69 TN5FCXA2VG-E
(
Save the setting
)
(
Cancel the setting
)
M
M
J-3 SPEC : Selection of the burnout & saturation cur-
rent value specification
(CUSTOM / NA-
MUR setting)
• Press the key on the screen
to display the
screen for selecting the burnout & saturation current
value specification (
).
• Select "CUSTOM" or "NAMUR" or “EXP (on the
screen
with the and keys.
Select "CUSTOM" for the custom setting.
Select "NAMUR" for NAMUR setting
* To change the saturation current value (upper limit,
lower limit), select the CUSTOM setting.
NAMUR
setting
CUSTOM setting
Saturation
current value
(lower limit)
3.8 mA
(fixed)
3.6 mA to 4.0 mA
Settable in increments of
0.1 mA
Saturation
current value
(upper limit)
20.5 mA
(fixed)
20.0 mA to 21.6 mA
Settable in increments of
0.1 mA
The table below lists the output current value for
burnout (OVER, UNDER).
NAMUR setting
CUSTOM setting
B u r n o u t
(UNDER)
3.4 to 3.6 mA
3.4 mA to 3.8 mA but under
the saturation current value
B u r n o u t
(OVER)
20.8 to 21.6 mA
20.8 mA to 22.5 mA but
above the saturation current
The values in the table above can be set in increments
of 0.1 mA.
• Select whether the CUSTOM / NAMUR setting is
saved on the screen .
Press the key to save the CUSTOM / NAMUR set-
ting.
Press the or key to cancel the setting and return
to the screen
.
Note :
When NAMUR is selected and Burnout direction is
set to HOLD, burnout will automatically change to
UNDERSCALE