Frick XLP3 Скачать руководство пользователя страница 15

140.925-IOM (APR 2019) 

Page 15

XLP3 EVAPORATIVE CONDENSERS

OPERATION

NOTICE

⋅  Check to ensure the controls for the fan motor are set 

to allow a maximum of six on-off cycles per hour to 

prevent motor overload.

⋅  With  a  switching  frequency  of  2.5  kHz,  the  line  lead 

length cannot exceed 100 feet. If the switching frequency 

is higher that 2.5 kHz and/or the line lead length exceeds 

100 feet, a dV/dT output filter is recommended to protect 

the motor.

⋅  For  fan  motors  controlled  with  VFDs,  when  reversing 

the direction of fan rotation, allow the fan to come to a 

complete stop before restarting the motor.

⋅  Only lubricate the bearings with one of the compatible 

water resistant greases listed on page 26.

⋅  Do not use steam or high pressure water to clean PVC 

eliminators or materials other than steel.

⋅  Spray system pressure greater than 10.0 psig may cause 

damage to the distribution system.

⋅  Never  use  chloride  or  chlorine  based  solvents  such  as 

bleach or muriatic (hydrochloric) acid to clean stainless 

steel. It is important to rinse the surface with warm water 

and wipe with a dry cloth after cleaning.

START-UP PROCEDURE

Considerations for Initial Start-Up

•  For units with independent fan control [standard on units 

with the Belt Drive Fan System], see page 22.

•  For units with VFDs, see page 22.
•  For units with vibration cutout switches, see page 20.

General

•  If the unit is mounted on vibration isolators or isolation rails 

(by others), refer to the vibration isolation manufacturer’s 
guidelines before loading/unloading weight from the unit. 

•  Verify fans and the pump motor are disconnected, locked 

out, and tagged out.

•  The unit must be level in both the length and width 

directions for proper operation.

Cleaning

•  Drain the cold water basin with the strainer in place.
•  Remove all dirt and debris from the fan guard(s) and 

combined inlet shields.

•  Inspect and clean all spray nozzles.
•  Clean all of the mechanical components, such as the fan 

and motor.

•  Flush the cold water basin to remove any accumulated dirt 

and debris.

•  Remove, clean, and replace the basin strainer.

 

DANGER

Rotating equipment will cause severe personal injury or 

death to persons who come in contact. Do not perform any 

service on or near the fans, motors, and drives, or inside 

the  unit  without  first  ensuring  that  the  fans  and  pump 

motors are disconnected, locked out, and tagged out.

Inspection

•  Conduct external inspection of the equipment. Check for 

leaks, corrosion, and any structural damage.

•  Conduct internal inspection of the equipment. Check 

for anything unusual such as structural or mechanical 
component damage.

•  Inspect piping and connections.
•  Thoroughly inspect the fans for any mechanical or physical 

damage.

•  At seasonal start-up or after prolonged shutdown, check 

the motor insulation with an insulation tester prior to the 
motor start-up.

•  Check and adjust the belt tension. Units equipped with the 

EC Fan System use direct drive motors and do not require 
belt tension.

Start-up

•  For Belt Drive Fan System units only, prior to seasonal 

start-up, lubricate the motor base adjusting screw (see 
Figure 22 on page 25) and the fan shaft bearings (see page 
26). At initial start-up, no bearing lubrication is required 
since the bearings are factory lubricated prior to shipment.

•  For Belt Drive Fan System units only, apply RUST VETO® 

to steel shafts.

•  Fill the cold water basin with fresh water to the overflow 

level via the make-up valve.

•  Set the make-up valve float so the water shuts off at the 

operating level (see Table 4 on page 24).

•  Execute one of the following biocide treatment programs 

while operating the circulating pump and prior to operating 
the unit fans:

  •  Resume treatment with the biocide that was used prior 

to shutdown. Operate the pump only while maintaining 
the maximum recommended biocide residual for a 
sufficient duration (residual and time will vary with 
the biocide) as recommended by the water treatment 
supplier. Start the fan only after this treatment period 
is completed.

  •  Check the pH of the circulating water and, if necessary, 

adjust it to 7.0 - 7.6 pH. Then, running the pump only, 
treat the system with sodium hypochlorite to maintain 
a level of 4 to 5 mg/l (ppm) free chlorine (as Cl2) over a 
six hour period. Test kits for measuring the free residual 
of chlorine are commercially available. Start the fan 
only after this treatment period is completed.

•  Start the unit pump and check for the proper rotation 

indicated by the arrow on the pump cover.

•  On installations where the unit pump was not furnished 

by Frick, a globe valve should be installed in the pump 
discharge line and the pump flow rate adjusted to the 
correct water flow and pressure (2.25 psig at spray header 
connection).

•  Check that the float operated make-up valve is operating 

freely. Closely monitor the water level and adjust as 
necessary during the first 24 hours of operation.

Содержание XLP3

Страница 1: ...ive Condenser THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PERSONAL INJU...

Страница 2: ...TIONS 14 START UP PROCEDURE 15 Considerations for Initial Start Up 15 General 15 Cleaning 15 Inspection 15 Start up 15 EXTENDED SHUTDOWN 16 PROLONGED OUTDOOR STORAGE 16 Storage Preparation 16 Motor Re...

Страница 3: ...afety Cage Optional Coil Connection Refrigerant Vapor In Coil Connection Refrig erant Liquid Out Terminal Box Pump Factory Pre Assembled Platforms with Perimeter Handrails Optional BranchLokTM Removal...

Страница 4: ...ellaneous parts are included with the shipment and where they are packed This envelope will be attached to the side of the unit or located in a box inside the unit INSTALLATION Unit Weights Before rig...

Страница 5: ...to ensure an airtight seal between the top and bottom section Install flat butyl sealer tape Frick part 554000 supplied with the unit on the mating flanges of the lower section in a continuous line A...

Страница 6: ...basin section sealer tape must be applied to both cross flanges see Figure 3 10 On units operating with a remote sump tank install a bleed line with valve between the system circulating pump discharg...

Страница 7: ...lease ensure that the correct voltage is supplied to the unit If unsure check your unit s submittal to verify that the provided power matches your unit On the factory terminal box remove the NEMA plug...

Страница 8: ...nd Figure 9 Detail A Check your submittal for the ladder orientation ordered Attach the ladder to the platform and fasten the lower and intermediate brackets to the ladder side rails as shown in Figur...

Страница 9: ...DENSERS INSTALLATION Figure 9 End Ladder Installation Detail A End Ladder Bracket Detail A Perimeter Guardrail Installation Detail B Corner Guardrail Installation Detail C Perimeter Guardrail Installa...

Страница 10: ...are provided for all handrail openings and all components are designed to meet OSHA requirements Share two lower fasteners on upper ladder bracket Upper ladder bracket Hoop Detail D Figure 11 Safety...

Страница 11: ...per the control panel wiring diagram 5 Connect the heater power wire conduit s to the heater power wire hub s provided on the control panel Make sure the con nection is watertight and secure Pull the...

Страница 12: ...Control Panel L1 L2 L3 Controller Liquid Level Temperature Combination Series TL Solitech CT N C NO NC T1 T2 G1 G2 Shielded Cable Assembly Sensor Probe Cord G2 G1 T2 T1 SH No 1 Heater 40 24 16 12 8 1...

Страница 13: ...ter basin a For connections 3 or less score the TripleGuard Corrosion Protection System with a hole saw as shown in Figure 14 b For connections 3 or greater proceed to step 4 4 Cut the hole from the o...

Страница 14: ...fan screens access panels and access doors in place CAUTION All electrical mechanical and rotating machinery are potential hazards particularly for those not familiar with their design construction an...

Страница 15: ...locked out and tagged out Inspection Conduct external inspection of the equipment Check for leaks corrosion and any structural damage Conduct internal inspection of the equipment Check for anything u...

Страница 16: ...fer to the manufacturer s guidelines before loading unloading weight from the unit Disconnect lock out and tag out the fans pump and motors Close the shut off valve in the make up water line supplied...

Страница 17: ...ump motors are disconnected locked out and tagged out Belt Drive Fan System Frick standard motors are designed for storage at ambient temperatures of 20 F to 104 F 28 9 C to 40 C Prolonged periods of...

Страница 18: ...system performance or create a safety hazard Fan Section Icing Protection There are three basic operational methods which can be used to provide the system s required cooling temperature setting fan...

Страница 19: ...heaters are sized for the specific unit The heating element has an enclosure that is suitable for outdoor use Annually inspect the basin heater prior to the risk of reaching freezing operating condit...

Страница 20: ...bration cutout switch is not needed Mechanical Vibration Cutout Switch Standard Set Point Adjustment When Installed 1 For safety turn off then lock and tag out the electrical supply to the fan motor s...

Страница 21: ...Control Panel L1 L2 L3 Controller Liquid Level Temperature Combination Series TL Solitech CT N C NO NC T1 T2 G1 G2 Shielded Cable Assembly Sensor Probe Cord G2 G1 T2 T1 SH No 1 Heater 40 24 16 12 8 10...

Страница 22: ...ent Staging Down Turn off the fan motor No need for delays NOTICE For a unit with a VFD with a switching frequency of 2 5 kHz the line lead length cannot exceed 100 feet If the switching frequency is...

Страница 23: ...the VFD on and verify that the fan is turning in the correct direction Using the VFD slowly about 1 RPM increase every five to ten seconds adjust the motor speed from the lowest limit to full speed wh...

Страница 24: ...tors are disconnected locked out and tagged out Blade Pitch Check to ensure that the blades are all at the same pitch If uncertain measure the pitch with an inclinometer All blades should be within 1...

Страница 25: ...s necessary Readjust tension at least once every three months Belt tension check Place a straight edge along the belt from sheave to sheave as shown in Figure 22a or use a tape measure as shown in Fig...

Страница 26: ...the bearings as follows Initial Start Up Normally no lubrication is required since the bearings have been lubricated at the factory prior to shipment However if the unit has been stored at the job si...

Страница 27: ...the valve seat if necessary Maintain the make up water supply pressure between 15 psig and 50 psig for proper operation Frick recommends a pressure regulator valve provided by others for pressures ove...

Страница 28: ...tection System for signs of deep scratches or blemishes especially in areas with field penetrations Touch these up with 3M Windo Weld Super Fast Urethane which is available through your local Frick Re...

Страница 29: ...Dissolved Solids TDS 1 500 ppm 2 050 ppm 2 050 ppm 2 500 ppm Conductivity 2 400 micromhos cm 3 300 micromhos cm 3 300 micromhos cm 4 000 micromhos cm Alkalinity as CaCO3 500 ppm 2 600 ppm 2 600 ppm 2...

Страница 30: ...methyl or ethyl alcohol or mineral spirits Stainless steel wipes or glass cleaners commonly available in stores may also be used NOTICE Never use chloride or chlorine based solvents such as bleach or...

Страница 31: ...reatment expert Bleed Line Calculations Bleed rate is determined by the fol lowing formula B E n 1 Where B Bleed Rate USGPM E Evaporation Rate USGPM Q USGPM x R F x 0 001 Q Process Fluid Flow Rate USG...

Страница 32: ...for proper rotation X Check general condition of the fan X X Check fan for uniform pitch 4 X Check fan for rotation without obstruction X X Check and recoat steel shafts with RUST VETO 4 X X X Check...

Страница 33: ...140 925 IOM APR 2019 Page 33 XLP3 EVAPORATIVE CONDENSERS MAINTENANCE NOTES...

Страница 34: ...ynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com frick Form 140 925 IOM 2019 04 Supersedes Nothing Subject to change without notice Published in USA 04 19 PDF 201...

Отзывы: