Boiler Manual
29
&KHFNRXWVWDUWXSYHUL¿FDWLRQ
Adjust and test boiler controls
1.
&OLLOWINSTRUCTIONSINTHISMANUALTOSETANDVERIFYOPERATION
OFTHEBOILERCONTROLS
2.
&OLLOWLOWWATERCUTOFFMANUFACTURERSINSTRUCTIONS
IFUSED
Have the following been done?
❏
Boiler and heat distribution units filled with water?
❏
Water chemistry verified per page 63?
❏
Sentinel X100 corrosion inhibitor added and water tested to
be within range?
❏
!IRPURGEDFROMSYSTEM
❏
!IRPURGEDFROMGASPIPING0IPINGCHECKEDFORLEAKS
❏
Condensate trap primed?
❏
)FBOILERHASBEENCONVERTEDTO,IQUElED0ETROLEUM,0 'AS
ISPROPANECONVERSIONLABELAFlXEDTOJACKET
FreeStyle
™
boilers are shipped ready to fire natural
GAS/.,94OlREONPROPANEYOUMUSTFOLLOWTHE
instructions in this manual to install the propane
venturi. See page 12
FOR
FreeStyle
™
80 or 120.
Failure to comply could result in severe personal
injury, death or substantial property damage.
❏
Thermostat circuit wiring checked to ensure there are no
stray voltages?
❏
Followed Operating Instructions, Figure 93, page 67?
❏
Burner flame and combustion verified per page 68?
❏
FreeStyle
™
CONTROLOPERATIONFORSPACEHEATINGAND$(7
IFUSED VERIlEDPERTHISMANUAL
❏
!DDITIONAL FIELDINSTALLED CONTROLS TESTED AS OUTLINED BY
CONTROL MANUFACTURERS "OILER SHOULD BE OPERATING AND
SHOULDGOOFFWHENCONTROLSARETESTED6ERIFYCONTROLSCAUSE
automatic reset lockout or manual reset lockout as desired.)
❏
!DDITIONAL FIELDINSTALLED LIMIT CONTROLS SET TO SYSTEM
temperature requirements? Balancing valves and controls
adjusted to provide design temperature to system?
❏
&LOW ADJUSTEDBALANCED FOR EACH ZONE OF MULTIPLE ZONES
systems?
❏
4HERMOSTATHEATANTICIPATORIFAVAILABLE SETPROPERLY
❏
"OILERCYCLEDWITHTHERMOSTATSANDWITH$(7AQUASTATIF
installed) — Raised to highest setting and verified boiler goes
through normal startup cycle? Lowered to lowest setting and
VERIlEDBOILERGOESOFF
❏
Natural gas input measured? (page 68)
❏
Incoming gas pressure checked by connecting manometer to
GASVALVEAHEADOFBOILER'ASPRESSUREMUSTBEATLEASTTHE
minimum values given on page 16, with boiler operating at
high fire, and no more than 13 inches (330 mm) w.c. with
BOILEROPERATINGORBOILEROFF
❏
/BSERVEDSEVERALOPERATINGCYCLESFORPROPEROPERATION
❏
Room thermostats set to desired room temperature (and
$(7 AQUASTAT IF INSTALLED TO DESIRED $(7 STORAGE TEM
-
perature)?
❏
All instructions shipped with this boiler reviewed with owner
or maintenance person?
❏
)GNITIONSYSTEMSAFETYSHUTOFFDEVICETESTED
Before leaving:
❏
Fill in
)NSTALLATIONCERTIlCATE
, page 120.
❏
Return instructions to envelope and give to owner.
Fill out start-up data on the In-
stallation and Service Certificate,
page 120.