DataView™ LI55 Level Controller
Quick Start
27
| P a g e
To set the Repeater / Analog Output:
Note:
Before configuring the Analog Output, make sure the Scale has
been completed.
1. Press
the
MENU
button to enter the Main Menu. Units (unitS) will
be the first operation available.
2. Press
the
Up
button to scroll through the menu options until you
reach Analog Output (Aout).
3. Press
ENTER
button to enter Analog output. Empty (EmPtY) will
appear.
4. Press
the
ENTER
button to change the Empty value.
a. Press the Right button to move the highlighted digit to the
right and the Up button to increase the setting's value.
5. Press
ENTER
button to save the settings.
a. Full
(FuLL)
will
appear.
6. Press
ENTER
button to move the highlighted digit to the right and
the Up button to increase the setting's value.
7. Press
ENTER
button again to save the settings.
8. Press
the
MENU
button to exit.