B) Minimum heating output adjustment
- set heating output adjuster maxR (pic. 13) to minimum (turn it fully counter-clockwise after removing the protective cap);
- adjust CO
2
in flue gas by turning offset adjuster C (pic. 23) and verify CO
2
to be within the range stated in no. 17 chart;
- exit chimney sweep mode by setting selector 9 (pic. 1) to any position other than WINTER;
Fuel
CO
2
Methane
8.8 ÷ 9.1
Propane
9.8 ÷ 10.1
No. 17 chart – CO
2
rates
A
C
B
pic. 22 - Adaptation to other gas types
pic. 23 - Gas valve adjustment