6.5.3. Connection methods

Wire modification for External 

input/output wire

(1)  Remove insulation from wire at-

tached to wire kit connector.

(2)  Remove insulation from field 

supplied cable. Use crimp type 

insulated butt connector to join field 

cable and wire kit wire.

(3)  Connect the wire with connecting 

wire with solder.

IMPORTANT:

Be sure to insulate the connection between the 

wires.

Locally 

purchased

Solder and insulate the connected parts.

Wire kit connector 

(optional parts)

Wiring arrangement

In following figure, all the possible connectors are connected for description.

In actual installation, you cannot connect all the connectors at once.

Cable tie (locally purchased): 

Bind to the transmission cable

Transmission cable

6.6.  External input and external output (Optional parts)

(1) External input

• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit 

PCB CNA01 or CNA02.

• 

“Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected 

with function setting of indoor unit.

• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.

• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.

• Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

• The wire connection should be separate from the power cable line.

Input select

Use either one of these types of terminal according to the application. (Both types of 

terminals cannot be used simultaneously.)

● Apply voltage terminal ([CNA01], [CNA03])

When a power supply must be provided at the input device you want to connect, use the 

Apply voltage terminal ([CNA01], [CNA03]).

In

pu

de

vi

ce 1

In

pu

de

vi

ce 2

In

pu

de

vi

ce 3

Load resis-

tance

Load resis-

tance

Load resis-

tance

*1

DC power supply 

12 to 24V

connected unit

*a

*a

*a

P.C.B

CNA01

CNA03

*b

*1 

Make the power supply DC12 to 24V. Select a power supply capacity with an ample sur

-

plus for the connected load.

Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.

*a  The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)

 

Provide a load resistance such that the current becomes DC10mA or less.

 

Select very low current use contacts (usable at DC12V, DC1mA or less).

*b   The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.

When connected to Apply voltage terminals of multiple indoor units with a connected unit, 

be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 

example.

DC power supply 

12 to 24V

connected unit

Load resis-

tance

P.C.B

P.C.B

CNA01

P.C.B

In

pu

de

vi

ce 1

In

pu

de

vi

ce 2

In

do

or

 uni

t

In

do

or

 uni

t

In

do

or

 uni

t

Load resis-

tance

CNA01

CNA01

● Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 

contact terminal ([CNA02], [CNA04]).

P.C.B

GND

Ch 1

Ch 3

*c

*c

*c

*d

Ch 2

CNA02

CNA04

connected unit

*c  Select very low current use contacts (usable at DC12V, DC1mA or less).

*d  The wiring is different from Apply voltage terminals. Be sufficiently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, 

insulate each indoor unit with relay, etc. as shown on below example.

P

ow

er s

up

pl

y f

or r

el

ay

In

do

or

 uni

t

In

do

or

 uni

t

In

do

or

 uni

t

Input device 2

Input device 1

K1 - K6: Relay

(Device for DC Current)

P.C.B

K1

P.C.B

P.C.B

CNA02

K2

K3

K4

K5

K6

CNA02

CNA02

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

● Input signal type

The input signal type can be selected.

It is switched by DIP switch on the indoor unit PCB. 

Pulse

The width of pulse 

must be longer than 

200msec.

Edge

DIP switch [Set 2 SW2]

Input signal type

OFF (Factory setting)

Edge

ON

Pulse

● When function setting is “Operation/Stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF → ON

Operation

ON → OFF

Stop

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF → ON

Operation

Ch2

OFF → ON

Stop

*  The last command has priority.

*  The indoor units within the same remote controller group operates in the same mode.

9371022635-01_IM.indb   8

08/02/2019   17:03:26

Содержание AIRSTAGE AUXB004GLEH

Страница 1: ...ersonnel only INSTALLATIONSANLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВ...

Страница 2: ...ny substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leakage make sure that it does not exceed the concentration limit If a refrigerant leakage exceeds the concentration limit it can lead to accidents such as...

Страница 3: ...lorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be ge...

Страница 4: ...nging bolt position 540 Hanging bolt position 570 Indoor unit 135 250 150 to 200 Min 450 Service access 75 Min 450 A Cassette grille Unit mm Fig C B Ceiling openings Cassette grille Standard type Grid type A 700 620 B 580 to 660 580 to 610 40 102 99 30 58 123 30 40 146 245 262 Drain pipe O D ø25 4 Unit mm Fig D Ceiling Control box Liquid pipe Gas pipe Special nut A Special nut B Hook Hanging bolt ...

Страница 5: ...them anymore Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection When the flare nut is tightened properly by your hand hold the body side coupling with a separate spanner then tighten with a torque wrench See the table below for the flare nut tightening torq...

Страница 6: ...r Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoo...

Страница 7: ...over wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring the figure Earth Ground cable 20 mm 50 mm A For solid core wiring 1 To connect the electri...

Страница 8: ...AUTION Do not bundle the remote controller cable or wire the remote controller cable in parallel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 6 5 Optional parts wiring 6 5 1 Layout of the indoor unit PCB CAUTION Do not operate any switches other than prescribed as it can cause the unit to operate improperly or malfunction Use...

Страница 9: ...ress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected...

Страница 10: ...oor unit fan stop DC 12 V Indoor unit fan operation 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU ...

Страница 11: ... 1 02 Adjust 2 Heat air temperature trigger 31 00 Standard Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 To lower the trigger temperature by 4 degrees C use setting 02 To raise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage ...

Страница 12: ...ple ADDRESS 24 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0...

Страница 13: ...s and outlets free of any obstacles No cooling No heating Does start and stop air conditioner op eration by remote control unit or external device No operation After installation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote ...

Отзывы: