ANTI-FROST

The boiler is equipped with anti-frost function, which is active in SUMMER/WINTER/ANTI-FROST modes.

When central heating water temperature sensor detects a water temperature of 5°C, the boiler is switched on and stays on at minimum 

heat output until central heating water temperature reaches 30°C or 15 minutes have elapsed.

Should boiler shut down, pump operation is still granted. 

In KC model, anti-frost function protects the domestic hot water system as well.

When domestic hot water probe detects a temperature of 5°C, the boiler ignites and stays on at minimum heat output until domestic hot 

water temperature reaches 10°C or 15 minutes have elapsed (the deviating valve is set to domestic hot water position).

Should boiler shut down, pump operation is still granted. 

In CH only boilers equipped with a DHW supply external cylinder, anti-frost function protects the cylinder as well. The function is active 

only for cylinders equipped with 

β

=3435 type NTC probe (refer to cylinder technical data).

When cylinder water temperature probe detects a water temperature of 5°C, the boiler is switched on and stays on at minimum heat ou-

tput until cylinder water temperature reaches 10°C or 15 minutes have elapsed (the deviating valve is set to domestic hot water position).

Should the boiler shut down, pump operation is granted. 

  

Anti-frost function protects the boiler only and not the whole central heating system.

 

Central heating system is to be protected by means of an ambient thermostat, although this is disabled when the 

 

boiler is set to the anti-frost and OFF modes. Should anti-frost protection be necessary for the boiler and CH system, 

 

select winter position through no. 9 knob.

CH system can be effectively protected from freezing by means of specific anti-freezing addictives suitable in multi-metal systems. 

Do not use automotive anti-frost products, and periodically check anti-frost product effectiveness.

PUMP AND DEVIATING VALVE ANTI-BLOCKING FUNCTION

Where the boiler is to remain inactive and:

- no. 9 selector is not set to the OFF position; 

- boiler is not disconnected from electric main power supply;

the circulation pump (KC and KR) and three-way valve (KC), are operated for 3 minutes every 24 hours in order to prevent blockage.

1.2.3. External probe operation (optional equipment)

The boiler can be equipped with an external temperature probe (optional equipment), through which the boiler adjusts CH water tem-
perature according to outdoor temperature, in other words, increasing CH water temperature when outdoor temperature decreases and 
vice-versa, providing increased energy saving operation (such boiler mode is called “sliding temperature operation”) . 

Boiler microprocessor program determines CH water temperature variations.

When an external temperature probe is connected to the boiler, CH water temperature adjusting knob, no. 
11 (pic. 1), loses its function and becomes a fictitious room temperature adjusting device. 
When no. 11 knob is turned fully counter-clockwise, selected room temperature is 15°C; when set to 9:00 
hours selected room temperature is 18°C; when set to 12:00 hours selected room temperature is 25°C; 
when set to 3:00 hours selected room temperature is 32°C; when is turned fully clockwise selected room 
temperature is 35°C; 
For best curve setting, it is advisable a position close to 20°C. 
Refer to 3.2.14. paragraph for detailed sliding temperature operation.

Содержание TAHITI CONDENSING KC24

Страница 1: ...IST 03 C 234 01 INSTALLATION USE AND MAINTENANCE TAHITI CONDENSING GB...

Страница 2: ...2 Dear Customer Thank You for choosing and buying one of our boilers Please read these instructions carefully in order to properly install operate and maintain the equipment...

Страница 3: ...can be recycled The packaging must therefore be sent to speci c waste manage ment sites Keep the packaging out of the reach of children as it may represent a source hazard In the event of failure and...

Страница 4: ...o install the boiler page 19 3 2 3 Positioning the boiler page 20 3 2 4 Installing the boiler page 20 3 2 5 Boiler room ventilation page 21 3 2 6 Air ue gas system page 21 3 2 6 1 Air ue gas system du...

Страница 5: ...ion page 29 pic 20 System head curves page 31 pic 21 Electric layout page 32 pic 22 Adaptation to other gas types page 34 pic 23 Gas valve adjustment page 34 CHART INDEX No 1 chart Correlation between...

Страница 6: ...d it signals ame presence on burner When the LED is on and blinking it signals an operation malfunc tion see no 2 chart on page 7 9 Boiler operation mode selector When the selector is set to OFF the b...

Страница 7: ...OFF OFF OFF OFF OFF OFF OFF OFF Safety thermostat shutdown GREEN OFF RED L OFF OFF OFF OFF OFF Flue gas thermostat shutdown GREEN OFF OFF RED L OFF OFF OFF OFF Flame absence shutdown GREEN OFF OFF OFF...

Страница 8: ...ween subsequent ignitions which depends on the selected operating range standard range 4 minutes reduced range 2 minutes Should water temperature in the system fall below the default value see 3 2 11...

Страница 9: ...ost protection be necessary for the boiler and CH system select winter position through no 9 knob CH system can be effectively protected from freezing by means of speci c anti freezing addictives suit...

Страница 10: ...ating When CH ow water overheats the boiler is shut down no 3 LED red starts ashing Should the above happen contact an authorized Service centre or quali ed personnel for service 1 3 3 Shut down due t...

Страница 11: ...ler receive incorrect information from the OpenTherm remote control optional equipment or should it not receive any due to remote control malfunctioning or incorrect connection between the boiler and...

Страница 12: ...composite and stainless steel heat exchanger with air purging device Twin shutter modulating gas valve with constant air gas ratio Modulating electronically managed ue gas discharge fan Three speed pu...

Страница 13: ...input adjusting trimmer Ignition heat input adjusting trimmer CH water temperature range adjusting device standard or reduced Ignition ame spread function Timer controlled CH thermostat 240 seconds s...

Страница 14: ...iew Top view pic 3 Dimensions S Condensate drain F Water mains intake G Gas intake SI Inspection trap plug M CH system ow C DHW ow KC model only SV 3 bar safety valve drain cock RC Filling tap R CH sy...

Страница 15: ...rain G Gas intake M CH system ow C DHW ow F Water mains intake R CH system return 1 Condensate drain siphon 2 Modulating gas valve 3 Safety thermostat 4 CH temperature probe 5 Modulating fan 6 Primary...

Страница 16: ...CO2 min max min max min max Methane Gas G20 31 4 8 7 30 5 9 6 33 2 9 6 35 4 20 8 8 9 1 Propane Gas G31 31 4 8 7 30 5 9 6 33 2 9 6 35 4 37 9 8 10 1 No 4 chart KC 32 model adjustment rates Hot water su...

Страница 17: ...1 bar KC 24 Max heat output Min heat output 30 heat output Casing heat loss with burner on 1 4 2 1 Casing heat loss with burner off 0 2 0 2 Chimney heat loss with burner on 2 6 2 2 Flue gas system ma...

Страница 18: ...ing heat loss with burner off 0 2 0 2 Chimney heat loss with burner on 2 6 2 2 Flue gas system mass ow rate g s 12 4 3 1 Flue gas temp air temp C 67 49 Maximum heat output ef ciency rating 60 80 C 96...

Страница 19: ...as it may be dangerous Manufacturer shall not be held responsible for harm to people and or animals and or damage to property due to failure in following the above mentioned instructions Packaging inc...

Страница 20: ...n the system employ non acid product available on the market Do not use solvents as they could damage system components Furthermore in the central heating system either new or modernized it is always...

Страница 21: ...ry to have air ue gas system ducts inspected as they might be obstructed or inadequate to ue gas discharge into the atmosphere In air intake ue gas discharge systems speci c manufacturer approved cond...

Страница 22: ...ore the combustion chamber heat exchanger Type C33 Boiler intended for connection to vertical outlet and intake ducts connected to the outside by means of coaxial or split ducts The distance between a...

Страница 23: ...rmissible length is to be reduced by 0 5 meter The wall terminal reduces maximum permissible length by 1 5 meters The air intake duct is to be tilted by 1 toward its exit in order to avoid rain water...

Страница 24: ...ed to air intake ue gas discharge system implemented with original rigid and smooth ducts delivered by the manufacturer pic 12 Dimensions for connection to air intake and ue gas discharge split pipe s...

Страница 25: ...the tower before starting combustion checking procedure pic 14 In order to verify combustion performance the following measurements must be implemented assess combustion air from no 1 opening pic 15...

Страница 26: ...ent in system compo nents and damage the pump and the heat exchanger CENTRAL HEATING CH ow and CH return pipes must be connected to the relevant 3 4 M and R couplings on the boiler pic 6 When calculat...

Страница 27: ...and service procedures Power supply to the boiler is to be tted with a differential magnetic thermal automatic switch of appropriate shut down capacity Electrical power supply is to be appropriately...

Страница 28: ...cables now should the external probe or the phone operation device not be in need to be installed close the remote control housing othe rwise follow the instructions described in the following paragr...

Страница 29: ...e wall facing north north east Do not install in window area next to ventilation openings or heat sources The external temperature probe automatically modi es CH ow temperature in relation to sensed o...

Страница 30: ...oiler and as soon as the system reaches working temperature stop the pump and repeat the air purging procedures allow the system to cool and restore water pressure to 1 1 3 bars WARNING As far as dome...

Страница 31: ...y valve is not blocked there are no water leaks the pump is not blocked WARNING The boiler is equipped with a pump with three speeds corresponding to the residual head to the system according to the c...

Страница 32: ...ning the external probe codes are not the same TA room thermostat jumper is to be removed Only in KR equipped by external cylinder with NTC probe and tem perature regulation on the boiler Only in KR e...

Страница 33: ...option CT option phone operation device T C 0 2 4 6 8 0 27203 24979 22959 21122 19451 10 17928 16539 15271 14113 13054 20 12084 11196 10382 9634 8948 30 8317 7736 7202 6709 6254 40 5835 5448 5090 475...

Страница 34: ...tive cap adjust CO2 in ue gas by turning offset adjuster C pic 23 and verify CO2 to be within the range stated in no 17 chart exit chimney sweep mode by setting selector 9 pic 1 to any position other...

Страница 35: ...n and safety for people animals and objects Maintenance and repair procedures are strictly to be carried out by quali ed personnel The manufacturer recommends Customers to contact an authorized Servic...

Страница 36: ...ce it The boiler is not operating no 3 LED red is ashing Boiler will resume operation when selector 9 is brought to reset position and CH water temperature goes back to normal parameters Boiler safety...

Страница 37: ...no 8 yellow LEDs are simultaneously ashing Boiler will automatically resume operation as soon as malfunction ends The boiler is not receiving data from remote control Remote control connection is int...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...40 Tel 39 0365 878 31 Fax 39 0365 878 576 e mail info fondital it www fondital it The manufacturer reserves the right to modify the data contained herein at any time without notice Uff Pubblicit Fond...

Отзывы: