Frick XLP3 Скачать руководство пользователя страница 18

140.925-IOM (APR 2019)

Page 18

XLP3 EVAPORATIVE CONDENSERS

OPERATION

Maintenance Requirements During Storage

•  Rotate all fans and motor shafts monthly by hand. Hand-

turning will ensure that the shafts and bearings are free 
and will redistribute grease within the bearings.

•  Inspect the cold water basin monthly to ensure that the 

drain is open and remove any leaves or debris that may 
have accumulated in the cold water basin.

•  Inspect the axial fans annually to ensure the blades are 

tight and there is no obvious corrosion between the hub 
and the fan blade.

•  Inspect the rust preventative coating on all motor external 

machined surfaces including shaft extensions monthly. If 
necessary, re-coat the surfaces with RUST VETO®.

Start-Up Preparation After Prolonged Storage

Keep in mind that start-up procedures after long periods of 
storage are just as important as pre-shutdown procedures.

•  Motors should be thoroughly inspected, cleaned, and 

restored to pre-storage condition.

•  Inspect axial fans prior to start-up to ensure that the 

blades are tight and that there is no obvious corrosion 
between the hub and the fan blade. Do not energize the 
fans if there is obvious corrosion of fan components. Loose 
fan blades could result in fan failure and possible injury or 
damage.

•  Reinstall all fan belts, motors, door gaskets, and drain 

plugs (as applicable), and remove all protective coverings.

•  For units stored prior to installation, conduct rigging 

procedures as directed in the unit’s Rigging and 
Assembly Instructions, or by contacting your local Frick 
Representative.

•  Perform an insulation test of motor windings to ensure 

satisfactory insulation resistance.

•  Conduct full start-up procedure as stated in the “Start-Up 

Procedure” on page 15. Be especially thorough for cleaning 
and inspection prior to start-up.

COLD WEATHER OPERATION

Inspection and Maintenance

Frick products can be operated at subfreezing ambient tem-
peratures provided proper operating methods are established 
and diligently followed.

•  Carry out frequent visual inspections and routine 

maintenance services during operation in subfreezing 
weather.

•  Ensure all controls for capacity and freeze protection are 

set properly and functioning normally.

•  Prevent excessively high water levels and possible overflow 

of the cold water basin due to over pumping, clogged 
strainers, or make-up valve malfunction.

•  Some unit icing can be expected in very cold weather. 

Usually this will not affect the operation of the unit. 
Resolve any icing conditions that may damage the unit or 
the supports, impair the system performance, or create a 
safety hazard.

Fan Section Icing Protection

There are three basic operational methods which can be used to 
provide the system’s required cooling: temperature setting, fan 
control, and dry operation. The method of control employed on a 
given application depends upon the climatic extremes which are 
expected, the variations in heat load that will be encountered, 
and the compatibility of the control system with other portions 
of the installation.

In subfreezing ambient temperatures, effective icing control may 
require a combination of these three methods. Operate each unit 
with the highest thermal load it can handle, rather than evenly 
dividing the total heat load across all cells. During prolonged 
cold weather periods, bypass the idle units and drain the basins.

Fan Control

Reduce the unit capacity by cycling the fans, thus modulating 
the airflow through the unit. Rapid on-off cycles can cause the 
fan motor to overheat. Set the controls to allow a maximum 
of six on-off cycles per hour. Periodically, cycle the fans off to 
prevent ice formation and/or to melt ice that accumulates on 
the combined inlet shields.

The following are fan control methods:

• 

Variable Frequency Drives:

 VFDs offer the most precise 

method of capacity control by modulating fan motor speed. 
When using VFDs, avoid operating at or near resonant 
speeds. Units with VFDs require premium efficient/inverter 
duty motors.

• 

Fan Cycling:

 Cycle the fan off for five minutes every 15 to 

20 minutes for each cell. If ice continues to build on the air 
intake, decrease the on-time. Observe the air intake of the 
unit at least every four to eight hours.

NOTICE

Modulating the water flow rate to the unit is NOT a recom-
mended method of controlling cooling capacity.

Dry Operation

One method to prevent icing is dry operation. Dry operation of 
the unit protects fans from ice formation due to mist and splash 
from the cold water basin. The water in the cold water basin 
must be drained in dry operation. For dry operation switch points 
and recommendations, contact your local Frick representative.

BASIN WATER AND INTERNAL PIPING  

FREEZE PROTECTION

Cold Water Basin Protection

It is important to protect the basin and internal piping. The basin 
water could freeze when the unit is shutdown and exposed to 
subfreezing ambient temperatures.

• 

Remote Sump:

 The ideal method of protection is a 

remote sump located in a heated indoor space. When the 
circulating pump stops, the water in the connecting piping 
will drain by gravity to this indoor sump.

• 

Basin Heaters:

 On applications without a remote sump, 

heat must be provided to the cold water basin. Electrical 
immersion heaters can provide the required function. 
Contact your local Frick Representative for details.

Содержание XLP3

Страница 1: ...ive Condenser THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PERSONAL INJU...

Страница 2: ...TIONS 14 START UP PROCEDURE 15 Considerations for Initial Start Up 15 General 15 Cleaning 15 Inspection 15 Start up 15 EXTENDED SHUTDOWN 16 PROLONGED OUTDOOR STORAGE 16 Storage Preparation 16 Motor Re...

Страница 3: ...afety Cage Optional Coil Connection Refrigerant Vapor In Coil Connection Refrig erant Liquid Out Terminal Box Pump Factory Pre Assembled Platforms with Perimeter Handrails Optional BranchLokTM Removal...

Страница 4: ...ellaneous parts are included with the shipment and where they are packed This envelope will be attached to the side of the unit or located in a box inside the unit INSTALLATION Unit Weights Before rig...

Страница 5: ...to ensure an airtight seal between the top and bottom section Install flat butyl sealer tape Frick part 554000 supplied with the unit on the mating flanges of the lower section in a continuous line A...

Страница 6: ...basin section sealer tape must be applied to both cross flanges see Figure 3 10 On units operating with a remote sump tank install a bleed line with valve between the system circulating pump discharg...

Страница 7: ...lease ensure that the correct voltage is supplied to the unit If unsure check your unit s submittal to verify that the provided power matches your unit On the factory terminal box remove the NEMA plug...

Страница 8: ...nd Figure 9 Detail A Check your submittal for the ladder orientation ordered Attach the ladder to the platform and fasten the lower and intermediate brackets to the ladder side rails as shown in Figur...

Страница 9: ...DENSERS INSTALLATION Figure 9 End Ladder Installation Detail A End Ladder Bracket Detail A Perimeter Guardrail Installation Detail B Corner Guardrail Installation Detail C Perimeter Guardrail Installa...

Страница 10: ...are provided for all handrail openings and all components are designed to meet OSHA requirements Share two lower fasteners on upper ladder bracket Upper ladder bracket Hoop Detail D Figure 11 Safety...

Страница 11: ...per the control panel wiring diagram 5 Connect the heater power wire conduit s to the heater power wire hub s provided on the control panel Make sure the con nection is watertight and secure Pull the...

Страница 12: ...Control Panel L1 L2 L3 Controller Liquid Level Temperature Combination Series TL Solitech CT N C NO NC T1 T2 G1 G2 Shielded Cable Assembly Sensor Probe Cord G2 G1 T2 T1 SH No 1 Heater 40 24 16 12 8 1...

Страница 13: ...ter basin a For connections 3 or less score the TripleGuard Corrosion Protection System with a hole saw as shown in Figure 14 b For connections 3 or greater proceed to step 4 4 Cut the hole from the o...

Страница 14: ...fan screens access panels and access doors in place CAUTION All electrical mechanical and rotating machinery are potential hazards particularly for those not familiar with their design construction an...

Страница 15: ...locked out and tagged out Inspection Conduct external inspection of the equipment Check for leaks corrosion and any structural damage Conduct internal inspection of the equipment Check for anything u...

Страница 16: ...fer to the manufacturer s guidelines before loading unloading weight from the unit Disconnect lock out and tag out the fans pump and motors Close the shut off valve in the make up water line supplied...

Страница 17: ...ump motors are disconnected locked out and tagged out Belt Drive Fan System Frick standard motors are designed for storage at ambient temperatures of 20 F to 104 F 28 9 C to 40 C Prolonged periods of...

Страница 18: ...system performance or create a safety hazard Fan Section Icing Protection There are three basic operational methods which can be used to provide the system s required cooling temperature setting fan...

Страница 19: ...heaters are sized for the specific unit The heating element has an enclosure that is suitable for outdoor use Annually inspect the basin heater prior to the risk of reaching freezing operating condit...

Страница 20: ...bration cutout switch is not needed Mechanical Vibration Cutout Switch Standard Set Point Adjustment When Installed 1 For safety turn off then lock and tag out the electrical supply to the fan motor s...

Страница 21: ...Control Panel L1 L2 L3 Controller Liquid Level Temperature Combination Series TL Solitech CT N C NO NC T1 T2 G1 G2 Shielded Cable Assembly Sensor Probe Cord G2 G1 T2 T1 SH No 1 Heater 40 24 16 12 8 10...

Страница 22: ...ent Staging Down Turn off the fan motor No need for delays NOTICE For a unit with a VFD with a switching frequency of 2 5 kHz the line lead length cannot exceed 100 feet If the switching frequency is...

Страница 23: ...the VFD on and verify that the fan is turning in the correct direction Using the VFD slowly about 1 RPM increase every five to ten seconds adjust the motor speed from the lowest limit to full speed wh...

Страница 24: ...tors are disconnected locked out and tagged out Blade Pitch Check to ensure that the blades are all at the same pitch If uncertain measure the pitch with an inclinometer All blades should be within 1...

Страница 25: ...s necessary Readjust tension at least once every three months Belt tension check Place a straight edge along the belt from sheave to sheave as shown in Figure 22a or use a tape measure as shown in Fig...

Страница 26: ...the bearings as follows Initial Start Up Normally no lubrication is required since the bearings have been lubricated at the factory prior to shipment However if the unit has been stored at the job si...

Страница 27: ...the valve seat if necessary Maintain the make up water supply pressure between 15 psig and 50 psig for proper operation Frick recommends a pressure regulator valve provided by others for pressures ove...

Страница 28: ...tection System for signs of deep scratches or blemishes especially in areas with field penetrations Touch these up with 3M Windo Weld Super Fast Urethane which is available through your local Frick Re...

Страница 29: ...Dissolved Solids TDS 1 500 ppm 2 050 ppm 2 050 ppm 2 500 ppm Conductivity 2 400 micromhos cm 3 300 micromhos cm 3 300 micromhos cm 4 000 micromhos cm Alkalinity as CaCO3 500 ppm 2 600 ppm 2 600 ppm 2...

Страница 30: ...methyl or ethyl alcohol or mineral spirits Stainless steel wipes or glass cleaners commonly available in stores may also be used NOTICE Never use chloride or chlorine based solvents such as bleach or...

Страница 31: ...reatment expert Bleed Line Calculations Bleed rate is determined by the fol lowing formula B E n 1 Where B Bleed Rate USGPM E Evaporation Rate USGPM Q USGPM x R F x 0 001 Q Process Fluid Flow Rate USG...

Страница 32: ...for proper rotation X Check general condition of the fan X X Check fan for uniform pitch 4 X Check fan for rotation without obstruction X X Check and recoat steel shafts with RUST VETO 4 X X X Check...

Страница 33: ...140 925 IOM APR 2019 Page 33 XLP3 EVAPORATIVE CONDENSERS MAINTENANCE NOTES...

Страница 34: ...ynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com frick Form 140 925 IOM 2019 04 Supersedes Nothing Subject to change without notice Published in USA 04 19 PDF 201...

Отзывы: