REQUIREMENTS FOR THE COMMONWEALTH OF 

MASSACHUSETTS

For all side wall horizontally vented gas fueled 

equipment installed in every dwelling, building or 

structure used in whole or in part for residential 

purposes, including those owned or operated by 

the Commonwealth and where the side wall ex

-

haust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, 

including but not limited to decks and porches, 

the following requirements shall be satisfied:

INSTALLATION OF CARBON 

MONOXIDE DETECTORS

At the time of installation of the side wall horizon

-

tal vented gas fueled equipment, the installing 

plumber or gasfitter shall observe that a hard 

wired carbon monoxide detector with an alarm 

and battery backup is installed on the floor level 

where the gas equipment is to be installed. In 

addition, the installing plumber or gasfitter shall 

observe that a battery operated or hard wired car

-

bon monoxide detector with an alarm is installed 

on each additional level of the dwelling, building or 

structure served by the side wall horizontal vented 

gas fueled equipment. It shall be the responsibility 

of the property owner to secure the services of 

qualified licensed professionals for the installation 

of hard wired carbon monoxide detectors.

In  the  event  that  the  side  wall  horizontally 

vented  gas  fueled  equipment  is  installed 

in a crawl space or an attic, the hard wired 

carbon  monoxide  detector  with  alarm  and 

battery back-up may be installed on the next 

adjacent floor level.

In  the  event  that  the  requirements  of  this 

subdivision  can  not  be  met  at  the  time  of 

completion  of  installation,  the  owner  shall 

have a period of thirty (30) days to comply with 

the above requirements; provided, however, 

that during said thirty (30) day period, a battery 

operated carbon monoxide detector with an 

alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required 

in accordance with the above provisions shall 

comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

SIGNAGE

A metal or plastic identification plate shall be 

permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust 

vent terminal for the horizontally vented gas 

fueled heating appliance or equipment. The 

sign shall read, in print size no less than 1/2" in 

size, "GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS".

INSPECTION

The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment 

shall not approve the installation unless, upon 

inspection,  the  inspector  observes  carbon 

monoxide detectors and signage installed in 

accordance with the provisions of 248 CMR 

5.08(2)(a) 1 through 4.

EXEMPTIONS: The following equipment is ex

-

empt from 248 CMR 5.08(2)(a) 1 through 4:

•  The equipment listed in Chapter 10 entitled 

"Equipment Not Required To Be Vented" 

in the most current edition of NFPA 54 as 

adopted by the Board; and

•  Product Approved  side  wall  horizontally 

vented gas fueled equipment installed in a 

room or structure separate from the dwell

-

ing, building or structure used in whole or 

in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided 

When the manufacturer of Product Approved 

side wall horizontally vented gas equipment 

provides a venting system design or venting 

system components with the equipment, the 

instructions provided by the manufacturer for 

installation of the equipment and the venting 

system shall include:

•  Detailed instructions for the installation of 

the venting system design or the venting 

system components; and

•  A complete parts list for the venting system 

design or venting system.

Gas Equipment Venting System Not 

Provided

When  the  manufacturer  of  a  Product Ap

-

proved side wall horizontally vented gas fu

-

eled equipment does not provide the parts for 

venting the flue gases, but identifies "special 

venting systems", the following requirements 

shall be satisfied by the manufacturer:

•  The referenced "special venting system" in

-

structions shall be included with the appliance 

or equipment installation instructions; and

•  The "special venting systems" shall be Prod

-

uct Approved by the Board, and the instruc

-

tions for that system shall include a parts list 

and detailed installation instructions.

A  copy  of  all  installation  instructions  for  all 

Product Approved  side  wall  horizontally 

vented gas fueled equipment, all venting in

-

structions, all parts lists for venting instruc

-

tions,  and/or  all  venting  design  instructions 

shall remain with the appliance or equipment 

at the completion of the installation.

Содержание DVF36NHI-C

Страница 1: ...yourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied in...

Страница 2: ...eplace designed for residential ap plications This fireplace must be installed with FMI PRODUCTS LLC vent pipe components and terminations Outside airflex installation is required for both horizontal...

Страница 3: ...fythisfireplaceunderanycircumstances Anyparts removed for servicing must be replaced prior to operating fireplace WARNING Do not use a blower insert heat exchanger insert or other accessory not approv...

Страница 4: ...e fire place inspected annually by a qualified service person 5 You must keep control compartments burners and circulating air passages clean More frequent cleaning may be needed due to excessive lint...

Страница 5: ...h traffic areas windy or drafty areas or near furniture or draperies Proper clearances must be maintained If your fireplace is to be installed directly on carpeting vinyl tile or any combustible mate...

Страница 6: ...ce to combustible materials are for framing purpose only NOTICE Thisfireplaceisintend edforuseassupplementalheat Use this fireplace along with your primary heating system Do not install this fireplace...

Страница 7: ...n US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally...

Страница 8: ...tly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP...

Страница 9: ...e components and terminations The venting system must terminate on the outside of the structure and can not be at tached to a chimney or flue system serving a separate solid fuel or gas burning applia...

Страница 10: ...cial twist lock con nections Twist Lock Procedure Female ends of pipes have locking lugs indentations These lugs will slide straight into match ing slots on male ends of adjacent pipes Push pipe secti...

Страница 11: ...with provided wood screws see Figure 11 Siding standoff must sit flush against exterior fascia material 6 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before conne...

Страница 12: ...hart with critical minimum and maximum dimensions which MUST be met NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent inspection and maintenance WARNING Never run vent downwa...

Страница 13: ...above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insula tion from falling into required clearance space If area above ceiling is a living space install...

Страница 14: ...the configurations for vertical termination VENTING INSTALLATION Continued Figure 18 Vertical Venting Configuration Vertical Venting V 40 max HIGH ALTITUDE INSTALLATION Your FMI PRODUCTS LLC direct v...

Страница 15: ...AK6 75 75 Outside Air Flex Vent Kit CHECK GAS TYPE Use proper gas type for the fireplace unit you are installing If you have conflicting gas types do not install fireplace See retailer where you purch...

Страница 16: ...gulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regulator with Vent Pointing Down FIREPLACE INSTALLATION Continued Apply pipe joint sealant lightly to male NPT threads...

Страница 17: ...LP supply tank valve for propane LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air 4 Check all joints of gas supply piping sys t...

Страница 18: ...oints for leaks 6 Turn off fireplace see To Turn Off Gas to Appliance page 23 REMOVING REPLACING GLASS DOORS CAUTION Do not operate thisfireplacewithabrokenglass door panel or without the glass doorpa...

Страница 19: ...hinges see Figure 26 Set aside to avoid scratches or damage FIREPLACE INSTALLATION Continued 3 Follow these instructions in reverse to reinstall Removing and Installing Inner Door All Models 1 Remove...

Страница 20: ...ner Door Screen and Rod Non Cool Touch Models Only LAVA ROCK EMBER FLAKES AND SCRAP LOG INSTALLATION Lava rock ember flakes and scrap log pieces are included with your fireplace Install these items wh...

Страница 21: ...er and on burner ports see Figure 30 This will create the glowing ember ap pearance as the flame touches the ember flakes Do not block burner ports or pilot ports by overlapping ember flakes in one ar...

Страница 22: ...rn on all electric power to appliance 10 Turn safety shutoff switch to the ON posi tion 11 Visually locate pilot Ignitor should begin to spark and main burner should ignite once flame appears at pilot...

Страница 23: ...e appliance rocker switch is turned OFF the pilot will shut OFF when the main burner shuts OFF 3 When the continuous pilot switch is in the ON position and the appliance rocker switch is turned ON the...

Страница 24: ...and grounding stem If your pilot assembly does not meet these requirements Turn the adjustment screw marked PILOT clockwise to decrease or counterclockwise to increase the flame to proper size see Fi...

Страница 25: ...curing The glass should be cleaned several times with a non ammonia nonabrasive household clean er and warm water after the first two weeks of operation Thereafter clean the glass two or three times...

Страница 26: ...Minimum Inlet Supply Pressure 7 w c DVF 36PSR C DVF 36PHR C DVF 36PSI C DVF 36PHI C DVF 36PSR CC DVF 36PHR CC DVF 36PSI CC DVF 36PHI CC Rating 62 000 Btu hr Gas Type Propane LP Gas Only Ignition Elec...

Страница 27: ...valve is not opening 7 No power to unit or ignition module REMEDY 1 Checktoseeifyouhavegas supply and that equipment shutoff valve is opened 2 Repeat lighting procedure several times to purge all air...

Страница 28: ...c connectors that plug in the face of the gas control valve Confirm the gas control valve is properly grounded to the module 1 Check electrical connec tions 1 Clean and adjust pilot flame for maximum...

Страница 29: ...s blocked 3 Improper venting or exces sive blockage 4 Excessive amounts of em bers and pan material OBSERVED PROBLEM Gas odor even when gas control valve is off Gas odor during combustion Glass soots...

Страница 30: ...F 36PHR C DVF 36NSI C DVF 36PSI C DVF 36NHI C DVF 36PHI C DVF 36NSR CC DVF 36PSR CC DVF 36NHR CC DVF 36PHR CC DVF 36NSI CC DVF 36PSI CC DVF 36NHI CC AND DVF 36PHI CC 10 14 9 7 21 11 32 23 24 26 25 41...

Страница 31: ...ctor 1 20 106702 01 5 Gasket 1 21 120431 01 Burner Base Gasket 1 22 117997 01 Glass Door Retainer 1 23 120142 01 Firebox Leg 4 24 117891 01 Fireplace Handle 4 25 21171 Gas Conduit Cover 1 26 24460 Gas...

Страница 32: ...14 28 8 5 3 4 15 27 21 24 26 32 29 30 31 35 26 38 26 33 36 34 34 39 PARTS MODELS DVF 36NSR C DVF 36PSR C DVF 36NHR C DVF 36PHR C DVF 36NSI C DVF 36PSI C DVF 36NHI C DVF 36PHI C DVF 36NSR CC DVF 36PSR...

Страница 33: ...3 8 x 18 1 25 125068 01 Battery Backup 1 26 125061 01 Valve Module Bracket 1 27 114365 24 Brass Orifice 32 NG 1 114365 16 Brass Orifice 51 LP 1 28 126117 01 Log Assembly 1 29 125063 01 Valve Motorize...

Страница 34: ...a 14 16 16 18 17 10 11a 11b 11c 11d 12b 12c 12d PARTS MODELS DVF 36NSR C DVF 36PSR C DVF 36NHR C DVF 36PHR C DVF 36NSI C DVF 36PSI C DVF 36NHI C DVF 36PHI C DVF 36NSR CC DVF 36PSR CC DVF 36NHR CC DVF...

Страница 35: ...efractory Right Red 1 8 125142 01 Hearth Refractory Front Ivory 1 125142 02 Hearth Refractory Front Red 1 9 121128 01 Top Refractory Bracket 2 10 121182 01 Rear Refractory Bracket 1 11a 125152 01 Left...

Страница 36: ...C who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material laborandincidentalcostsas...

Отзывы: