FR150A Series Multifunctional Compact
Inverter
- 26 -
1:Grounding short-circuit
detection before the first starts
2:Grounding short-circuit
detection before each starts
Hundred
’s place: Speed tracking
0:Track from zero speed
1:Track from max frequency
Thousand
’s place: Select if Jog
function takes the priority
0:Disable
1:Enable
Ten thousand
’s place: Tracking
direction
0: Last direction when stop
1: Positive direction
2: Negative direction
3: Starting direction
F02.05
Start frequency
0.00
~
10.00Hz
0.00Hz
×
F02.06
Startup frequency holding
time
0.0
~
100.0s
0.0s
×
F02.07
Startup DC brakin current
0.0
~
150.0%
0.0%
×
F02.08
DC braking time at start
0.0
~
100.0s
0.0s
×
F02.09
Speed search current
0.0
~
180.0%
100.0%
△
F02.10
Sped search decel time
0.0
~
10.0s
1.0s
×
F02.11
Sped search coefficient
0.01
~
5.00
0.30
△
F02.12
Stop mode
0: Ramp to stop
0
×
1: Coast to stop
F02.13
Initial frequency of stop DC
braking
0.01
~
50.00Hz
2.00Hz
×
F02.14
Stop DC braking current
0.0
~
150.0%
0.0%
×
F02.15
Waiting time of stop DC
braking
0.0
~
30.0s
0.0s
×
F02.16
Stop DC braking time
0.0
~
30.0s
0.0s
×
F02.17
Dynamic brake
0: Disabled
0
×
1: Enabled
2: Enabled at running
3: Enabled at deceleration
F02.18
Dynamic Brake
Voltage
480
~
800V
700V
×
F02.19
Brake use ratio
5.0
~
100.0%
100.0%
×
F02.20
0Hz output selection
0: No voltage output
0
×
1: Voltage output
F02.21
Auto-start of power-on
again
0: Invalid
0
△
1: Valid
F02.22
Waiting time between
auto-start and power-on
again
0.0~10.0s
0.5s
△
Group F03: Accel/Decel Parameters
F03.00
Accel time 0
0.0
~
6000.0s
15.0s
△
F03.01
Decel time 0
0.0
~
6000.0s
15.0s
△
F03.02
Accel time 1
0.0
~
6000.0s
15.0s
△
F03.03
Decel time 1
0.0
~
6000.0s
15.0s
△
F03.04
Accel time 2
0.0
~
6000.0s
15.0s
△
F03.05
Decel time 2
0.0
~
6000.0s
15.0s
△
F03.06
Accel time 3
0.0
~
6000.0s
15.0s
△