32
Conn.
Designation
Function/assignment
CON1 L1, L2, L3
Supply connection, power supply, protection class 1
PE
PE
Ground connection, PE connection
CON2 RSA
Bus connection RS485, RSA, MODBUS-RTU; SELV*
CON2 RSB
Bus connection RS485, RSB, MODBUS-RTU; SELV*
CON2 GND
GND reference ground for control interface, SELV*
CON2 IO1
IN2: Digital input - positive logic (factory setting: Enable)
function parameterizable, SELV*
- FAN OFF: Pin open or applied voltage < 1.5 VDC
- FAN ON: applied voltage 3.5-50 VDC
CON2 IO2
IN1: Analog input 0-10 V
0-10 V, Ri=100 K, parameterizable as set value or measured value (factory setting: 9,8V
→
560rpm/0,5V
→
0rpm)
SELV*
CON2 IO3
OUT1: Analog output 0-10 V
0-10 V, max 5 mA (factory setting: 0rpm
→
0,5V/560rpm
→
9,8V)
SELV
CON2 V out
Voltage output 10 VDC +/-5%, Pmax=800 mW
short-circuit-proof, supply for external devices, SELV*
CON2 COM
Status relay, floating status contact; common connection, nominal voltage 250 VAC; max 2 A (AC1): min
10 mA; Reinforced insulation in accordance with EN60335-1, EN61800-5-1, UL60730-1
CON2 NC
Status relay, floating status contact, break for failure