Generator Operating Instructions
Page 26 Panda 14.000 NE PVK-U S00420 - Chapter B: Generator Operating Instructions
B.2 Operating Instructions
B.2.1Routine „Pre-Start“ Checks (daily)
1. Check engine oil level (should be on MAX).
LOW OIL PRESSURE WARNING LIGHT!
The generator switches off in the case of insufficient oil-pressure. Do not run the generator with the oil at the lowest
level in the crankcase. (A smaller volume of oil will become contaminated considerably quicker than a larger
volume and there is the possibility that small air bubbles will get in the oil.) Therefore daily oil-checks are required.
The oil-level should always be refilled to MAX. Check oil level prior to starting motor or at least 5 minutes after the
motor has stopped.
Change the type of engine oil according to the ambient temperature. See Table F.2, “Engine oil,”
on Page II
For Oil-Quantities see Table F.5, “Technical Data Engine,” on Page IX
2. Check engine cooling system (all hoses and hose connections for leaks)
3. Check thermal switches and all cables and cable end terminal connections
a. Exhaust temperature switch
b. Engine temperature switch
c. Oil temperature switch
d. Oil pressure switch
4. Check tightness of all retaining and connection bolts on the engine & generator and generator
base mount bolts.
5. Switch main battery switch "ON" (if installed).
6. Open fuel inlet valve (if installed).
B.2.2Preliminary remarks
Damage to Starter Motor
The starter is fitted with a free wheel or axial rotating spring cog, which prevents the starter being
driven externally by means of the motor. The free wheel will be heavily worn, if the starter still
operates, thereby causing damage to the springs, roller bearings or cog teeth. This could lead to
complete destruction of the starter.
It is important that every person who operates the generator is informed of this situation.
This is practically the only handling error that can be made on board that can lead to fatal
consequences for both generator and operator.
Содержание Panda 14.000 NE PVK-U
Страница 1: ...Generator type Panda 14 000 NE PVK U 400V 50 Hz 12kW Icemaster Fischer Panda...
Страница 28: ...The Panda Generator Page 24 Panda 14 000 NE PVK U S00420 Chapter A The Panda Generator...
Страница 62: ...Generator Failure Page 58 Panda 14 000 NE PVK U S00420 Chapter D Generator Failure...
Страница 92: ...Appendix Page VIII Panda 14 000 NE PVK U S00420 Chapter F Appendix...
Страница 94: ...Measurements Page X Panda 14 000 NE PVK U S00420 Chapter F Appendix F 7 Measurements...
Страница 96: ...Wiring diagram control panel Page XII Panda 14 000 NE PVK U S00420 Chapter F Appendix...