49 TN5FCXA2VG-E
6-2 : Change of URV
(upper limit of the measuring
range = 20 mA / 100% point)
• Press the key on the screen
to display the
screen for setting the 100% point (
).
• Input the numerical values with the and keys on
the screen
.
Functions of the keys:
key: To decrease the value.
key: To increase the value.
Range: –99999 ≤ URV ≤ 99999
Note)
If “setERROR” is displayed as a URV value, the unit
is not supported.
• To set the decimal point position, press the key on
the screen
. “P” is displayed at the left of the unit
name (
) and you can set the decimal point position
with the and keys.
key: To move the decimal point position to left
key: To move the decimal point position to right
• Select whether the URV setting is saved on the
screen
.
Press the key to save the 100% point setting.
Press the or key to cancel the setting.
The setting range of the transmitter is independant
ot the setting range of the indicator.
After changing the range in this menu, it is neces-
sary to change the range in the LCD indicator
(menu G).
Using an analog indicator and the transmitter range
is changed, replacement of the analog indicator is
required.
SPAN
SPAN
SPAN
M
①
②
③
④
⑤
M
M
M
(Cancel the setting)
(Save the setting)
Important