9 Measurement
FLUXUS G831ST-HT
9.2 Measurement settings
83
UMFLUXUS_G831ST-HTV1-0EN, 2021-06-01
Depending on the selected source item, it is possible to output measured values, status values or event values.
9.2.5.1
Output of a measured value
• Select the list item
Options\Outputs\...\Values
.
• Press ENTER.
Output range
• Select a list item.
– 4...20 mA
– Other range
• Press ENTER.
If
Other range
is selected, enter the values
Output
MIN
and
Output MAX
.
The output range has to be > 10 % of the max. output value (
Output MAX
). If the output range is smaller, an error
message will be displayed.
If the function
NAMUR NE43
is activated in the menu item
Special functions\Current output
, only the output
range 4…20 mA applies.
Error output
An error value can be defined which is output if the source item cannot be measured.
• Select a list item for the error output.
• Press ENTER.
• If
Other value
is selected or the function
NAMUR NE43
is activated, enter an error value. The value has to be outside
the output range. If the value is not valid, an error message will be displayed. The permissible range is displayed.
• Press ENTER.
Tab. 9.2:
Output of measured values, status values or event values
source item
measured value
event value
value
status
physical quantities
Flow quantities
x
x
Totalizers
x
x
Fluid properties
x
x
Miscellaneous
(Custom. Input 1...4)
x
x
Diagnostic values
(except
Transd. temp. violat.
)
x
events
Diagnostic values
\
Transd. temp. violat.
x
Event trigger
x
Source item
Values
Output range
Error value
Measuring range
Output info
Test signal
Test mea. range
see annex A
Options\Outputs\...\Output range
Options\Outputs\...\Error value