AP BIO
Maintenance of the AP BIO
400/500/1000/2400
FG-DC_10523-GB_AP Bio_IOM-R0-12/2020 • Subject to modifications
25
Replacing the AirFend filter
Fig. 9-2
Replacing the AirFend filter AP BIO 400, AP BIO 500 and AP BIO 1000
1: Lever
2: Filter quick release
3: Access panel
4: AirFend filter H14
•
Swing the lever (1) of each of the 4 AirFend filter quick-releases (2) and rotate them
90°.
•
Open the plastic bag, remove the new AirFend filter and put it aside.
•
Lift the AirFend filter (4) slightly and remove it from the frame.
•
Put the used filter into the empty plastic bag of the new filter and seal up with a tape.
•
Clean inner flat surfaces carefully with a cloth and disinfect with spray, observe the
exposure time of disinfection liquids of min. 30 sec. Also refer to “Cleaning the air
purifier” on page 27.
•
Reassemble the new AirFend filter in the reverse order.
•
Close access panel (3).
Содержание AP BIO 1000
Страница 1: ...AP BIO 400 500 1000 2400 AIR PURIFIER INSTALLATION OPERATION AND MAINTENANCE MANUAL ...
Страница 30: ...Notes AP BIO 400 500 1000 2400 30 FG DC_10523 GB_AP Bio_IOM R0 12 2020 Subject to modifications ...
Страница 31: ...AP BIO Notes 400 500 1000 2400 FG DC_10523 GB_AP Bio_IOM R0 12 2020 Subject to modifications 31 ...