F codes: Fundamental Functions
●
E codes: Extension Terminal Functions
Terminal X1 function
Terminal X2 function
Terminal X3 function
Terminal X4 function
Terminal X5 function
Selecting function code data assigns the corresponding function to
terminals [X1] to [X5] as listed below.
0 (1000)
: Select multi-frequency
[SS1]
1 (1001)
: Select multi-frequency
[SS2]
2 (1002)
: Select multi-frequency
[SS4]
3 (1003)
: Select multi-frequency
[SS8]
4 (1004)
: Select ACC/DEC time
[RT1]
6 (1006)
: Enable 3-wire operation
[HLD]
7 (1007)
: Coast to a stop
[BX]
8 (1008)
: Reset alarm
[RST]
9 (1009)
: Enable external alarm trip
[THR]
10 (1010)
: Ready for jogging
[JOG]
11 (1011)
: Select frequency command 2/1
[Hz2/Hz1]
12 (1012)
: Select motor 2/motor 1
[M2/M1]
13
: Enable DC braking
[DCBRK]
14 (1014)
: Select torque limiter level
[TL2/TL1]
17 (1017)
: UP (Increase output frequency)
[UP]
18 (1018)
: DOWN (Decrease output frequency)
[DOWN]
19 (1019)
: Enable data change with keypad
[WE-KP]
20 (1020)
: Cancel PID control
[Hz/PID]
21 (1021)
: Switch normal/inverse operation
[IVS]
24 (1024)
: Enable communications link via RS-485 or field bus
[LE]
25 (1025)
: Universal DI
[U-DI]
26 (1026)
: Enable auto search for idling motor speed at starting [STM]
27 (1027)
: Speed feedback control switch
[PG/Hz]
30 (1030)
: Force to stop
[STOP]
33 (1033)
: Reset PID integral and differential components [PID-RST]
34 (1034)
: Hold PID integral component
[PID-HLD]
42 (1042)
: Position control limit switch
[LS]
43 (1043)
: Position control start/reset command
[S/R]
44 (1044)
: Serial pulse Receive mode
[SPRM]
45 (1045)
: Position Control return mode
[RTN]
46 (1046)
: Overload stopping effective command
[OLS]
Setting the value of 1000s in parentheses ( ) shown above assigns a negative logic input to a terminal.
Note: In the case of THR and STOP , data (1009) and (1030) are for normal logic, and "9" and "30" are
for negative logic, respectively.
-
-
-
-
-
-
-
-
-
-
Y
Y
Y
Y
Y
0
1
2
7
8
Current Limiter
Electronic Thermal
Overload Protection
for braking resistor
(Mode selection)
(Level)
(Discharging capability)
(Allowable average loss)
0: Disable (No current limiter works.)
1: Enable at constant speed (Disable during ACC/DEC)
2: Enable during ACC/constant speed operation
20 to 200
(The data is interpreted as the rated output current of the inverter for 100%.)
1 to 900 999: Disable
0: Reserved
0.001 to 50.000 0.000: Reserved
2
180
999
0.000
(Limiting Level for driving)
(Limiting Level for braking)
20 to 200 999 : Disable
20 to 200 999 : Disable
Selecting function code data assigns the corresponding function to terminals [Y1], [Y2], and [30A/B/C] as listed below.
0 (1000)
: Inverter running
[RUN]
1 (1001)
: Frequency arrival signal
[FAR]
2 (1002)
: Frequency detected
[FDT]
3 (1003)
: Undervoltage detected (Inverter stopped)
[LU]
4 (1004)
: Torque polarity detected
[B/D]
5 (1005)
: Inverter output limiting
[IOL]
6 (1006)
: Auto-restarting after momentary power failure
[IPF]
7 (1007)
: Motor overload early warning
[OL]
10 (1010)
: Inverter ready to run
[RDY]
21 (1021)
: Frequency arrival signal 2
[FAR2]
22 (1022)
: Inverter output limiting with delay
[IOL2]
26 (1026)
: Auto-resetting
[TRY]
28 (1028)
: Heat sink overheat early warning
[OH]
30 (1030)
: Service lifetime alarm
[LIFE]
33 (1033)
: Reference loss detected
[REF OFF]
35 (1035)
: Inverter output on
[RUN2]
36 (1036)
: Overload prevention control
[OLP]
37 (1037)
: Current detected
[ID]
38 (1038)
: Current detected 2
[ID2]
42 (1042)
: PID alarm
[PID-ALM]
49 (1049)
: Switched to motor 2
[SWM2]
57 (1057)
: Brake signal
[BRKS]
76 (1076)
: PG error signal
[PG-ERR]
80 (1080) : Over traveling
[OT]
81 (1081) : Time up of the start timer or the end timer
[TO]
82 (1082)
: Completion of positioning
[PSET]
83 (1083)
: Current position pulse overflow
[POF]
99 (1099)
: Alarm output (for any alarm)
[ALM]
Setting the value of 1000s in parentheses ( ) shown above assigns a negative logic input to a terminal.
1
1
-
-
-
%
%
-
-
-
Y
Y
Y
Y
Y
999
999
0
7
99
0.01
0.01
Y
Y
10.0
10.0
s
s
0.00 to 3600 Note: Entering 0.00 cancels the acceleration time, requiring external soft-start.
0.00 to 3600 Note: Entering 0.00 cancels the acceleration time, requiring external soft-start.
Acceleration Time 2
Deceleration Time 2
Torque
Limiter 2
Terminal [Y1] Function
Terminal [Y2] Function
Terminal [30A/B/C] Function
Func.
Code
Data
copy
*
2
Name
Data setting range
Default
setting
Min.
Unit
Func.
Code
Data
copy
*
2
Name
Data setting range
Default
setting
Min.
Unit
-
1
1
0.001
-
%
kWs
kW
Y
Y
Y
Y
*1 When you make settings from the keypad, the incremental unit is restricted by the number of
digits that the LED monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is as follows:
"1" for -200 to -100, "0.1" for -99.9 to -10.0, "0.01" for -9.99 to -0.01, "0.01" for 0.00 to 99.99,
and "0.1" for 100.0 to 200.0
*2 Symbols in the "Data copy" column
Y: Will be copied unconditionally.
Y1: Will not be copied if the rated capacity differs from the source inverter.
Y2: Will not be copied if the rated input voltage differs from the source inverter.
N: Will not be copied.
*3 Reserved for the maker. Do not set any data.
<Changing, validating, and saving function code data when the motor is running>
: Impossible, : Possible (Change data with keys and then
save/validate it with key), : Possible (Change and validate data with
keys and then save it with key)