INSTALLATION AND SETUP
Electrical Installation
13
2.
Pilot Device
(D3, D4)
MT1311/ MT2211 only.
HOA switch inputs. These dry inputs are wired to a door-
mounted pilot device such as an HOA switch.
•
SG - Common
•
D3 - Hand Signal
•
D4 - Auto Signal
3.
Dry Inputs
- (D1, D2)
MT1311/ MT2211 only.
These connections
provide input for a wide selection of switches or programma
-
ble controls, such as use of float switch (High Float/Low Float)
inputs.
•
SG - Common
•
D1 - Auto Run/Low Float
•
D2 - Shut Down/High Float
4.
Voltage (Wet) Inputs
- (V1, V2)
MT1311/ MT2211 only.
These connections provide input for various
types of voltage control signals. This wet input can be used for remote start/stop of a pump motor,
such as in an irrigation system, building management control, or programmable logic control. Refer to
“Fill/Drain using Float Switches” on page 27
for further information.
•
Voltage input pairs accept AC/DC voltages 12 V to 240 V± 10%, up to 5 mA.
•
Inputs can be programmed to be activated by either an incoming voltage signal (Active High) or a
loss of voltage (Active Low). Default state is Active High.
5.
Contactor Control Circuit
- (M2, M1)
MT1311/ MT2211 only.
Provides a factory-wired TRIAC signal
capable of closing up to 2 A contactors at 24 VAC to 600 VAC.
6.
Contactor Power Output
- (C+, C-)
MT2211 only.
This factory-wired circuit provides 24 V AC PWM
output to close only FCS manufactured contactors 100AF frame size and smaller.
7.
Relay Output
- (01, 02) The O1/O2 connectors are the connections for a programmable relay output.
This relay can be configured to close in various situations. Connect an external light, horn, or other
signaling device to the relay output to indicate the fault condition. By default, O1/O2 closes when the
SubMonitor Connect is in the fault condition. These relay contacts are rated for up to 1 A at 240 VAC/
VDC.
8.
PT100/PT1000
- (I+, V+, I-/V-) Analog input reading of motor winding and lower bearing temperature
from external sensors.
•
I+ Positive connection for excitation current circuit for two, three, and four wire PT100/PT1000 RTD
sensors.
•
V+ Positive connection for voltage sensing circuit for two, three, and four wire PT100/PT1000 RTD
sensors.
•
I-/V- Negative connection for both the excitation circuit and voltage sensing circuit for two, three,
and four wire PT100/PT1000 RTD sensors.
9.
Insulation Check
- (Ground, W) This output puts a small voltage across a motor winding (W) and
ground. A fault occurs if the measured resistance on the motor winding is less than insulation check
resistance trip threshold setting. The default setting is off; the Fault trigger default setting is 500 kΩ;
the Alarm trigger default setting is 1000 kΩ. Refer to
for further
information.
10.
RS-485 Modbus
- (-, +, SG) This RS-485 connection is for Modbus RTU communications I/O using
shielded twisted pair cable.These connections provide access for external computer-based monitoring
and control.
•
+ Positive RS-485 wire
•
- Negative RS-485 wire
•
SG Used for the shield wire
•
Termination Switches (above this connector) Leave both 1 and 2 in the OFF position.
Содержание SUBMONITOR CONNECT MT1111
Страница 1: ...franklinwater com SUBMONITORCONNECT Installation and Operation Manual ...
Страница 60: ...SPECIFICATIONS Wiring Diagrams for Panels 60 Standard SMS Panel Using Current Transformers 200 480VAC MT1311 ...
Страница 61: ...SPECIFICATIONS Wiring Diagrams for Panels 61 Standard SMS Panel Using Current Transformers 600VAC MT1311 ...
Страница 62: ...SPECIFICATIONS Wiring Diagrams for Panels 62 Standard SMS Panel with PWM Contactor Output MT2211 ...
Страница 63: ...SPECIFICATIONS Wiring Diagrams for Panels 63 Reduced Voltage SMS Panel with Relay Contactor Output MT1311 ...
Страница 66: ...SPECIFICATIONS Wiring Diagrams for Panels 66 Reduced Voltage SMS Panel with PWM Contactor Output MT2211 ...
Страница 72: ...800 348 2420 franklinwater com For technical assistance please contact Form 250001701 Rev 002 06 19 ...
Страница 73: ...ESPAÑOL ES franklinagua com SUBMONITORCONNECT Manual de instalación y funcionamiento ...
Страница 142: ...ESPECIFICACIONES Diagramas de cableado para paneles 70 Panel SMS estándar con salida de contactor PWM MT2211 ...
Страница 146: ...ESPECIFICACIONES Diagramas de cableado para paneles 74 Panel SMS de voltaje reducido con salida de contactor PWM MT2211 ...
Страница 152: ...800 348 2420 franklinagua com Para la ayuda técnica por favor póngase en contacto Form 250001701 Rev 002 06 19 ...
Страница 153: ...franklinwater com FRANÇAIS FR SUBMONITORCONNECT Manuel d installation et d utilisation ...
Страница 220: ...SPÉCIFICATIONS Diagrammes de câblage pour les panneaux 68 Panneau SMS standard avec sortie de contacteur PWM MT2211 ...
Страница 229: ...NOTES 77 NOTES ...
Страница 230: ...NOTES 78 NOTES ...
Страница 232: ...800 348 2420 franklinwater com Pour l aide technique entrez s il vous plaît en contact Form 250001701 Rév 002 06 19 ...