![Formula Air E-PURE ASPRA P10000 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/formula-air/e-pure-aspra-p10000/e-pure-aspra-p10000_manual_2320246028.webp)
ENGLISH
User manual | Filter E-PURE ASPRA P10000
www.formula-air.com
28
29
5. Usage
Error-
light *
Display
notification **
Problem
Consequence
Solution /
Explanation
OFF
Cleaning
routine
initiated.
Waiting for fan
to spin down
xx:xxs
None
Brush started, in xxx seconds the
brush will start moving downwards
OFF
Brush
moving down
time out in:
xx:xxs
None
Brush is moving downwards, once
at the bottom, it will return to the
upward position.
N.A.
(If the bush does not reach the
bottom
within the set time (xxx), the
unit will
provide an error.)
OFF
Brush
moving up
time out in:
xx:xxs
None
Brush is going up Depending on
the program, after returning,
it will go down again or the fan
and high voltage will turn on after
a few seconds
N.A.
(If the bush does not reach
the top
within the set time (xxx), the
unit will
provide an error.)
OFF
Local
setpoint for
fan speed:
xx%
None
Local set point of the fan has been
changed to the indicated value.
Text will be displayed when
the fan
set point is locally changed
using
the FAN + 10%.
OFF
Central control
active.
Local setting of
fan speed is
NOT allowed
None
If the device is connected to a
central control (to be ordered
separately), the device will not
respond to a local change of the
fan set point.
Text will be displayed if one
tries to locally alter the fan
set point with the FAN +
10% button, while the unit is
connected to a central control.
OFF
Filter time-out
on: date
Check filter
fan: xx%
I: xxx uA
brush: xxhxxm
Collectors
might be
saturated
The purifying capacity of the unit
might be reduced.
Check collectors and replace if
necessary.
OFF
TAKE CARE:
Filter timer
will be reset
Press again to
reset filter
timer
None
ONLY IF THE COLLECTORS HAV
IN FACT BEEN REPLACED BY NEW
CLEAN COLLECTORS: press button
again.
Otherwise DO NOT UNDERTAKE
ACTION
By pressing the button again
the system is instructed to
reset the filtertimer. This is
needed if COMPLETELY NEW
COLLECTORS have been
mounted. In any other
situation do not press the button
again, as the filter timer will not
be accurate any longer.