5-3
Troubleshooting and Maintenance
Interpreting Model 3095FT
Alarms and Events
All Model 3095FT alarms are entered in the event log. In addition,
specific alarm conditions are displayed on the optional LCD Meter, and
specific alarm conditions can be viewed via the Model 3095FT User
Interface software (see the Maintenance, Transmitter, Self Test
selection on Page 4-34). Table 5-2 summarizes these alarm messages.
Column 2 of Table 5-2 identifies an event code for major alarms and
events. Table 5-1 explains these event codes. Also note that the last
column of Table 5-2 identifies corrective actions, and when necessary
cross-references to sections of this manual for additional information.
TABLE 5-1. Event Code Explanation.
Event
Code
Alarm/Event
Explanation
0
Fatal Alarm
Non-recoverable error causing transmitter to stop calculations
1
Critical Alarm
Error which may result in unreliable data
2
Warning
Outside normal operational conditions
3
Return to Normal
Return to normal operational conditions
4 or 5
Configuration Parameter
Changed
User change to configuration parameter via HART command
TABLE 5-2. Model 3095FT Event and
Alarm Summary
Alarm Description,
UI Display - Self Test,
and Event Log Description
Event
Code
(Table
5-1)
Alarm
Code
(Index)
LCD
Display
Action
Power Up / Master Reset
2
0
F_NO_
SIGNAL
The Model 3095FT has been reset by one of the following actions:
Power Up, Master Reset Command (Starting or exiting any
maintenance task), or Start Data Logging
Sensor module is not updating
0
1
F_NO_
SIGNAL
The sensor module has undergone a component or software failure.
Replace the sensor module as described on Page 5-10. Contact your
Field Service Center.
DP signal exceeded Upper Range
Limit + 10% (URL + 10%)
1
2
C_DP_
O_RANG
This display means that the transmitter differential pressure reading
exceeds its sensor limits by more than 10%. There are two possible
causes. Either the transmitter is overpressured, or it has a sensor
malfunction. Check the pressure input to the transmitter. If an
overpressure condition exists, correct it. If not, replace the sensor
module as described on Page 5-10.
DP signal return-to-normal
3
3
none
No action required.
AP signal exceeded Upper Range
Limit + 10% (URL + 10%)
1
4
C_AP_
O-RANG
This display means that the transmitter absolute pressure reading
exceeds its sensor limits by more than 10%. There are two possible
causes. Either the transmitter is overpressured, or it has a sensor
malfunction. Check the pressure input to the transmitter. If an
overpressure condition exists, correct it. If not, replace the sensor
module as described on Page 5-10.
AP signal is unreasonable - open
bridge
1
5
C_AP_
OPEN_B
This display means that the transmitter absolute pressure reading
exceeds its sensor limits. There are two possible causes. Either the
transmitter is overpressured, or it has a sensor malfunction. Check the
pressure input to the transmitter. If an overpressure condition exists,
correct it. If not, replace the sensor module as described on Page 5-10.
AP signal below 0.5 psia
1
6
C_AP_
VERY_L
This display means that the transmitter absolute pressure reading
exceeds its sensor limits. There are two possible causes. Either the
transmitter is underpressured, or it has a sensor malfunction. Check the
pressure input to the transmitter. If an underpressure condition exists,
correct it. If not, replace the sensor module as described on Page 5-10.
AP sensor shorted
0
7
F_AP_
SHORTD
The sensor module has undergone a component or software failure.
Replace the sensor module as described on Page 5-10. Contact your
Field Service Center.
Содержание 3095FT
Страница 1: ...R Model 3095FT HART Flow Transmitter 00809 0100 4015 English Rev B1...
Страница 2: ......
Страница 4: ......
Страница 45: ...3 13 Options and Accessories 3051 1006D03A FIGURE 3 5 Recharging the Battery 15 to 36 V dc 500 mA minimum...
Страница 98: ...Rosemount Model 3095FT HART Flow Transmitter 4 50...
Страница 117: ...5 19 Troubleshooting and Maintenance FIGURE 5 2 Replacing the Remote Power Supply Battery...
Страница 118: ...Rosemount Model 3095FT HART Flow Transmitter 5 20...
Страница 146: ...Rosemount Model 3095FT HART Flow Transmitter 7 24...
Страница 147: ...Appendix A 1 A Model 3095 Explosion Proof Installation Drawing Factory Mutual Drawing Number 03095 1025 Rev G...
Страница 148: ...Rosemount Model 3095FT HART Flow Transmitter A 2...
Страница 149: ...A 3 Appendix A...
Страница 150: ...Rosemount Model 3095FT HART Flow Transmitter A 4...
Страница 151: ...Appendix B 1 B Index of I S F M for 3095 and Index of I S F M for 03095 5000 Drawing Numbers 03095 1020 and 03095 5000...
Страница 152: ...Rosemount Model 3095FT HART Flow Transmitter B 2...
Страница 153: ...B 3 Appendix B...
Страница 154: ...Rosemount Model 3095FT HART Flow Transmitter B 4...
Страница 155: ...B 5 Appendix B...
Страница 156: ...Rosemount Model 3095FT HART Flow Transmitter B 6...
Страница 157: ...B 7 Appendix B...
Страница 158: ...Rosemount Model 3095FT HART Flow Transmitter B 8...
Страница 159: ...Appendix C 1 C Model 3095 Explosion Proof Installation Drawing CSA Drawing Number 03095 1024 Rev D...
Страница 160: ...Rosemount Model 3095FT HART Flow Transmitter C 2...
Страница 161: ...C 3 Appendix C...
Страница 162: ...Rosemount Model 3095FT HART Flow Transmitter C 4...
Страница 163: ...Appendix D 1 D Index of I S CSA for 3095 and Index of I S CDA for 03095 5000 Drawing Numbers 03095 1021 and 03095 1031...
Страница 164: ...Rosemount Model 3095FT HART Flow Transmitter D 2...
Страница 165: ...D 3 Appendix D...
Страница 166: ...Rosemount Model 3095FT HART Flow Transmitter D 4...
Страница 167: ...D 5 Appendix D...
Страница 168: ...Rosemount Model 3095FT HART Flow Transmitter D 6...
Страница 183: ......