to 1/50

300 mm or less

700 mm or less

700 mm or less

Horizontal or 

upward gradient

Working procedure

(1)  Install the attached drain hose to the drain port of the body. Install the hose band 

from the top of the hose within the graphic display area. 

(2)  Use vinyl adhesive agent to glue the drain piping (PVC pipe VP25) which is prepared 

on site or elbow socket.

(3)   (Apply color adhesive agent evenly until the gauge line and seal)

(4) 

Check the drainage

. (See separate diagram)

(5)  Install the heat insulation.

(6)  Use the attached heat insulation to insulate the drain port and band parts of the body.

Install the knob 

faces upward

Locally arranged 

vinyl pipe

Attached drain hose 

(Accessories)

Attached heat insulation 

(Accessories)

Attached hose band 

(Accessories)

Drain hose

Hose band

20 mm

Transparent 

visible portion

5 to 10 mm

Applying area 

of adhesive 

Gauge line

Drain 

hose

4 mm or less

35 mm

Wind the attached heat insulation 

around the hose band

Make sure the 

alignment is on top

Make sure there 

are no gaps

(a) Top view

(b) Side view

(c) Hose opening view

(d) Top view

20 mm

NOTE:

 Check for drainage

Pour about 1 liter of water 

from the position shown in the 

diagram or from the airflow 

outlet to the dew tray. Check 

for any abnormalities such as 

strange noises and whether 

the drain pump functions 

normally.

Watering 

pot

Drain pipe

Wire cover

Screw

6.  ELECTRICAL  WIRING

 WARNING

Electrical work must be performed in accordance with this Manual by a person certified 

under the national or regional regulations. Be sure to use a dedicated circuit for the unit. 

An insufficient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or fire.
Before starting work, check that power is not being supplied to the all units.
For wiring, use the prescribed type of cables, connect them securely, making sure that 

there are no external forces of the cables applied to the terminal connections.

Improperly connected or secured cables can cause serious accidents such as overheat-

ing the terminals, electric shock, or fire.

Securely install the electrical box cover on the unit. 

An improperly installed electrical box cover can cause serious accidents such as electric 

shock or fire through exposure to dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 

could result.
Use the included connection cables and power cables or ones specified by the 

manufacturer. Improper connections, insufficient insulation, or exceeding the allowable 

current can cause electric shock or fire.

Do not modify the power cables, use extension cables, or use any branches in the wir-

ing. Improper connections, insufficient insulation, or exceeding the allowable current can 

cause electric shock or fire.
Match the terminal block numbers and connection cable colors with those of the outdoor 

unit (or RB unit). Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the 

cables with wiring holders. Improper connections, either in the wiring or at the ends of 

the wiring, can cause a malfunction, electric shock, or fire.

Always fasten the outside covering of the connection cable with the cable clamp. (If the 

insulator is chafed, electric discharge may occur.)

Install an earth leakage breaker. In addition, install the earth leakage breaker so that the 

entire AC main power supply is cut off at the same time. Otherwise, electric shock or fire 

could result.
Always connect the earth (ground) cable.

Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cables so as not to be direct touched with your hand.

Perform wiring work in accordance with standards so that the air conditioner can be 

operated safely and positively.
Connect the connection cable firmly to the terminal board. Imperfect installation may 

cause a fire.
If the supply cable is damaged, it must be replaced by the manufacturer, its service 

agent or similarly qualified persons in order to avoid a hazard.

 CAUTION

Earth (Ground) the unit. 

Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 

telephone earth (ground) cable. 

Improper earthing (grounding) may cause electric shock.

Do not connect power supply cables to the transmission or remote controller terminals, 

as this will damage the product.
Never bundle the power supply cable and transmission cable, remote control cable 

together.

Separate these cable by 50 mm or more.

Bundling these cables together will cause miss operation or breakdown.

When handling PCB, static electricity charged in the body may cause malfunction of the 

PCB. Follow the cautions below:

• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.

• 

Cut power (breaker) off.

• Touch metal part of the indoor units for more than 10 seconds to discharge static 

electricity charged in the body.

• Do not touch terminals of parts and patterns implemented on PCB.

6.1.  Electrical  requirement

• Select the power cable type and size 

in accordance with relevant local and 

national regulations.

Voltage rating

230 V

Operating range

198 to 264 V (50 Hz)

198 to 253 V (60 Hz)

• Specifications for local wiring power cord and branch wiring are in compliance with local 

code.

• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

9371022635-01_IM.indb   5

08/02/2019   17:03:12

Содержание AIRSTAGE AUXB004GLEH

Страница 1: ...ersonnel only INSTALLATIONSANLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВ...

Страница 2: ...ny substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leakage make sure that it does not exceed the concentration limit If a refrigerant leakage exceeds the concentration limit it can lead to accidents such as...

Страница 3: ...lorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be ge...

Страница 4: ...nging bolt position 540 Hanging bolt position 570 Indoor unit 135 250 150 to 200 Min 450 Service access 75 Min 450 A Cassette grille Unit mm Fig C B Ceiling openings Cassette grille Standard type Grid type A 700 620 B 580 to 660 580 to 610 40 102 99 30 58 123 30 40 146 245 262 Drain pipe O D ø25 4 Unit mm Fig D Ceiling Control box Liquid pipe Gas pipe Special nut A Special nut B Hook Hanging bolt ...

Страница 5: ...them anymore Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection When the flare nut is tightened properly by your hand hold the body side coupling with a separate spanner then tighten with a torque wrench See the table below for the flare nut tightening torq...

Страница 6: ...r Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoo...

Страница 7: ...over wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring the figure Earth Ground cable 20 mm 50 mm A For solid core wiring 1 To connect the electri...

Страница 8: ...AUTION Do not bundle the remote controller cable or wire the remote controller cable in parallel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 6 5 Optional parts wiring 6 5 1 Layout of the indoor unit PCB CAUTION Do not operate any switches other than prescribed as it can cause the unit to operate improperly or malfunction Use...

Страница 9: ...ress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected...

Страница 10: ...oor unit fan stop DC 12 V Indoor unit fan operation 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU ...

Страница 11: ... 1 02 Adjust 2 Heat air temperature trigger 31 00 Standard Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 To lower the trigger temperature by 4 degrees C use setting 02 To raise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage ...

Страница 12: ...ple ADDRESS 24 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0...

Страница 13: ...s and outlets free of any obstacles No cooling No heating Does start and stop air conditioner op eration by remote control unit or external device No operation After installation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote ...

Отзывы: