INSTALLATION AND SETUP
Programming Menus
18
Programming Menus
RW = Read and Write, R = Read Only, W = Write Only
RC = Adjustable parameter while the pump is running (Running Change).
Some of the ranges below are scaled by a Modbus
multiplier
(shown in the table as multi = x.x). For exam
-
ple, a voltage of 100 V is reported by Modbus as 1000, so the user has to multiply the Modbus value by 0.1
for the actual reading value.
Programming: Basic Setup Menu
Mod
bus
RW
RC
Menu / Parameter
Name
Range
Description
400
RW
N
Application
0 - Custom
1 - Submersible Pump
2 - Surface Pump
Selecting an application resets the parameters described
below to default values.
Custom
defaults:
There are no defaults when choosing the Custom applica
-
tion.
Submersible
Pump defaults:
Service Factor = 100 (multiplier scaled by 0.01; 100 =
1.00) This parameter cannot be changed for Submersible
pumps.
Trip Class = S (Submersible)
Underpower Level = 65 (65%)
Surface
Pump defaults:
Service Factor = 115 (1.15)
Trip Class = 10 (Class 10)
Underpower Level = 20 (20%)
430
431
RW
N
Nominal
Voltage
120.0 to 7200;
208.0 (default)
multi = 0.1
The motor nameplate voltage rating.
401
RW
N
FLA/SFA
1.0 to 1000.0;
1.0 (default)
multi = 0.1
Surface Pump: FLA
Submersible Pump: SFA
Custom: FLA
For surface motor applications, this should be set to the
FLA listed on the motor nameplate, or as listed in the
Franklin Electric AIM manual.
For submersible motor applications, set according to the
SFA listed in the Franklin Electric AIM manual.
506
RW
Y
Power Fail Mode
0 - Off (default)
1 - Last
The operational state for the SubMonitor Connect to
return to after recovery from a loss of power. If “Last” is
selected, and motor was running before the power fail,
the motor may start running again when power resumes.
432
RW
N
Overvoltage
(enable)
0 - Off
1 - Fault and Alarm (default)
2 - Alarm Only
An overvoltage alarm triggers if the calculated
average
of
the three line-to-line voltages exceeds the user set
nominal voltage by the over voltage percentage (next
menu item) continuously for a time exceeding the trip
time. The trip time is set in
Advanced Setup > Motor
Protection > Voltage > Overvoltage > Time to Trip
.
Содержание SUBMONITOR CONNECT MT1111
Страница 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Страница 60: ...SPECIFICATIONS Wiring Diagrams for Panels 60 Standard SMS Panel Using Current Transformers 200 480VAC MT1311 ...
Страница 61: ...SPECIFICATIONS Wiring Diagrams for Panels 61 Standard SMS Panel Using Current Transformers 600VAC MT1311 ...
Страница 62: ...SPECIFICATIONS Wiring Diagrams for Panels 62 Standard SMS Panel with PWM Contactor Output MT2211 ...
Страница 63: ...SPECIFICATIONS Wiring Diagrams for Panels 63 Reduced Voltage SMS Panel with Relay Contactor Output MT1311 ...
Страница 66: ...SPECIFICATIONS Wiring Diagrams for Panels 66 Reduced Voltage SMS Panel with PWM Contactor Output MT2211 ...
Страница 72: ...800 348 2420 franklinwater com For technical assistance please contact Form 250001701 Rev 002 06 19 ...
Страница 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Страница 142: ...ESPECIFICACIONES Diagramas de cableado para paneles 70 Panel SMS estándar con salida de contactor PWM MT2211 ...
Страница 146: ...ESPECIFICACIONES Diagramas de cableado para paneles 74 Panel SMS de voltaje reducido con salida de contactor PWM MT2211 ...
Страница 152: ...800 348 2420 franklinagua com Para la ayuda técnica por favor póngase en contacto Form 250001701 Rev 002 06 19 ...
Страница 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Страница 220: ...SPÉCIFICATIONS Diagrammes de câblage pour les panneaux 68 Panneau SMS standard avec sortie de contacteur PWM MT2211 ...
Страница 229: ...NOTES 77 NOTES ...
Страница 230: ...NOTES 78 NOTES ...
Страница 232: ...800 348 2420 franklinwater com Pour l aide technique entrez s il vous plaît en contact Form 250001701 Rév 002 06 19 ...