TN5FCXA2VG-E
54
M
⑧
⑨
⑪
M
M
⑩
(Cancel the setting)
(Save the setting)
9-3 UNDER : Change of burnout current
when UN-
DER (UNDERSCALE) is selected.
This display appears if you select “UNDER” for the
burnout direction.
• Press the key on the screen
to display the
screen for changing the burnout current for UNDER-
SCALE (
).
• You can change the burnout current with the and
keys on the screen
.
Settable range: 3.4 mA =< Burnout (UNDER) =< 3.8
mA
For NAMUR specification : 3.4 mA => Burnout (UN-
DER) =< 3.6 mA
• Select whether the burnout current setting is saved
on the screen .
Press the key to save the burnout current setting
for UNDERSCALE.
Press the or key to cancel the setting.
Note)
You can change the saturation current value (lower
and upper limits) setting in “J. Value and specifi-
cation of saturation current.”