General information for fitters, maintenance technicians and users 

This INSTRUCTION MANUAL, which is an integral and indispensable part of the product, must be handed over to the user by the in-

staller and must be kept in a safe place for future reference. The manual must accompany the boiler should it be sold or its possession 

transferred. Following to the boiler installation, the fitter is to advise the user about boiler operation and its safety devices.

This boiler must be used for the purposes for which it has been intended. 

Any other use shall be considered incorrect and therefore dangerous.

The boiler must be installed by qualified personnel, in compliance with applicable laws and standards and according to the manufac-

turer’s instructions given in this manual. Incorrect installation may cause injury to persons and/or animals and damage to property. The 

manufacturer shall not be held liable for any such injury and/or damage. 

Damage and/or injury caused by incorrect installation or use and/or damage and/or injury due to non-observance of the manufacturer’s 

instructions shall relieve the manufacturer from any and all contractual and extra-contractual liability.

Before installing the boiler, check that the technical data correspond to the requirements for its correct use in the system.

Check that the boiler is intact and it has not been damaged during transport and handling: do not install equipment which is damaged 

and/or faulty.

Do not obstruct the air suction openings.

Only manufacturer approved and supplied accessories or optional kits (including electric ones) are to be installed.

Properly dispose of the packaging as all the materials can be recycled. The packaging must therefore be sent to specific waste manage-

ment sites.

Keep the packaging out of the reach of children as it may represent a source hazard.

In the event of failure and/or faulty functioning, switch off the boiler. Do not attempt to make repairs: contact qualified technicians.

Manufacturer approved and supplied parts must be used for all repairs to the boiler.

Non-observance of the above requirements may affect the safety of the boilers and endanger people, animals and property.

The manufacturer, in order to guarantee efficient and correct functioning of the equipment, recommends the boiler to be serviced and 

repaired by an authorized Service Centre which is best trained for the purpose.

Routine boiler maintenance is to be performed according to the schedule indicated in the relevant section of this manual.

Appropriate boiler maintenance ensures efficient operation, environment preservation, and safety for people, animals and 

objects. 

In the event of long periods of inactivity of the boiler, disconnect it from power mains and close the gas tap.

Warning! When power mains are disconnected, boiler electronic anti-frost function will not be operative.

Should there be a risk of freezing, add anti-frost: it is not advisable to empty the system as this may result in damage; use specific anti-

frost products suitable for multi-metal heating systems.

IMPORTANT

Should you smell gas:

- do not turn on or off electric switches and do not turn on electric appliances;

- do not ignite flames and do not smoke;

- close the main gas tap;

- open doors and windows;

- contact a Service Centre, a qualified installer or the gas supply company.

    

Never use flames to detect gas leaks.

   

The boiler is designed for installation in the country indicated on the technical data plate: installation in any other 

   

country may be source of danger for people, animals and objects. 

Содержание TAHITI CONDENSING KC24

Страница 1: ...IST 03 C 234 01 INSTALLATION USE AND MAINTENANCE TAHITI CONDENSING GB...

Страница 2: ...2 Dear Customer Thank You for choosing and buying one of our boilers Please read these instructions carefully in order to properly install operate and maintain the equipment...

Страница 3: ...can be recycled The packaging must therefore be sent to speci c waste manage ment sites Keep the packaging out of the reach of children as it may represent a source hazard In the event of failure and...

Страница 4: ...o install the boiler page 19 3 2 3 Positioning the boiler page 20 3 2 4 Installing the boiler page 20 3 2 5 Boiler room ventilation page 21 3 2 6 Air ue gas system page 21 3 2 6 1 Air ue gas system du...

Страница 5: ...ion page 29 pic 20 System head curves page 31 pic 21 Electric layout page 32 pic 22 Adaptation to other gas types page 34 pic 23 Gas valve adjustment page 34 CHART INDEX No 1 chart Correlation between...

Страница 6: ...d it signals ame presence on burner When the LED is on and blinking it signals an operation malfunc tion see no 2 chart on page 7 9 Boiler operation mode selector When the selector is set to OFF the b...

Страница 7: ...OFF OFF OFF OFF OFF OFF OFF OFF Safety thermostat shutdown GREEN OFF RED L OFF OFF OFF OFF OFF Flue gas thermostat shutdown GREEN OFF OFF RED L OFF OFF OFF OFF Flame absence shutdown GREEN OFF OFF OFF...

Страница 8: ...ween subsequent ignitions which depends on the selected operating range standard range 4 minutes reduced range 2 minutes Should water temperature in the system fall below the default value see 3 2 11...

Страница 9: ...ost protection be necessary for the boiler and CH system select winter position through no 9 knob CH system can be effectively protected from freezing by means of speci c anti freezing addictives suit...

Страница 10: ...ating When CH ow water overheats the boiler is shut down no 3 LED red starts ashing Should the above happen contact an authorized Service centre or quali ed personnel for service 1 3 3 Shut down due t...

Страница 11: ...ler receive incorrect information from the OpenTherm remote control optional equipment or should it not receive any due to remote control malfunctioning or incorrect connection between the boiler and...

Страница 12: ...composite and stainless steel heat exchanger with air purging device Twin shutter modulating gas valve with constant air gas ratio Modulating electronically managed ue gas discharge fan Three speed pu...

Страница 13: ...input adjusting trimmer Ignition heat input adjusting trimmer CH water temperature range adjusting device standard or reduced Ignition ame spread function Timer controlled CH thermostat 240 seconds s...

Страница 14: ...iew Top view pic 3 Dimensions S Condensate drain F Water mains intake G Gas intake SI Inspection trap plug M CH system ow C DHW ow KC model only SV 3 bar safety valve drain cock RC Filling tap R CH sy...

Страница 15: ...rain G Gas intake M CH system ow C DHW ow F Water mains intake R CH system return 1 Condensate drain siphon 2 Modulating gas valve 3 Safety thermostat 4 CH temperature probe 5 Modulating fan 6 Primary...

Страница 16: ...CO2 min max min max min max Methane Gas G20 31 4 8 7 30 5 9 6 33 2 9 6 35 4 20 8 8 9 1 Propane Gas G31 31 4 8 7 30 5 9 6 33 2 9 6 35 4 37 9 8 10 1 No 4 chart KC 32 model adjustment rates Hot water su...

Страница 17: ...1 bar KC 24 Max heat output Min heat output 30 heat output Casing heat loss with burner on 1 4 2 1 Casing heat loss with burner off 0 2 0 2 Chimney heat loss with burner on 2 6 2 2 Flue gas system ma...

Страница 18: ...ing heat loss with burner off 0 2 0 2 Chimney heat loss with burner on 2 6 2 2 Flue gas system mass ow rate g s 12 4 3 1 Flue gas temp air temp C 67 49 Maximum heat output ef ciency rating 60 80 C 96...

Страница 19: ...as it may be dangerous Manufacturer shall not be held responsible for harm to people and or animals and or damage to property due to failure in following the above mentioned instructions Packaging inc...

Страница 20: ...n the system employ non acid product available on the market Do not use solvents as they could damage system components Furthermore in the central heating system either new or modernized it is always...

Страница 21: ...ry to have air ue gas system ducts inspected as they might be obstructed or inadequate to ue gas discharge into the atmosphere In air intake ue gas discharge systems speci c manufacturer approved cond...

Страница 22: ...ore the combustion chamber heat exchanger Type C33 Boiler intended for connection to vertical outlet and intake ducts connected to the outside by means of coaxial or split ducts The distance between a...

Страница 23: ...rmissible length is to be reduced by 0 5 meter The wall terminal reduces maximum permissible length by 1 5 meters The air intake duct is to be tilted by 1 toward its exit in order to avoid rain water...

Страница 24: ...ed to air intake ue gas discharge system implemented with original rigid and smooth ducts delivered by the manufacturer pic 12 Dimensions for connection to air intake and ue gas discharge split pipe s...

Страница 25: ...the tower before starting combustion checking procedure pic 14 In order to verify combustion performance the following measurements must be implemented assess combustion air from no 1 opening pic 15...

Страница 26: ...ent in system compo nents and damage the pump and the heat exchanger CENTRAL HEATING CH ow and CH return pipes must be connected to the relevant 3 4 M and R couplings on the boiler pic 6 When calculat...

Страница 27: ...and service procedures Power supply to the boiler is to be tted with a differential magnetic thermal automatic switch of appropriate shut down capacity Electrical power supply is to be appropriately...

Страница 28: ...cables now should the external probe or the phone operation device not be in need to be installed close the remote control housing othe rwise follow the instructions described in the following paragr...

Страница 29: ...e wall facing north north east Do not install in window area next to ventilation openings or heat sources The external temperature probe automatically modi es CH ow temperature in relation to sensed o...

Страница 30: ...oiler and as soon as the system reaches working temperature stop the pump and repeat the air purging procedures allow the system to cool and restore water pressure to 1 1 3 bars WARNING As far as dome...

Страница 31: ...y valve is not blocked there are no water leaks the pump is not blocked WARNING The boiler is equipped with a pump with three speeds corresponding to the residual head to the system according to the c...

Страница 32: ...ning the external probe codes are not the same TA room thermostat jumper is to be removed Only in KR equipped by external cylinder with NTC probe and tem perature regulation on the boiler Only in KR e...

Страница 33: ...option CT option phone operation device T C 0 2 4 6 8 0 27203 24979 22959 21122 19451 10 17928 16539 15271 14113 13054 20 12084 11196 10382 9634 8948 30 8317 7736 7202 6709 6254 40 5835 5448 5090 475...

Страница 34: ...tive cap adjust CO2 in ue gas by turning offset adjuster C pic 23 and verify CO2 to be within the range stated in no 17 chart exit chimney sweep mode by setting selector 9 pic 1 to any position other...

Страница 35: ...n and safety for people animals and objects Maintenance and repair procedures are strictly to be carried out by quali ed personnel The manufacturer recommends Customers to contact an authorized Servic...

Страница 36: ...ce it The boiler is not operating no 3 LED red is ashing Boiler will resume operation when selector 9 is brought to reset position and CH water temperature goes back to normal parameters Boiler safety...

Страница 37: ...no 8 yellow LEDs are simultaneously ashing Boiler will automatically resume operation as soon as malfunction ends The boiler is not receiving data from remote control Remote control connection is int...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...40 Tel 39 0365 878 31 Fax 39 0365 878 576 e mail info fondital it www fondital it The manufacturer reserves the right to modify the data contained herein at any time without notice Uff Pubblicit Fond...