83 TN5FCXA2VG-E
Used for selecting output at occurrence of a fault
in the detecting unit.
• Burnout direction is selectable under display
• For selection of NOT USED, press <1>.
• For selection of OVERSCALE, press <2>.
• For selection of UNDERSCALE, press <3>.
For NAMUR specification, the meaning of each
condition above is as follows.
• NOT USED
Not used (Output hold)
Saturation current = current set value
Note) Output value just before the occurrence of
trouble is given in the output hold mode.
• OVER SCALE
Over scale (Output 20.8
to 22.5 mA but above the lupper limit value of
saturation current value)
Saturation current = current set value
• UNDER SCALE
Under scale (Output 3.4
mA to 3.8 mA but under the lower limit value of
saturation current value)
Saturation current = 3.8, 20.8mA
For NAMUR specification :
3.4 mA => Burnout (UNDER) ≤ 3.6 mA
• Press "ENT" to confirm the setting.
Change of burnout current for OVERSCALE
and UNDERSCALE
• On display (5), press "CHANGE" to set the bur-
nout current.
• Press "DEC" or "INC" to change the burnout
current (settable in increments of 0.1 mA) on
display
.
• Press "ENT" to confirm the setting otherwise
press "CL" to cancel the setting on display
.
• Display
with saturate current appears.
Note : Specification of the saturation current value
(Upper limit and Lower limit) is changeable
according to the Menu "J : Saturation cur-
rent value"
The ower limit value ofsaturation valuer is
settable up to 4.0 mA at Custom specifi-
cation (3.2 mA to 4.0 mA)
Display symbol of Menu 9 is : "9 : BUR-
NOUT EXP" at Customs specification.
Menu 9 : Burnout direction
CHNG
3
9-2: BURNOUT
CHANGE
4
5
6
2
9:BURNOUT
NOT USED
(HOLD)
< INC > < CHANGE >
1
9-2: BURNOUT
CHANGE
Selection of
burnout direction
(ex)
< ENT > < CL >
CL
CL
CL
CHNG
CHNG
ENT
INC
CL
CL
or
or
2
1
3
3
9-1: BURNOUT
< 1 > NOT USED
< 2 > OVER SCALE
< 3 > UNDER SCALE
UNDER SCALE
9-4: BURNOUT
< CHANGE > < CL >
UNDER SCALE
Y.YmA
9-5: BURNOUT
< CL >
Saturate Current
3.8-20.8mA (*1)
9-5: BURNOUT CHNG
< DEC > <ENT > < CL >
UNDER SCALE
UNDER SCALE (burnout current)
for display 1
Y.YmA
UNDER SCALE
ENT
ENT
ENT
INC
7
8
9
10
CL
CL
9-5: BURNOUT CHNG
UNDER SCALE
Y.YmA
9: BURNOUT
< INC > < CHANGE >
for Menu No.A
for Menu No.A
UNDER SCALE
Y.YmA
Upon pressing <DEC> or <INC>
burnout current can be changed.
(See above.)
(The upper limit value is 3.8mA,
but under the lower limit value
of saturation current value.)
9-7: BURNOUT
< CL >
Saturate Current
3.8-20.8mA (*1)
INC
DEC
Y.YmA
4.0mA
3.9mA
3.8mA
3.7mA
3.6mA
3.5mA
3.4mA
3.3mA
3.2mA
Current set value of
saturation current is
displayed.
Change of
Over scale
current 22.5mA
Not supported
(Gray display)
*1) When it's NAMUR sepecification, the saturation current is 3.8~20.8mA.
Change of Over scale current
22.5mA
22.4mA
22.3mA
22.2mA
22.1mA
22.0mA
21.9mA
21.8mA
21.7mA
21.6mA
21.5mA
21.4mA
21.3mA
21.2mA
21.1mA
21.0mA
20.9mA
20.8mA
INC
DEC