Part number 550-142-850/0115
93
FreeStyle
™
W
ALL
M
OUNT
GAS
-
FIRED
WATER
BOILER
—
Boiler Manual
32
Troubleshooting
(continued)
Category
%PROMPARAMETERS
Unit
2ANGE
$EF
Description
Num.
Address
Description
Low
High
Value
'+:FRQ¿J
42,2
ML – 810A
DHW set point limit – LOW
°F
50
104
50
'+:FRQ¿J
43,2
CL5 – 1E76
DHW set point limit – HIGH
°F
104
158
149
'+:FRQ¿J
44,2
CL5 – 05F4
DHW user set point – Default value
°F
50
158
149
'+:FRQ¿J
45,2
ML – 810D
CH pre-pump time
Sec
0
60
30
'+:FRQ¿J
46,2
ML – 810E
Minimum virtual set point
°F
68
176
95
'+:FRQ¿J
9,3
CL5 – 066E
DHW P factor
Num
0
255
20
'+:FRQ¿J
10,3
CL5 – 0691
DHW I factor
Num
0
255
240
'+:FRQ¿J
11,3
ML – 80EB
DHW FF factor
Num
0
255
0
'+:FRQ¿J
12,3
ML – 80EC
Fan absolute DHW maximum speed
Hz
0
220
200
'+:FRQ¿J
13,3
ML – 80ED
Fan absolute CH maximum speed
Hz
0
220
200
'+:FRQ¿J
14,3
ML – 80EE
Fan absolute minimum speed
Hz
0
165
40
'+:FRQ¿J
15,3
CL5 – 2D89
Fan offset low level
Hz
0
220
10
'+:FRQ¿J
16,3
ML – 80F0
Ignition level
%
0
100
60
'+:FRQ¿J
17,3
ML – 80F1
DHW maximum output boost/limit level
%
75
125
100
'+:FRQ¿J
18,3
ML – 80F2
DHW maximum output boost/limit time
Sec
0
120
60
'+:FRQ¿J
19,3
ML – 80F3
'+:RYHUWHPSBEXUQHU2))¿[HG
°F 68
194
167
'+:FRQ¿J
20,3
ML – 80F4
'+:RYHUWHPSBEXUQHU21¿[HG
°F 68
194
163
'+:FRQ¿J
21,3
ML – 80F5
DHW over-temp_burnerOFF – setpoint
°F
0
200
9
'+:FRQ¿J
22,3
ML – 80F6
DHW over-temp_burnerON – setpoint
°F
0
200
0
'+:FRQ¿J
23,3
ML – 80F7
DHW over-temp_burnerOFF – solar
°F
0
200
18
'+:FRQ¿J
24,3
ML – 80F8
DHW over-temp_burnerON – solar
°F
0
200
18
'+:FRQ¿J
25,3
ML – 80F9
DHW start waiting time – solar1
Sec
0
255
5
'+:FRQ¿J
26,3
ML – 80FA
DHW start waiting time – solar2
Sec
0
255
10
'+:FRQ¿J
27,3
ML – 80FB
DHW start waiting time – solar3
Sec
0
255
20
'+:FRQ¿J
28,3
CL5 – 0A5E
DHW comfort switch on point
°F
0
176
104
'+:FRQ¿J
29,3
CL5 – 0A62
DHW comfort temp difference
°F
0
100
36
'+:FRQ¿J
30,3
ML – 80FE
DHW pump start temperature
°F
0
255
68
'+:FRQ¿J
31,3
ML – 80FF
DHW pump start waiting time
Sec
0
255
1
'+:FRQ¿J
32,3
CL5 – 05A1
DHW OFF time
Sec
0
255
120
'+:FRQ¿J
33,3
CL5 – 0A04
DHW pump over-run time
Sec
0
255
30
'+:FRQ¿J
34,3
CL5 – 0A6D
Delta T1
°F
0
108
32
'+:FRQ¿J
35,3
CL5 – 0A92
Delta T2
°F
0
255
255
'+:FRQ¿J
36,3
ML – 8104
CH supply for CH pump over-run OFF
°F
32
212
91
'+:FRQ¿J
37,3
CL5 – 0C94
CH supply for CH pump over-run ON
°F
0
200
18
'+:FRQ¿J
38,3
ML – 8106
CH supply over-temp_burnerOFF
°F
0
212
203
'+:FRQ¿J
39,3
ML – 8107
CH supply over-temp_burnerON
°F
32
212
194
'+:FRQ¿J
40,3
ML – 8108
CH return over-temp_burnerOFF
°F
32
212
203
'+:FRQ¿J
41,3
ML – 8109
CH return over-temp_burnerON
°F
32
212
194
'+:FRQ¿J
42,3
ML – 810A
DHW set point limit – LOW
°F
50
104
104
'+:FRQ¿J
43,3
CL5 – 1E76
DHW set point limit – HIGH
°F
104
158
131
'+:FRQ¿J
44,3
CL5 – 05F4
DHW user set point – Default value
°F
50
158
131
'+:FRQ¿J
45,3
ML – 810D
CH pre-pump time
Sec
0
60
30
'+:FRQ¿J
46,3
ML – 810E
Minimum virtual set point
°F
68
176
95
Figure 121
4ROUBLESHOOTINGSUGGESTIONSFOR
FreeStyle
™
BOILERS
&AULTDISPLAYSANDDIAGNOSTICS
(continued)