5-5
Troubleshooting and Maintenance
Exit on-line maintenance mode
2
28
none
Also performs a master reset (alarm code 0). No action required.
Sensor board eeprom not
initialized, default values used
1
29
C_SEN
EE_INI
The sensor electronics has not been properly initialized at the factory.
Replace the sensor module as described on Page 5-10. Contact your
Field Service Center.
Event log upload to host.
2
30
none
The User Interface software retrieved the event log from the Model
3095FT. No action required.
Variable log upload to host.
2
31
none
The User Interface software retrieved the variable log from the Model
3095FT. No action required.
Daily log upload to host.
2
32
none
The User Interface software retrieved the daily log from the Model
3095FT. No action required.
Off-line maintenance mode
2
33
A_OFF
LINE_M
Return transmitter to On-Line Normal Operation.
Exit off-line maintenance mode
2
34
none
Also performs a master reset (alarm code 0). No action required.
C_d calc. floating point range
exceeded
2
36
none
Indicates failure in the flow calculation. Contact your Field Service
Center.
C_d calc. failure to converge
2
37
none
Can occur at extremely low Reynolds numbers. Contact your System
Engineer. Consider raising your low flow cut-off value.
C_d calc. result late
2
38
none
Indicates failure in the flow calculation. Contact your Field Service
Center.
C_d calc.return to normal
2
39
none
No action required.
Z calc. floating point range
exceeded
2
40
none
Indicates failure in the flow calculation. Contact your Field Service
Center.
Z calc. failure to converge
2
41
none
Indicates failure in the flow calculation. Contact your Field Service
Center.
Z calc. result late
2
42
none
Indicates failure in the flow calculation. Contact your Field Service
Center.
C_d calc.return to normal
2
43
none
Indicates failure in the flow calculation. Contact your Field Service
Center.
On-line maintenance mode with
default PVs
2
44
none
Verify transmitter was returned to On-Line Normal Operation.
On-line maintenance mode with
one second average PVs
2
45
none
Verify transmitter was returned to On-Line Normal Operation.
On-line maintenance mode with
user entered PVs
2
46
none
Verify transmitter was returned to On-Line Normal Operation.
Flash eeprom error
0
47
F_CRC
EEPROM
Flash eeprom checksum failed indicating corrupted output board
memory. Replace the output electronics board as described on
Page 5-10.
Alarm Description,
UI Display - Self Test,
and Event Log Description
Event
Code
(Table
5-1)
Alarm
Code
(Index)
LCD
Display
Action
Содержание 3095FT
Страница 1: ...R Model 3095FT HART Flow Transmitter 00809 0100 4015 English Rev B1...
Страница 2: ......
Страница 4: ......
Страница 45: ...3 13 Options and Accessories 3051 1006D03A FIGURE 3 5 Recharging the Battery 15 to 36 V dc 500 mA minimum...
Страница 98: ...Rosemount Model 3095FT HART Flow Transmitter 4 50...
Страница 117: ...5 19 Troubleshooting and Maintenance FIGURE 5 2 Replacing the Remote Power Supply Battery...
Страница 118: ...Rosemount Model 3095FT HART Flow Transmitter 5 20...
Страница 146: ...Rosemount Model 3095FT HART Flow Transmitter 7 24...
Страница 147: ...Appendix A 1 A Model 3095 Explosion Proof Installation Drawing Factory Mutual Drawing Number 03095 1025 Rev G...
Страница 148: ...Rosemount Model 3095FT HART Flow Transmitter A 2...
Страница 149: ...A 3 Appendix A...
Страница 150: ...Rosemount Model 3095FT HART Flow Transmitter A 4...
Страница 151: ...Appendix B 1 B Index of I S F M for 3095 and Index of I S F M for 03095 5000 Drawing Numbers 03095 1020 and 03095 5000...
Страница 152: ...Rosemount Model 3095FT HART Flow Transmitter B 2...
Страница 153: ...B 3 Appendix B...
Страница 154: ...Rosemount Model 3095FT HART Flow Transmitter B 4...
Страница 155: ...B 5 Appendix B...
Страница 156: ...Rosemount Model 3095FT HART Flow Transmitter B 6...
Страница 157: ...B 7 Appendix B...
Страница 158: ...Rosemount Model 3095FT HART Flow Transmitter B 8...
Страница 159: ...Appendix C 1 C Model 3095 Explosion Proof Installation Drawing CSA Drawing Number 03095 1024 Rev D...
Страница 160: ...Rosemount Model 3095FT HART Flow Transmitter C 2...
Страница 161: ...C 3 Appendix C...
Страница 162: ...Rosemount Model 3095FT HART Flow Transmitter C 4...
Страница 163: ...Appendix D 1 D Index of I S CSA for 3095 and Index of I S CDA for 03095 5000 Drawing Numbers 03095 1021 and 03095 1031...
Страница 164: ...Rosemount Model 3095FT HART Flow Transmitter D 2...
Страница 165: ...D 3 Appendix D...
Страница 166: ...Rosemount Model 3095FT HART Flow Transmitter D 4...
Страница 167: ...D 5 Appendix D...
Страница 168: ...Rosemount Model 3095FT HART Flow Transmitter D 6...
Страница 183: ......