Operating Manual Web Guide Controller BKS309
23.07.2019
22
8.3
Description of operating parameters
Adjust Reference Position [Ref Pos]
Purpose:
The reference position can be adjusted using this parameter.
Range:
-5.00 to
+5.00
Default: 0.00
Increment:
0.01
Unit:
[mm]
Set Reference Mode [Ref Mode]
Purpose:
This parameter determinates how the reference position is defined. This
can either be the position that is defined with parameter [Ref Pos] or the
actual material position within the sensor when the controller is
switched to automatic operation.
Two settings are possible:
Setting:
[Manual]
Purpose: If
[Manual] is chosen, the Reference Position is taken from the
parameter [RefPos].
Setting:
Automatic [Auto]
Purpose: If
[Auto] behavior is chosen, the Reference Position is determinate by
taking the actual material position within the sensor when the controller
is switched to automatic operation.
Note:
The two parameters [RefMode] and [SafeRef] are conditionally
dependent on each other. If you require one of both functions, either set
[RefMode] to [Auto] or [SafeRef] to [Yes] .
Do not activate both functions simultaneously!
Save the Reference Position [SaveRef]
Purpose:
The parameter saves the last Reference Position change. It sets after re-
booting the Reference Position to the last used value or to 0 (zero).
Two settings are possible:
Setting:
[No]
Purpose: If
[No] behaviour is chosen, the Reference Position is set to 0 after
rebooting (default setting).
Setting:
[Yes]
Purpose: If
[Yes] behavior is chosen, after rebooting the Reference Position is set
to the last used value.