FR150A Series Multifunctional Compact
Inverter
- 39 -
1:Hold when power off
Ten’s place: select if it can be
reduced to negative
0:Disable
1:Enable
F12.51
UP/DOWN speed of
Multi-reference
0.0
~
100.0% (0.0%Invalid)
0.0%
△
Group F13 Process PID
F13.00
PID setting
0: F13.01 digital setting
0
×
1: keypad potentiometer
2: AI1
3: Communication
4: Multi-Reference
5: DI7/HI pulse input
6: AI2
F13.01
PID digital setting
0.0
~
100.0%
50.0%
△
F13.02
PID feedback
0: AI1
0
×
1: AI2
2: Communication
3: AI1+AI2
4: AI1-AI2
5: Max{AI1
,
AI2}
6: Min{AI1
,
AI2}
7: DI7/HI pulse input
F13.03
PID setting feedback
range
0.0
~
6000.0
100.0
△
F13.04
PID action direction
0: Forward action
0
×
1: Reverse action
F13.05
Filtering time of PID
setting
0.000
~
10.000s
0.000s
△
F13.06
Filtering time of PID
feedback
0.000
~
10.000s
0.000s
△
F13.07
Filtering time of PID
output
0.000
~
10.000s
0.000s
△
F13.08
Proportional gain Kp1
0.0
~
100.0
1.0
△
F13.09
Integration time Ti1
0.01
~
10.00s
0.10s
△
F13.10
Differential time Td1
0.000
~
10.000s
0.000s
△
F13.17
PID offset limit
0.0
~
100.0%
1.0%
×
F13.22
PID output frequency
upper limit
PID output frequency lower limit
~
100.0%
(
100.0% corresponds to
maximum frequency
)
100.0%
×
F13.23
PID output frequency
lower limit
–100.0%
~
PID output frequency
lower limit
0.0%
×
F13.24
Low value of
PID feedback loss
0.1
~
100.0%
0.0%: Not judging feedback loss
0.0%
×
F13.25
Detection time for low
value of
PID feedback loss
0.0
~
30.0s
1.0s
×
F13.26
PID operation at stop
Unit’s place: PID operation
selection when stop
0:Do not operate when stop
1:Operate when stop
00000
×
Ten’s place: output is limited by
output frequency
0:No limited