5-9
Troubleshooting and Maintenance
Transmitter Electronics
• Connect a personal computer and use the User Interface Software
to check the sensor limits to ensure calibration adjustments are
within the sensor range and that calibration is correct for the
pressure being applied.
• Connect a personal computer and using the User Interface
Software, select Maintenance, Transmitter, Self Test (see Page 4-
34) to detect any electronic failures.
• Make sure the post connectors are clean.
• Confirm that the electronics housing is properly sealed against
moisture.
• If the electronics are still suspect, substitute new electronics.
Sensing Element
• The sensing element is not field repairable and must be replaced
if found to be defective. Check for obvious defects, such as a
punctured isolating diaphragm or fill fluid loss, and contact your
nearest Rosemount Service Center.
Symptom: Sluggish Output
Response/Drift
Potential Source and Corrective Action
Orifice Plate
• Check for restrictions at the orifice plate.
Impulse Piping
• Check for leaks or blockage.
• Ensure that blocking valves are fully open.
• Check for sediment in the transmitter process flange.
Transmitter Electronics
• Connect a personal computer and using the User Interface
Software, select Maintenance, Transmitter, Self Test (see Page 4-
34) to detect any electronic failures.
• Confirm that damping is correctly set (see Page 4-30).
• Confirm that electronics housing is properly sealed against
moisture.
Sensing Element
• The sensing element is not field repairable and must be replaced
if found to be defective. Check for defects, such as a ruptured
isolating diaphragm or fill fluid loss, and contact your nearest
Rosemount Service Center.
• Confirm that the electronics housing is properly sealed against
moisture.
Содержание 3095FT
Страница 1: ...R Model 3095FT HART Flow Transmitter 00809 0100 4015 English Rev B1...
Страница 2: ......
Страница 4: ......
Страница 45: ...3 13 Options and Accessories 3051 1006D03A FIGURE 3 5 Recharging the Battery 15 to 36 V dc 500 mA minimum...
Страница 98: ...Rosemount Model 3095FT HART Flow Transmitter 4 50...
Страница 117: ...5 19 Troubleshooting and Maintenance FIGURE 5 2 Replacing the Remote Power Supply Battery...
Страница 118: ...Rosemount Model 3095FT HART Flow Transmitter 5 20...
Страница 146: ...Rosemount Model 3095FT HART Flow Transmitter 7 24...
Страница 147: ...Appendix A 1 A Model 3095 Explosion Proof Installation Drawing Factory Mutual Drawing Number 03095 1025 Rev G...
Страница 148: ...Rosemount Model 3095FT HART Flow Transmitter A 2...
Страница 149: ...A 3 Appendix A...
Страница 150: ...Rosemount Model 3095FT HART Flow Transmitter A 4...
Страница 151: ...Appendix B 1 B Index of I S F M for 3095 and Index of I S F M for 03095 5000 Drawing Numbers 03095 1020 and 03095 5000...
Страница 152: ...Rosemount Model 3095FT HART Flow Transmitter B 2...
Страница 153: ...B 3 Appendix B...
Страница 154: ...Rosemount Model 3095FT HART Flow Transmitter B 4...
Страница 155: ...B 5 Appendix B...
Страница 156: ...Rosemount Model 3095FT HART Flow Transmitter B 6...
Страница 157: ...B 7 Appendix B...
Страница 158: ...Rosemount Model 3095FT HART Flow Transmitter B 8...
Страница 159: ...Appendix C 1 C Model 3095 Explosion Proof Installation Drawing CSA Drawing Number 03095 1024 Rev D...
Страница 160: ...Rosemount Model 3095FT HART Flow Transmitter C 2...
Страница 161: ...C 3 Appendix C...
Страница 162: ...Rosemount Model 3095FT HART Flow Transmitter C 4...
Страница 163: ...Appendix D 1 D Index of I S CSA for 3095 and Index of I S CDA for 03095 5000 Drawing Numbers 03095 1021 and 03095 1031...
Страница 164: ...Rosemount Model 3095FT HART Flow Transmitter D 2...
Страница 165: ...D 3 Appendix D...
Страница 166: ...Rosemount Model 3095FT HART Flow Transmitter D 4...
Страница 167: ...D 5 Appendix D...
Страница 168: ...Rosemount Model 3095FT HART Flow Transmitter D 6...
Страница 183: ......