114
PB
No.
Malfunction
Name
Display Method of Indoor Unit
Display Method of Outdoor Unit
A/C status
Possible Causes
Dual‑8
Code
Display
Indicator Display (During blinking,
ON 0.5s and OFF 0.5s)
Indicator has 3 kinds of display status
and during blinking, ON 0.5s and
OFF 0.5s
Power
Indicator
Cool
Indicator
Heating
Indicator
Yellow
Indicator
Red
Indicator
Green
Indicator
26
compressor
intermediate
frequence in
test state
P3
during
blinking
ON and
0.25s and
OFF and
0.25s
during
blinking
ON and
0.25s and
OFF and
0.25s
Showing during middle cool‑
ing or middle heating test
27
overcurrent
protection of
phase current
for compres‑
sor
P5
OFF 3s
and blink
15 times
During cooling and drying op‑
eration, compressor will stop
while indoor fan will operate;
During heating operation,
the complete unit will stop
operation.
Refer to the malfunction
analysis (IPM protection, loss
of synchronism protection
and overcurrent protection of
phase current for compres‑
sor).
28
charging
malfunction
of capacitor
PU
OFF 3s
and blink
17 times
During cooling and drying op‑
eration, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
Refer to the part three—charg‑
ing malfunction analysis of
capacitor
29
malfunction
of module
temperature
sensor circuit
P7
OFF 3s
and blink
18 times
s
During cooling and drying op‑
eration, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
Replace outdoor control
panel AP1
30
module high
temperature
protection
P8
OFF 3s
and blink
19 times
During cooling operation,
compressor will stop while
indoor fan will operate;
During heating operation, the
complete unit will stop
After the complete unit is de‑
energized for 20mins, check
whether the thermal grease
on IPM Module of outdoor
control panel AP is sufficient
and whether the radiator is
inserted tightly. If no faults
found, replace control panel
AP1
31
decrease
frequency
due to high
temperature
resistant dur‑
ing heating
operation
H0
OFF 3s
and blink
10 times
All loads operate normally,
while
operation frequency for
compressor is decreased
Refer to the malfunction
analysis (overload, high
temperature resistant)
32
static dedust‑
ing protection
H2
OFF 3s
and blink
twice
TROUBLESHOOTING
Diagnostic Codes
Содержание FSHW091
Страница 8: ...8 INTRODUCTION FSHSW09A1A FSHSW12A1A Figure 102 Indoor Units FSHSW18A3A FSHSW24A3A FSHSW36A3A ...
Страница 47: ...47 INSTALLATION ...
Страница 48: ...48 INSTALLATION Installation Tools ...
Страница 72: ...72 WIRED CONTROLLER Display ...
Страница 122: ...122 TROUBLESHOOTING Malfunction of IDUFanMotorU8 Service Manual No Start End ...
Страница 146: ...146 WIRING DIAGRAMS Figure 8054 9 12KOutdoorUnitWiringDiagrams 60000706067401 3 2 N 1 C3 C4 ...
Страница 147: ...147 WIRING DIAGRAMS Figure 805 18 24kOutdoorUnitWiringDiagrams Figure 806 36kOutdoorUnitWiringDiagrams 6361000047001 ...
Страница 158: ...158 FIgure 906 PARTS CATALOG 9KOutdoorUnit 28 27 29 31 30 32 ...
Страница 160: ...160 PARTS CATALOG 12k OutdoorUnit 28 27 29 31 30 32 FIgure 907 ...