Rosemount Model 3095FT HART Flow Transmitter
4-28
c. If using a vacuum pump, pull a vacuum to both the low and
high sides of the transmitter, then enter the low value as the
trim value, set the units, then select Ok.
OR
If using a barometer, enter the barometric reading as the Trim
Value, select the units, then click Ok.
d.Wait for the Measured Value to stabilize, then click Ok.
The User Interface then displays the SP slope screen.
2. Trim SP Slope (Span).
a.Using the dead-weight tester, apply the desired high pressure to
both the low and high sides of the transmitter.
b.Enter the high value as the Trim Value, select the units, then
click Ok.
c. Wait for the Measured Value to stabilize, then click Ok.
3. Trim DP Offset (Zero).
a.Select Maintenance, Transmitter, Sensor Trim to display the
Sensor Trim Select screen.
b.Select DP and Offset & Slope, then select Ok to display the
“Sensor Trim: Enter Value” screen.
c. Using the dead-weight tester, apply the desired low pressure
value to the high side of the transmitter, enter the low value as
the trim value, select the units, then click Ok.
NOTE
If zero is the desired low value, do not use the dead weight tester.
Instead, enter zero as the trim value, select the units, then click Ok.
d.Wait for the Measured Value to stabilize, then click Ok.
The User Interface then displays the DP slope screen.
4. Trim DP Slope (Span).
a.Using the dead-weight tester, apply the desired high pressure to
the high side of the transmitter.
b.Enter the high value as the Trim Value, select the units, then
click Ok.
c. Wait for the Measured Value to stabilize, then click Ok.
FIGURE 4-17. Sensor Trim Apply
Condition Screen.
3
0
9
5
-3
09
500
23
Содержание 3095FT
Страница 1: ...R Model 3095FT HART Flow Transmitter 00809 0100 4015 English Rev B1...
Страница 2: ......
Страница 4: ......
Страница 45: ...3 13 Options and Accessories 3051 1006D03A FIGURE 3 5 Recharging the Battery 15 to 36 V dc 500 mA minimum...
Страница 98: ...Rosemount Model 3095FT HART Flow Transmitter 4 50...
Страница 117: ...5 19 Troubleshooting and Maintenance FIGURE 5 2 Replacing the Remote Power Supply Battery...
Страница 118: ...Rosemount Model 3095FT HART Flow Transmitter 5 20...
Страница 146: ...Rosemount Model 3095FT HART Flow Transmitter 7 24...
Страница 147: ...Appendix A 1 A Model 3095 Explosion Proof Installation Drawing Factory Mutual Drawing Number 03095 1025 Rev G...
Страница 148: ...Rosemount Model 3095FT HART Flow Transmitter A 2...
Страница 149: ...A 3 Appendix A...
Страница 150: ...Rosemount Model 3095FT HART Flow Transmitter A 4...
Страница 151: ...Appendix B 1 B Index of I S F M for 3095 and Index of I S F M for 03095 5000 Drawing Numbers 03095 1020 and 03095 5000...
Страница 152: ...Rosemount Model 3095FT HART Flow Transmitter B 2...
Страница 153: ...B 3 Appendix B...
Страница 154: ...Rosemount Model 3095FT HART Flow Transmitter B 4...
Страница 155: ...B 5 Appendix B...
Страница 156: ...Rosemount Model 3095FT HART Flow Transmitter B 6...
Страница 157: ...B 7 Appendix B...
Страница 158: ...Rosemount Model 3095FT HART Flow Transmitter B 8...
Страница 159: ...Appendix C 1 C Model 3095 Explosion Proof Installation Drawing CSA Drawing Number 03095 1024 Rev D...
Страница 160: ...Rosemount Model 3095FT HART Flow Transmitter C 2...
Страница 161: ...C 3 Appendix C...
Страница 162: ...Rosemount Model 3095FT HART Flow Transmitter C 4...
Страница 163: ...Appendix D 1 D Index of I S CSA for 3095 and Index of I S CDA for 03095 5000 Drawing Numbers 03095 1021 and 03095 1031...
Страница 164: ...Rosemount Model 3095FT HART Flow Transmitter D 2...
Страница 165: ...D 3 Appendix D...
Страница 166: ...Rosemount Model 3095FT HART Flow Transmitter D 4...
Страница 167: ...D 5 Appendix D...
Страница 168: ...Rosemount Model 3095FT HART Flow Transmitter D 6...
Страница 183: ......