FR150A Series Multifunctional Compact
Inverter
- 23 -
4.1 Five LED (digital) display indicators
Hz
V
A
%
Ten thousand
’
s
place
Thousand
’
s place
Hundred
’
s place
Unit
’
s place
Ten
’
s place
Fig.4-1
LED indicators
4.2 Standard Function Parameters
Table 5-1
Standard Function Parameters
Param.
Parameter Name
Setting Range
Default
Attr
Group F00: System Parameters
F00.00
Setting of User
Password
0
~
65535
0
×
F00.01
Function code display
0: Display all function code
1
×
1: Display F00.00
、
F00.01 and user
setting function code
2: Display F00.00
、
F00.01 and the
function code different with factory
setting
F00.02
Parameter Protection
0: All parameter programmable
0
×
1: Only F00.02 and this parameter
programmable
F00.04
Parameter Initialization
0: No operation
0
×
1: Restore all parameters to factory
default (excluding motor
parameters)
2: Clear fault record
3: Restore user backup parameters
4: Back up current user parameters
5: Restore factory default(include
motor parameter)
6: Power consumption zero-
clearing(U00.35)
F00.06
Parameter
editing mode
0:Editable via keypad and
RS485
0
×
1:Editable via keypad
2:Editable via RS485
F00.08
Motor 1 control mode
0: Voltage/Frequency (V/F)
control
1
×
1:Sensor-less vector control 1
2: Sensor-less vector control 2
F00.09
DI7/HI input mode
0:Digital input terminal 7
0
×
1: Pulse input
F00.12
PWM optimization
Unit's place: PWM modulation
mode
100
×
0: Fixed carrier
1: Random carrier