37
BOILER STATUS
MALFUNCTION
PROBABLE CAUSE
SOLUTION
No. 2 (red) and no. 8 (yellow) LEDs are
alternatively flashing (in KR boilers with
external cylinder equipped by NTC
probe).
Boiler will automatically resume operation
as soon as malfunction ends
Cylinder probe is not operating
Flow probe is disconnected
Reconnect it
Flow probe is faulty
Replace it
No. 4 (red) and no. 8 (yellow) LEDs are
simultaneously flashing.
Boiler will automatically resume operation
as soon as malfunction ends
The boiler is not receiving data from
remote control
Remote control connection is interrupted
Check connections of remote control
Remote control is faulty
Replace remote control
Boiler is not operating
in DHW mode (KC)
DHW flow switch is not operating
The system has inadequate pressure or
flow rate
Check DHW system
Check flow switch filter
Flow switch sensor is faulty or discon-
nected
Replace it or reconnect it
Flow switch is blocked
Replace it