Commissioning and operation
AP BIO
400/500/1000/2400
20
FG-DC_10523-GB_AP Bio_IOM-R0-12/2020 • Subject to modifications
7.1.2 Symbols of the control panel display
Fig. 7-2
Symbols of the control panel display
Tab.7-1
Symbols of the control panel display
7.2
Commissioning
•
Set the power switch to position ON (I). Refer to:
Fig. 4-1 General overview AP BIO 400, 500 and 1000 Pos. 5 and
Fig. 4-2 General overview AP BIO 2400 Pos. 5.
•
After a few moments, the WAIT symbol will disappear from the display.
•
Use the INCREASE button to adjust the air volume setpoint to the maximum value
•
Enable unit to operate for 3 to 5 hours.
•
After 3 to 5 hours of initial activation use the INCREASE or DECREASE button to
adjust the air volume setpoint to the desired value.
•
Repeat the above activation procedure when the AirFend HEPA14 filter is replaced.
Symbol
Meaning
Constant flow
On/Off status light
Off = Unit is off
On = Unit is on
Regulation mode status light
Off = Manual mode
On = Automatic mode
Fan status light
Off = Fan is off
On = Fan is running
Alarm light indicating clogged filter alarm light
Notice for the first unit activation!
– When the unit is switched on for the first time, the AirFend is transferred to the
HEPA filter which activates the biological AirFend layer.
– This will result in a smell of cloves and other biological substances.
– Such smell emissions are normal and do not represent a reason for complaint.
– This smell subsides in a few days following the activation.
– Activation of the AirFend layer can cause allergic reaction.