background image

NOTES

When running general-purpose motors

 Driving a 460V general-purpose motor

When driving a 400V general-purpose motor with 
an inverter using extremely long cables, damage to 
the insulation of the motor may occur. Use an 
output circuit filter (OFL) if necessary after checking 
with the motor manufacturer. Fuji's motors do not 
require the use of output circuit filters because of 
their reinforced insulation.

 Torque characteristics and temperature rise

When the inverter is used to run a general-purpose 
motor, the temperature of the motor becomes 
higher than when it is operated using a commercial 
power supply. In the low-speed range, the cooling 
effect will be weakened, so decrease the output 
torque of the motor. If constant torque is required in 
the low-speed range, use a Fuji inverter motor or a 
motor equipped with an externally powered 
ventilating fan.

 Vibration

When the motor is mounted to a machine, 
resonance may be caused by the natural 
frequencies, including that of the machine. 
Operation of a 2-pole motor at 60Hz or more may 
cause abnormal vibration.
* Study use of tier coupling or dampening rubber.
* It is also recommended to use the inverter jump 

frequency control to avoid resonance points.

 Noise

When an inverter is used with a general-purpose 
motor, the motor noise level is higher than that with 
a commercial power supply. To reduce noise, raise 
carrier frequency of the inverter. High-speed 
operation at 60Hz or more can also result in more 
noise.

When running special motors

 High-speed motors

When driving a high-speed motor while setting the 
frequency higher than 120Hz, test the combination 
with another motor to confirm the safety of high-
speed motors.

 Explosion-proof motors

When driving an explosion-proof motor with an 
inverter, use a combination of a motor and an 
inverter that has been approved in advance.

 Submersible motors and pumps

These motors have a larger rated current than 
general-purpose motors. Select an inverter whose 
rated output current is greater than that of the 
motor.
These motors differ from general-purpose motors in 
thermal characteristics. Set a low value in the 
thermal time constant of the motor when setting the 
electronic thermal facility.

 Brake motors

For motors equipped with parallel-connected 
brakes, their braking power must be supplied from 
the primary circuit (commercial power supply). If the 
brake power is connected to the inverter power 
output circuit (secondary circuit) by mistake, 
problems may occur.
Do not use inverters for driving motors equipped 
with series-connected brakes.

 Geared motors

If the power transmission mechanism uses an oil-

lubricated gearbox or speed changer/reducer, then 
continuous motor operation at low speed may 
cause poor lubrication. Avoid such operation.

 Synchronous motors

It is necessary to use software suitable for this 
motor type. Contact Fuji for details.

 Single-phase motors

Single-phase motors are not suitable for inverter-
driven variable speed operation. Use three-phase 
motors.
* Even if a single-phase power supply is available, 
use a three-phase motor as the inverter provides 
three-phase output.

Environmental conditions

 Installation location

Use the inverter in a location with an ambient 
temperature range of -10 to 50

˚

C(14 to 122

˚

F).

The inverter and braking resistor surfaces become 
hot under certain operating conditions. Install the 
inverter on nonflammable material such as metal.
Ensure that the installation location meets the 
environmental conditions specified in "Environment" 
in inverter specifications.

Combination with peripheral devices

 Installing a molded case circuit 

breaker (MCCB)

Install a recommended molded case circuit breaker 
(MCCB) or a groud-fault circuit interrupter (GFCI) in 
the primary circuit of each inverter to protect the 
wiring. Ensure that the circuit breaker capacity is 
equivalent to or lower than the recommended 
capacity.

 Installing a magnetic contactor (MC) 

in the output (secondary) circuit

If a magnetic contactor (MC) is mounted in the 
inverter's secondary circuit for switching the motor 
to commercial power or for any other purpose, 
ensure that both the inverter and the motor are fully 
stopped before you turn the MC on or off. Remove 
the surge killer integrated with the MC.

 Installing a magnetic contactor (MC) 

in the input (primary) circuit

Do not turn the magnetic contactor (MC) in the 
primary circuit on or off more than once an hour as 
an inverter fault may result. If frequent starts or 
stops are required during motor operation, use 
FWD/REV signals.

 Protecting the motor

The electronic thermal facility of the inverter can 
protect the motor. The operation level and the motor 
type (general-purpose motor, inverter motor) should 
be set. For high-speed motors or water-cooled 
motors, set a small value for the thermal time 
constant to protect the motor.
If you connect the motor thermal relay to the motor 
with a long cable, a high-frequency current may 
flow into the wiring stray capacitance. This may 
cause the relay to trip at a current lower than the 
set value for the thermal relay. If this happens, 
lower the carrier frequency or use the output circuit 
filter (OFL).

 Discontinuance of power-factor correcting capacitor

Do not mount power factor correcting capacitors in 
the inverter (primary) circuit. (Use the DC 
REACTOR to improve the inverter power factor.) Do 

not use power factor correcting capacitors in the 
inverter output circuit (secondary). An overcurrent 
trip will occur, disabling motor operation.

 Discontinuance of surge killer

Do not mount surge killers in the inverter output 
(secondary) circuit.

 Reducing noise

Use of a filter and shielded wires are typical 
measures against noise to ensure that EMC 
Directives are met. 

 Measures against surge currents

If an overvoltage trip occurs while the inverter is 
stopped or operated under a light load, it is 
assumed that the surge current is generated by 
open/close of the phase-advancing capacitor in the 
power system.
We recommend connecting a DC REACTOR to the 
inverter.

 Megger test

When checking the insulation resistance of the 
inverter, use a 500V megger and follow the 
instructions contained in the Instruction Manual.

Wiring

 Wiring distance of control circuit

When performing remote operation, use the twisted 
shield wire and limit the distance between the 
inverter and the control box to 65.6ft(20m).

 Wiring length between inverter and motor

If long wiring is used between the inverter and the 
motor, the inverter will overheat or trip as a result of 
overcurrent (high-frequency current flowing into the 
stray capacitance) in the wires connected to the 
phases. Ensure that the wiring is shorter than 
164ft(50m). If this length must be exceeded, lower 
the carrier frequency or mount an output circuit filter 
(OFL).

 Wiring size

Select cables with a sufficient capacity by referring 
to the current value or recommended wire size.

 Wiring type

Do not use multicore cables that are normally used 
for connecting several inverters and motors.

 Grounding

Securely ground the inverter using the grounding 
terminal.

Selecting inverter capacity

 Driving general-purpose motor

Select an inverter according to the applicable motor 
ratings listed in the standard specifications table for 
the inverter. When high starting torque is required 
or quick acceleration or deceleration is required, 
select an inverter with a capacity one size greater 
than the standard.

 Driving special motors

Select an inverter that meets the following condition:
Inverter rated current > Motor rated current.

Transportation and storage

When transporting or storing inverters, follow the 
procedures and select locations that meet the 
environmental conditions that agree with the 
inverter specifications.

Printed in Japan 2007-7 (G07/G07) CM 30 FIS

Printed on 100% recycled paper

Fuji Electric Corp. of America

Information in this catalog is subject to change without notice.

47520 Westinghouse Drive Fremont, CA 94539, U.S.A.

Tel.+1-510-440-1060 Fax.+1-510-440-1063

http://www.fujielectric.com

Содержание FRN001E1E-2U

Страница 1: ...MEH531 High Performance Compact Inverters...

Страница 2: ...kes it possible to reduce the effect on peripheral equipment The design life of each internal component with limited life has been extended to 10 years This helps to extend the maintenance cycle for y...

Страница 3: ...dhorizontalconveyance Impacts are detected mechanically and not only can the inverter s operation pattern be set on coast to stop or deceleration stop but switching from torque limitation to current l...

Страница 4: ...oequipmentmaintenanceisdisplayed Detailed information can be checked for the four most recent alarms The alarm history records the latest four incidents Item Purpose Motor cumulative running time hr N...

Страница 5: ...direction and operation of the fan is picked up to start the fan smoothly This function is convenient in such cases as when switching instantaneously from commercial power supply to the inverter Equip...

Страница 6: ...or and have two communications ports Complies with standards Sink Source switchable Wide voltage range The multi function keypad displays multiple languages Japanese English German French Spanish Ital...

Страница 7: ...4U FRN015E1E 4U FRN020E1E 4U Semi standard type EMC filter built in type FRNF12E1E 7U FRNF25E1E 7U FRNF50E1E 7U FRN001E1E 7U FRN002E1E 7U FRN003E1E 7U Three phase 230V Three phase 460V Single phase 23...

Страница 8: ...ated current 150 Built in Three phase 230V 1 8 to 20HP Three phase 460V 1 2 to 20HP Standard type 1 Fuji s 4 pole standard motor 2 Rated capacity is calculated by assuming the output rated voltage as...

Страница 9: ...oling method EMC standard Emission compliance Immunity Weight Mass lbs kg Rated capacity kVA 2 Rated voltage V 3 Rated current A 4 Overload capability Rated frequency Hz Phases voltage frequency Volta...

Страница 10: ...is set the time setting is cancelled and acceleration and deceleration is made according to the pattern given with an external signal Acceleration and deceleration time can be independently set with...

Страница 11: ...e number of pulses to the stop position and deceleration point Select either of reverse prevention or forward rotation prevention The life early warning of the main circuit capacitors capacitors on th...

Страница 12: ...6 5 0 28 7 0 26 6 5 W D D1 D2 C elongated hole 0 2 5 0 24 6 H1 0 24 6 H C Name plate W1 0 24 6 0 24 6 W H1 0 24 6 0 24 6 H 0 2 5 0 2 5 D2 D1 D C Name plate W1 0 31 8 0 31 8 W H1 0 31 8 0 28 7 H 2 R0 1...

Страница 13: ...6 3 82 97 3 82 97 5 04 128 6 46 164 7 72 196 2 64 67 3 82 97 5 04 128 4 72 120 5 12 130 7 09 180 8 66 220 10 24 260 5 12 130 5 12 130 7 09 180 8 66 220 10 24 260 4 72 120 5 12 130 7 09 180 4 33 110 4...

Страница 14: ...97 0 26 6 5 0 26 6 5 W D D1 D2 H H1 4 65 118 0 24 6 0 24 6 3 5 89 D3 0 41 10 5 4 0 2 06 4 5x7 elongated hole 0 36 92 0 2 5 D3 1 06 27 0 41 10 5 W 6 61 168 H H1 7 48 190 5 04 128 0 24 6 0 24 6 0 24 6...

Страница 15: ...4 33 110 5 51 140 7 15 181 5 8 66 220 3 15 80 4 33 110 5 51 140 4 72 120 7 09 180 11 22 285 13 78 357 5 12 130 7 09 180 11 22 285 13 07 332 4 72 120 5 12 130 7 09 180 6 69 170 9 65 245 7 09 180 9 65 2...

Страница 16: ...urs during operation the lamp is unlit during keypad operation and lit during terminal block operation LED monitor When the motor is running or stopped The monitor displays speeds such as output frequ...

Страница 17: ...when installing a coil such as the MC or solenoid near the inverter Note4 THR function can be used by assigning code 9 external alarm to any of the terminals X1 to X5 FWD or REV function code E01 to...

Страница 18: ...and the motor coasts to stop ON across Hz2 Hz1 and CM Freq set 2 is effective ON across M2 M1 and CM The motor 2 setting is available OFF across M2 M1 and CM The motor 1 setting is available ON across...

Страница 19: ...for PC loader Analog monitor Pulse monitor Transistor output power Transistor output 1 Transistor output 2 Inverter running Inverter output on Speed freq arrival Speed freq detection Undervoltage dete...

Страница 20: ...FRN007E1 4U FRN010E1 4U FRN015E1 4U FRN020E1 4U FRNF12E1 7U FRNF25E1 7U FRNF50E1 7U FRN001E1 7U FRN002E1 7U FRN003E1 7U Fig A Fig B Fig B Fig C Fig C Fig D Fig E Three phase 230V Single phase 230V Thr...

Страница 21: ...r connection between the control board and power source board or interface board or short circuit between terminals between 13 and 11 is detected Simulated alarm is output to check the fault sequence...

Страница 22: ...tput frequency 2 after slip compensation 2 Output current 3 Output voltage 4 Output torque 5 Load factor 6 Input power 7 PID feedback amount PV 8 PG feedback value 9 DC link bus voltage 10 Universal A...

Страница 23: ...Y2 and 30A B C as listed below 0 1000 Inverter running RUN 1 1001 Frequency arrival signal FAR 2 1002 Frequency detected FDT 3 1003 Undervoltage detected Inverter stopped LU 4 1004 Torque polarity de...

Страница 24: ...mode Menus 0 and 1 1 Function code data check mode Menu 2 2 Full menu mode Menus 0 through 6 0 Current input C1 function 4 to 20 mADC 1 Voltage input V2 function 0 to 10 VDC Selecting function code d...

Страница 25: ...0 0 00 0 00 0 00 0 00 0 00 0 00 0 2 0 0 100 0 0 05 100 0 1 0 0 100 0 0 05 100 0 0 0 100 0 0 05 100 0 0 00 0 00 0 00 0 Hysteresis width offset Gain Filter time constant Gain base point Polarity offset...

Страница 26: ...0 Disable Always in operation 1 Enable ON OFF controllable 0 Linear 1 S curve Weak 2 S curve Strong 3 Curvilinear 0 Disable 1 Enable Reverse rotation inhibited 2 Enable Forward rotation inhibited 0 Di...

Страница 27: ...motor with separately powered cooling fan 0 00 Disable 1 to 135 of the rated current allowable continuous drive current of the motor 0 5 to 75 0 0 0 to 60 0 Hz 0 to 100 0 00 Disable 0 01 to 30 00 0 1...

Страница 28: ...Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y 0 0 0 100 0 0 0 00 0 5 200 0 100 0 999 999 0 10 0 0 0 100 0 0 0 00 0 0 100 0 0 0 100 1 0 1 0 1 0 1 0 Pole kW HP A A s Hz 2 0 01 0 01 0 01 0 01...

Страница 29: ...5 link Loader Follow H30 and y98 data 2 Follow H30 and y98 data Via RS 485 link Loader 3 Via RS 485 link Loader Via RS 485 link Loader 1 0 1 1 0 01 1 0 1 1 0 01 s s s s s s Y Y Y Y Y Y Y Y Y Y Y Y Y Y...

Страница 30: ...4 Writing function code allocation 5 Writing function code allocation 6 Writing function code allocation 7 Writing function code allocation 8 Read function code allocation 1 Read function code alloca...

Страница 31: ...g reactor is not used in the thyristors transformer it is necessary to connect an AC reactor on the inverter s input side and so be sure to verify that this is done 3 Used to prevent tripping in cases...

Страница 32: ...55 140 55 37 55 75 50 55 140 55 38 55 75 50 55 45 30 20 20 10 45 30 20 20 10 45 30 250 133 73 50 75 20 10 250 133 73 50 75 20 10 250 133 73 50 0 06 0 044 0 09 0 068 0 10 0 075 0 10 0 077 0 12 0 093 0...

Страница 33: ...1 5 2x8 0 20x0 31 5 2x8 0 20x0 31 5 2x8 0 24x0 43 6x11 0 24x0 43 6x11 0 24x0 43 6x11 0 28x0 43 7x11 0 28x0 43 7x11 0 28x0 43 7x11 0 20x0 31 5 2x8 0 20x0 31 5 2x8 0 20x0 31 5 2x8 0 24x0 35 6x9 0 24x0 3...

Страница 34: ...generator PG RS 485 communication card OPC F1 RS Connection with a host master device such as PC or PLC allows you to control FRENIC Multi as a subordinate slave device The card is added to the RS 485...

Страница 35: ...the cooling effect and to make the panel more compact 0 44 11 3 0 31 7 8 29 5 75 5 04 128 7 09 180 0 28 7 6 69 170 Optional type Applicable inverter type Previous inverter type FRNF12E1S 2U FRNF25E1S...

Страница 36: ...verter type With DCR Without DCR With DCR Without DCR With DCR Without DCR Output circuit MCCB GFCI rated current A Magnetic contactor MC Input circuit Inverter output U V W DC Reactor P1 P DC Reactor...

Страница 37: ...is difficult to provide repairs or supply spare parts even within this 7 year period For details please confirm at our company s business office or our service office 3 Repair Period after Production...

Страница 38: ...MEMO...

Страница 39: ...MEMO...

Страница 40: ...g a magnetic contactor MC in the output secondary circuit If a magnetic contactor MC is mounted in the inverter s secondary circuit for switching the motor to commercial power or for any other purpose...

Отзывы: