3.3 Viewing Status Parameters
There are stop state parameters and running state parameters.
It has 4 status parameters in the stop or running state .You can press “>>” on the keypad to display
status parameters. Which parameters are displayed is determined by the values of F16.03
~
F16.06
(
Running state parameters 1
~
4
)
、
F16.07
~
F16.10
(
stop state parameters1
~
4
),
it can select the
U00 group.
3.4 Motor Auto-tuning
Tuning is valid only when the keyboard command mode. Set tuning mode (stationary or rotating),
press the ENT key to confirm, the keyboard will display TUNE, then press the RUN key, the inverter
will drive motor acceleration and deceleration, positive inversion operation,and the run indicator lights.
Tuning duration of about two minutes, when the display TUNE message disappears, returning to
normal parameter display status, which means that the tuning is completed.
3.5 Password Setting
The inverter provides password protection function, it is set a user's password when F00.00 set to
nonzero. If five minutes without operating the keypad, the password protection is effective, and the
keypad will show “-----”, then the user must enter the correct password to enter the regular menu,
otherwise inaccessible.
There are three ways a user password into force:
Method 1: Set F00.00 parameter to nonzero, then press the ESC + ENT key.
Method 2: Set F00.00 parameter to nonzero, then do not use the keypad within five minutes.
Method 3: Set F00.00 parameter to nonzero, then completely power down and then power.
If you want to cancel the password protection functions, only through a password to enter, and set
F00.00 to 0.
3.6 Keypad lock
3.6.1 Keypad lock
The following three methods to any one immediately lock all or part of the keypad buttons; see the
definition of the function code F16.02.
Method 1:Set F16.02parameter to nonzero, then press the ESC + ENT key.
Method 2:Set F16.02 parameter to nonzero, and then do not use the keypad within five minutes.
Method 3:Set F16.02 parameter to nonzero, then completely power down and then power.
3.6.2 Keypad unlock
Press the ESC + >> keys to unlock. Unlocking operation does not change the value of F16.02,
That means when Meet the keypad locking conditions, the keypad will be locked again. If you want the
control panel no longer be locked, after unlocking the F16.02 must change the value to 0.
3.7 Shortcut menus function code description
Factory setting mode is changed to be shortcut menu mode (F00.01=1) in the software
version above V1.07, group 17 is for the parameters of shortcut menu.
The difference of display between shortcut manual and basic menu is in the second level
menu, please refer to below the details of difference and the switching method.
Menu mode
Shortcut menu
Basic menu
Display
difference
F01.01.
The last digit of F01.01. function
code is with radix point, no
flashing
F01.01 function code is
without radix point, and flashing
Function
difference
1. Press
or
for
up-down switch in F17 function
code
2.
can’t return back to
first level menu
1. Press
or
up-down switch in
sequency
2. Press
return back to first level
menu
F01.01