Vertical Termination Installation

Note: Vertical restrictor must be installed in 

all vertical installations.

1.  Determine  route  your  vertical  venting 

will  take.  If  ceiling  joists,  roof  rafters  or 

other framing will obstruct venting system, 

consider an offset (see Figure 16) to avoid 

cutting load bearing members. 

Note: Pay 

special attention to these installation 

instructions for required clearances (air 

space) to combustibles when passing 

through ceilings, walls, roofs, enclosures, 

attic rafters, etc. Do not pack air spaces 

with insulation. Also note maximum 

vertical rise of venting system and any 

maximum horizontal offset limitations.

2.  Set fireplace in desired location. Drop a 

plumb line down from ceiling to position 

of  fireplace  exit  flue.  Mark  center  point 

where vent will penetrate ceiling. Drill a 

small locating hole at this point.

 

Drop a plumb line from inside of roof to 

locating hole in ceiling. Mark center point 

where vent will penetrate roof. Drill a small 

locating hole at this point.

Flat Ceiling Installation

1.  Cut a 11 

1

/

2

" square hole in ceiling using 

locating hole as a center point. Opening 

should be framed to 11 

1

/

2

" x 11 

1

/

2

" inside 

dimensions, as shown in Figure 8 on page 

9 using framing lumber the same size as 

ceiling joists. If area above ceiling is an 

insulated ceiling or an attic, nail firestop 

from top side. This prevents loose insula

-

tion  from  falling  into  required  clearance 

space.  If  area  above  ceiling  is  a  living 

space, install firestop below framed hole. 

Firestop should be installed with no less 

than three nails per side (see Figure 17).

2.  Assemble  desired  lengths  of  pipe  and 

elbows necessary to reach from fireplace 

flue up through firestop. Be sure all pipe 

and  elbow  connections  are  fully  twist-

locked (see Figure 8, page 10).

3.  Cut a hole in the roof using locating hole 

as  a  center  point.  (Cover  any  exposed 

open  vent  pipes  before  cutting  hole  in 

roof.) The 11 

1

/

2

" x 11 

1

/

2

" hole must be 

measured on the horizontal; actual length 

may be larger depending on pitch of roof. 

There must be a 1" clearance from vent 

pipe  to  combustible  materials.  Frame 

opening as shown in Figure 9, page 10.

4.  Connect a section of pipe and extend up 

through hole.

 

Note: If an offset is needed to avoid 

obstructions, you must support vent pipe 

every 3 feet. Use wall straps for this pur-

pose (see Figure 15, page 12). Whenever 

possible, use 45° elbows instead of 90° 

elbows. The 45° elbow offers less restric-

tion to the flow of flue gases.

VENTING INSTALLATION

Continued

Figure 16 - Offset with Wall Strap and 45° 

Elbows

45° Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

Figure 17 - Installing Firestop

If area above is a living space, install 

firestop below framed hole.

If area above is an attic or insulated area, 

install firestop above framed hole.

Содержание DVF36NHI-C

Страница 1: ...yourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied in...

Страница 2: ...eplace designed for residential ap plications This fireplace must be installed with FMI PRODUCTS LLC vent pipe components and terminations Outside airflex installation is required for both horizontal...

Страница 3: ...fythisfireplaceunderanycircumstances Anyparts removed for servicing must be replaced prior to operating fireplace WARNING Do not use a blower insert heat exchanger insert or other accessory not approv...

Страница 4: ...e fire place inspected annually by a qualified service person 5 You must keep control compartments burners and circulating air passages clean More frequent cleaning may be needed due to excessive lint...

Страница 5: ...h traffic areas windy or drafty areas or near furniture or draperies Proper clearances must be maintained If your fireplace is to be installed directly on carpeting vinyl tile or any combustible mate...

Страница 6: ...ce to combustible materials are for framing purpose only NOTICE Thisfireplaceisintend edforuseassupplementalheat Use this fireplace along with your primary heating system Do not install this fireplace...

Страница 7: ...n US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally...

Страница 8: ...tly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP...

Страница 9: ...e components and terminations The venting system must terminate on the outside of the structure and can not be at tached to a chimney or flue system serving a separate solid fuel or gas burning applia...

Страница 10: ...cial twist lock con nections Twist Lock Procedure Female ends of pipes have locking lugs indentations These lugs will slide straight into match ing slots on male ends of adjacent pipes Push pipe secti...

Страница 11: ...with provided wood screws see Figure 11 Siding standoff must sit flush against exterior fascia material 6 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before conne...

Страница 12: ...hart with critical minimum and maximum dimensions which MUST be met NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent inspection and maintenance WARNING Never run vent downwa...

Страница 13: ...above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insula tion from falling into required clearance space If area above ceiling is a living space install...

Страница 14: ...the configurations for vertical termination VENTING INSTALLATION Continued Figure 18 Vertical Venting Configuration Vertical Venting V 40 max HIGH ALTITUDE INSTALLATION Your FMI PRODUCTS LLC direct v...

Страница 15: ...AK6 75 75 Outside Air Flex Vent Kit CHECK GAS TYPE Use proper gas type for the fireplace unit you are installing If you have conflicting gas types do not install fireplace See retailer where you purch...

Страница 16: ...gulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regulator with Vent Pointing Down FIREPLACE INSTALLATION Continued Apply pipe joint sealant lightly to male NPT threads...

Страница 17: ...LP supply tank valve for propane LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air 4 Check all joints of gas supply piping sys t...

Страница 18: ...oints for leaks 6 Turn off fireplace see To Turn Off Gas to Appliance page 23 REMOVING REPLACING GLASS DOORS CAUTION Do not operate thisfireplacewithabrokenglass door panel or without the glass doorpa...

Страница 19: ...hinges see Figure 26 Set aside to avoid scratches or damage FIREPLACE INSTALLATION Continued 3 Follow these instructions in reverse to reinstall Removing and Installing Inner Door All Models 1 Remove...

Страница 20: ...ner Door Screen and Rod Non Cool Touch Models Only LAVA ROCK EMBER FLAKES AND SCRAP LOG INSTALLATION Lava rock ember flakes and scrap log pieces are included with your fireplace Install these items wh...

Страница 21: ...er and on burner ports see Figure 30 This will create the glowing ember ap pearance as the flame touches the ember flakes Do not block burner ports or pilot ports by overlapping ember flakes in one ar...

Страница 22: ...rn on all electric power to appliance 10 Turn safety shutoff switch to the ON posi tion 11 Visually locate pilot Ignitor should begin to spark and main burner should ignite once flame appears at pilot...

Страница 23: ...e appliance rocker switch is turned OFF the pilot will shut OFF when the main burner shuts OFF 3 When the continuous pilot switch is in the ON position and the appliance rocker switch is turned ON the...

Страница 24: ...and grounding stem If your pilot assembly does not meet these requirements Turn the adjustment screw marked PILOT clockwise to decrease or counterclockwise to increase the flame to proper size see Fi...

Страница 25: ...curing The glass should be cleaned several times with a non ammonia nonabrasive household clean er and warm water after the first two weeks of operation Thereafter clean the glass two or three times...

Страница 26: ...Minimum Inlet Supply Pressure 7 w c DVF 36PSR C DVF 36PHR C DVF 36PSI C DVF 36PHI C DVF 36PSR CC DVF 36PHR CC DVF 36PSI CC DVF 36PHI CC Rating 62 000 Btu hr Gas Type Propane LP Gas Only Ignition Elec...

Страница 27: ...valve is not opening 7 No power to unit or ignition module REMEDY 1 Checktoseeifyouhavegas supply and that equipment shutoff valve is opened 2 Repeat lighting procedure several times to purge all air...

Страница 28: ...c connectors that plug in the face of the gas control valve Confirm the gas control valve is properly grounded to the module 1 Check electrical connec tions 1 Clean and adjust pilot flame for maximum...

Страница 29: ...s blocked 3 Improper venting or exces sive blockage 4 Excessive amounts of em bers and pan material OBSERVED PROBLEM Gas odor even when gas control valve is off Gas odor during combustion Glass soots...

Страница 30: ...F 36PHR C DVF 36NSI C DVF 36PSI C DVF 36NHI C DVF 36PHI C DVF 36NSR CC DVF 36PSR CC DVF 36NHR CC DVF 36PHR CC DVF 36NSI CC DVF 36PSI CC DVF 36NHI CC AND DVF 36PHI CC 10 14 9 7 21 11 32 23 24 26 25 41...

Страница 31: ...ctor 1 20 106702 01 5 Gasket 1 21 120431 01 Burner Base Gasket 1 22 117997 01 Glass Door Retainer 1 23 120142 01 Firebox Leg 4 24 117891 01 Fireplace Handle 4 25 21171 Gas Conduit Cover 1 26 24460 Gas...

Страница 32: ...14 28 8 5 3 4 15 27 21 24 26 32 29 30 31 35 26 38 26 33 36 34 34 39 PARTS MODELS DVF 36NSR C DVF 36PSR C DVF 36NHR C DVF 36PHR C DVF 36NSI C DVF 36PSI C DVF 36NHI C DVF 36PHI C DVF 36NSR CC DVF 36PSR...

Страница 33: ...3 8 x 18 1 25 125068 01 Battery Backup 1 26 125061 01 Valve Module Bracket 1 27 114365 24 Brass Orifice 32 NG 1 114365 16 Brass Orifice 51 LP 1 28 126117 01 Log Assembly 1 29 125063 01 Valve Motorize...

Страница 34: ...a 14 16 16 18 17 10 11a 11b 11c 11d 12b 12c 12d PARTS MODELS DVF 36NSR C DVF 36PSR C DVF 36NHR C DVF 36PHR C DVF 36NSI C DVF 36PSI C DVF 36NHI C DVF 36PHI C DVF 36NSR CC DVF 36PSR CC DVF 36NHR CC DVF...

Страница 35: ...efractory Right Red 1 8 125142 01 Hearth Refractory Front Ivory 1 125142 02 Hearth Refractory Front Red 1 9 121128 01 Top Refractory Bracket 2 10 121182 01 Rear Refractory Bracket 1 11a 125152 01 Left...

Страница 36: ...C who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material laborandincidentalcostsas...

Отзывы: