33 TN5FCXA2VG-E
Hexagon key
wrench
Threaded plug
Caution on wiring
Two conduit connection are available and one is closed.
If the closed conduit connection must be used, please follow procedure below :
(1) Remove the threaded plug of the top connection. Put a new seal (Teflon...) on the thread
to ensure the sealing
(2) Screw the thread plug on the other terminal connection.
(3) Insert the cable through the free terminal connection and connect it.
• The unused terminal connection is of great importance to flameproof and
water prevention.
• When performing an insulation check after wiring, use a megohmmeter
of 250 V DC or less and avoid applying a high voltage. If an arrester is
equipped, avoid the insulation resistance test and the dielectric strength
measurement.
DANGER