I N S T A L L A T I O N A N D O P E R A T I N G I N S T R U C T I O N S
GB
Application
The Flamcovent can be used in heating/cooling systems
(with glycol-based additives, max. 50%).
Min./max. system temperature –10 °C to +120 °C.
Min. system pressure at the Flamcovent 0.2 bar. See the label for the maximum
permissible working pressure.
Max. speed through the Flamcovent 1.5 m/s.
Maximum static height above Flamcovent: central heating:
30 m, chilled water system: 15 m (fi g. 1, 2).
Safety
Construction/installation
Install the Flamcovent in a dry location not susceptible to frost which is easily
accessible for maintenance purposes.
Heating system: install the Flamcovent directly before the boiler or mixing valve,
in the supply pipe, ideally before the circulation pump (fi g. 3, 4, 5).
Chilled water system: just before the chiller.
Make sure installation is performed by qualifi ed personnel only.
Local legislation/guidelines must be observed at all times.
Flush the installation thoroughly before installing the Flamcovent.
The Flamcovent must be fi tted vertically (fi g. 6).
The bleed port on the Flamcovent has a 22 mm connection for fi tting a drain pipe (fi g. 6).
For service purposes, there must be at least 100 mm clearance above the bleed
port (fi g. 7).
The Flamcovent must be visually inspected regularly.
Should there be a leak from the bleed port, it can be closed with the screw (fi g. 8).
Flamcovent types DN 50 – DN 600 can have a drain cock for fl ushing out dirt fi tted
as an optional extra (fi g. 9).
Floating dirt can be drained by using the upper drain cock (fi g. 10),
types DN 50 – DN 600).
Servicing may only be carried out when the system has been de-pressurized and
has cooled down.
Maintenance/service
Removal
De-pressurize the system and remove the Flamcovent from the system.
Local legislation must be adhered to when disposing of the Flamcovent.