Operating Manual EMGZ421
24
Unit of force
Use:
This parameter stores the force unit of the sensor.
Range:
N,
kN
Default:
N
Sensitivity sensor A
Use:
To get the correct force value, the electronic unit has to know the
sensitivity of the force sensors, that means how much signal the sensor
will answer by nominal force. Standard for FMS force sensors is
1.8mV/V.
Range:
0.1
to
3.0
Default:
1.8
Increment:
0.1
Unit:
[mV/V]
Sensitivity sensor B
Use:
Identical
with
Sensitivity sensor A
.
Range:
0.1
to
3.0
Default:
1.8
Increment:
0.1
Unit:
[mV/V]
Min. limit value A+B
Use:
The digital output „Limit value min. A+B“ will be activated if the
threshold value stored in this parameter is passed under. If the
parameter contains a zero value, limit switch monitoring is inactive.
Range:
-9999
to
9999
Default:
0
Increment:
1
Unit:
[N,kN]
Max. limit value A+B
Use:
The digital output „Limit value max. A+B“ will be activated if the
threshold value stored in this parameter is passed over. If the
parameter contains a zero value, limit switch monitoring is inactive.
Range:
-9999
to
9999
Default:
0
Increment:
1
Unit:
[N,kN]
|A–B| > limit
Use:
The digital output „|A–B| > limit“ will be activated if the difference of
the measuring values A and B exceeds the value stored here. If the
parameter contains a zero value, limit switch monitoring is inactive.
Range:
-9999
to
9999
Default:
0
Increment:
1
Unit:
[N,kN]