background image

En-3

H: Maximum height from floor to ceiling

Model name

H (mm)

AUXB004 AUXB007 AUXB009 AUXB012 AUXB014 AUXB018 AUXB024

Standard mode

2,700

2,700

2,700

2,700

2,700

2,700

2,700

High Ceiling 

mode

-

-

-

3,000

3,000

3,000

3,000

Be sure to make the function settings with the remote controller according to the 

installed ceiling height.

3.3.  Discharge direction setting

The discharge direction can be selected as shown below.

(4 directions)

(3 directions)

100 or more

Unit: mm

Fig. B

Piping position

*  Select the most appropriate airflow 

direction from 3 or 4 directions according 

to the shape of the room and the instal-

lation position.

*  When changing the number of outlets, 

we recommend using the optional AIR 

OUTLET SHUTTER PLATE KIT to close 

the outlet.

*  For the specific closing pattern, please 

refer to the attached AIR OUTLET 

SHUTTER PLATE KIT’S MANUAL. (Do 

so before installing the cassette grille as 

it will be installed on the body.)

3.4.  Installing the unit

 WARNING

Install the air conditioner in a location which can withstand a load of at least 5 times the 

weight of the main unit and which will not amplify sound or vibration. If the installation 

location is not strong enough, the indoor unit may fall and cause injuries.

If the job is done with the panel frame only, there is a risk that the unit will come loose. 

Please take care.
When fastening the hangers, make the bolt positions uniform.

Perform final tightening by tightening the double nut firmly. The product may fall if not 

installed properly.
Using a level, or vinyl hose filled with water, fine adjust so that the body is level.

Install the air conditioner as follows.

Indoor unit installation

(1) 

Make the holes for installing in the ceiling (Fig. D).

(2)  Install the hanging bolts (M10), refer to the position in Fig. C.

(3)  Install special nut A, then special nut B onto the hanging bolt (Fig. D).

(4) 

Raise the body and mount its hooks onto the hanging bolt between the special nuts.

(5)  Turn special nut B to adjust the height of the body.

(6)  Be sure to leave service access for future service at the designated position.

530 (Hanging bolt position)

540 (Hanging bolt position)

 570 (Indoor unit)

135

250

150 to 200

Min. 450

Service access

75

Min. 450

A

 (Cassette grille)

Unit: mm

Fig. C

B

 (Ceiling openings)

Cassette grille

Standard 

type

Grid type

A

 700

 620

B

 580 to 660  580 to 610

40

102

99

30

58

123

30

40

146

245

262

Drain pipe (O.D. ø25.4)

Unit: mm

Fig. D

Ceiling

Control box

Liquid pipe

Gas pipe

Special nut A

Special nut B

Hook

Hanging bolt

30 or more
After installing the body, 

tighten the nuts.

19

Ceiling

Indoor unit

Leveling

• Using a level, or vinyl hose 

filled with water, fine adjust 

so that the body is level.

• Inclined installation so 

as the drain pipe side 

is higher may cause a 

malfunction of the float 

switch, and may cause 

water leakage.

Vinyl hoses

Drain pipe

4.  PIPE  INSTALLATION

 CAUTION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 

refrigerant R410A models. Also, when storing the piping, securely seal the openings by 

pinching, taping, etc.
While welding the pipes, be sure to blow dry nitrogen gas through them.

4.1.  Selecting the pipe material

 CAUTION

Do not use existing pipes from another refrigeration system or refrigerant.
Use pipes that have clean external and internal sides without any contamination which 

may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.

Material : Phosphor deoxidized seamless copper pipes

It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion (es-

pecially on the interior surface). Otherwise, the expansion valve or capillary tube may 

become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 

incurs pressure higher than when using conventional (R22) refrigerant, it is necessary to 

choose adequate materials.

• 

Thicknesses of copper pipes used with R410A are as shown in the table.

• Never use copper pipes thinner than those indicated in the table even if they are avail-

able on the market.

Thicknesses of 

Annealed Copper 

Pipes (R410A)

Pipe outside diameter [mm (in)]

Thickness [mm]

6.35 (1/4)

0.80

9.52 (3/8)

0.80

12.70 (1/2)

0.80

15.88 (5/8)

1.00

19.05 (3/4)

1.20

9371022635-01_IM.indb   3

08/02/2019   17:03:08

Содержание AIRSTAGE AUXB004GLEH

Страница 1: ...ersonnel only INSTALLATIONSANLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВ...

Страница 2: ...ny substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leakage make sure that it does not exceed the concentration limit If a refrigerant leakage exceeds the concentration limit it can lead to accidents such as...

Страница 3: ...lorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be ge...

Страница 4: ...nging bolt position 540 Hanging bolt position 570 Indoor unit 135 250 150 to 200 Min 450 Service access 75 Min 450 A Cassette grille Unit mm Fig C B Ceiling openings Cassette grille Standard type Grid type A 700 620 B 580 to 660 580 to 610 40 102 99 30 58 123 30 40 146 245 262 Drain pipe O D ø25 4 Unit mm Fig D Ceiling Control box Liquid pipe Gas pipe Special nut A Special nut B Hook Hanging bolt ...

Страница 5: ...them anymore Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection When the flare nut is tightened properly by your hand hold the body side coupling with a separate spanner then tighten with a torque wrench See the table below for the flare nut tightening torq...

Страница 6: ...r Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoo...

Страница 7: ...over wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring the figure Earth Ground cable 20 mm 50 mm A For solid core wiring 1 To connect the electri...

Страница 8: ...AUTION Do not bundle the remote controller cable or wire the remote controller cable in parallel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 6 5 Optional parts wiring 6 5 1 Layout of the indoor unit PCB CAUTION Do not operate any switches other than prescribed as it can cause the unit to operate improperly or malfunction Use...

Страница 9: ...ress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected...

Страница 10: ...oor unit fan stop DC 12 V Indoor unit fan operation 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU ...

Страница 11: ... 1 02 Adjust 2 Heat air temperature trigger 31 00 Standard Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 To lower the trigger temperature by 4 degrees C use setting 02 To raise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage ...

Страница 12: ...ple ADDRESS 24 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0...

Страница 13: ...s and outlets free of any obstacles No cooling No heating Does start and stop air conditioner op eration by remote control unit or external device No operation After installation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote ...

Отзывы: