TN5FCXA2VG-E
60
M
M
①
②
②
③
M
(Save the setting)
(Cancel the setting)
Menu F : Lock of adjustment functions
You can lock/unlock the adjustment function of the lo-
cal configurator unit as follows.
INDICATION
When the adjustment functions are locked, the exter-
nal adjusting screw is also locked.
• Press the key on the screen
to display the lock
selection screen of adjusting functions (
).
• Select the locking/unlocking of the adjustment func-
tions on the screen
with the and keys.
Select lock to lock the adjustment functions of the lo-
cal configurator unit with LCD display.
Select UnLock to cancel the lock of the adjustment
functions of the local configrator unit with LCD dis-
play.
• Select whether the locking/unlocking of the adjust-
ment functions are saved on the screen
.
• After selecting the locking/unlocking, press the key
to save the setting.
Press the or key to cancel the setting and return
to the screen
.
List of adjustment functions locked/unlocked
A. Zero/span calibration
A-1. ZERO
A-2. SPAN
B Output circuit calibration b-1. 4mA Adj
b-2. 20mA Adj
I. Input/Output range ad-
justment
I-1. LRV Adj
I-2. URV Adj