107
EN-US
Field adjustable
trip points
Relevant stan-
dards and direc-
tives
Field adjustable trip points
208 V
240 V
Nominal AC output voltage,
Line-to-Line, [V]
208
240
Operating AC voltage range default,
Line-to-Line, [V]
183-229
212-264
Adjustment range for voltage,
Line-to-Line, [V]
180-240
180-270
Voltage trip limit accuracy
Line-to-Line,
[% of nominal value]
± 1,5
± 1,5
Nominal output frequency [Hz]
60
60
Operating frequency range [Hz]
59.3-60.5
59.3-60.5
Adjustment range for frequency [Hz]
57.0-60.5
57.0-60.5
Frequency trip limit accuracy, [Hz]
± 0,02
± 0,02
Reconnect time, [s]
305
305
Adjustment range for reconnect time, [s]
1-999
1-999
Operating AC voltage range
Line-to-Neutral, [V]
106 - 132
106 - 132
Adjustment range for voltage
Line-to-Neutral, [V]
60 - 144
60 - 144
Voltage trip limit accuracy
Line-to-Neutral,
[% of nominal value]
± 1,5
± 1,5
-
UL 1741
-
IEEE 1547
-
IEEE 1547.1
-
ANSI/IEEE C62.41
-
FCC Part 15 A & B
-
NEC Article 690
-
C22. 2 No. 107.1-01
(September 2001)
Содержание IG 2000
Страница 2: ...0...
Страница 4: ...2...
Страница 6: ...4...
Страница 10: ...8...
Страница 15: ...General Information...
Страница 16: ......
Страница 21: ...Installation and Startup...
Страница 22: ......
Страница 50: ...48...
Страница 51: ...Operation...
Страница 52: ......
Страница 80: ...78...
Страница 81: ...Troubleshooting and Maintenance...
Страница 82: ......
Страница 95: ...Appendix...
Страница 96: ......
Страница 113: ...111 EN US...
Страница 114: ...112...
Страница 115: ...113 EN US...