Generator Operating Instructions
Page 28 Panda 14.000 NE PVK-U S00420 - Chapter B: Generator Operating Instructions
B.2.3Overloading of Engine during longer Operation
Please ensure that the genset is not overloaded. Overloading occurs when the electrical load
(demand) induces a load torque in the generator which is higher than that which the diesel drive
motor can provide. Overloading causes the engine to run rough, burn oil, creates excessive
exhaust (environmentally unfriendly) and even to stall. Extra caution should be practised with
multi-power units (single and 3-phase current generation) to avoid overloading the diesel drive
engine.
The generator should only be loaded at the peak rated power for short periods only! A high peak
current is required to start many electrical devices, especially electric motors and compressors
(from a still stand state).
Please ensure that the genset is not overloaded. Overloading occurs when the electrical load
(demand) induces a load torque in the generator which is higher than that which the diesel drive
motor can provide. Overloading causes the engine to run rough, burn oil, creates excessive
exhaust (environmentally unfriendly) and even to stall. Extra caution should be practised with
multi-power units (single and 3-phase current generation) to avoid overloading the diesel drive
engine.
The generator should only be loaded at the peak rated power for short periods only! A high peak
current is required to start many electrical devices, especially electric motors and compressors
(from a still stand state).
B.2.4Starting Generator
1. If necessary open the fuel valve.
2. If necessary, close the main battery switch.
3. Check if all the load have been switched off.
The load is switched off, before the generator is switched off. The generator is not to be started with load connec-
ted. If necessary, the main switch or fuse should be switched off or the load should be individually switched off.
4. Press "ON" button (Position 13 on Control panel).
Control light for "ON" Button must light up (Position 14 on Control panel).
5. Pre-heat engine (Position 09 on Control panel).
Pre-heating is necessary for every running temperature. Pre-heating is not necessary, only if the generator has just
been run. The heating period should take at least 6 seconds, however, 20 seconds at the maximum. Heating must
last for 20 seconds at a temperature of +5°C. If a second attempt is to be made, then a pause of at least 60
seconds is required.
The generator can be started with the assistance of a pre-heating device at temperatures as low as - 20°C. Please
note that the generator can only be run at temperatures below -8°C with winter fuel and additional special additi-
ves.
6. Press "START" button (Position 10 on Control panel).
The electric starter may only be used for a maximum of 20 seconds. Thereafter, a pause of, at least, 60 seconds is
required. If the genset does not immediately start, then the fuel intake should be checked to ensure it is flowing fre-
ely. (For temperatures below - 8°C check whether there is winter fuel)
7. Check circuit- voltmeter, to test whether there is AC voltage and is within the tolerance range
(Frequency and voltage).
Содержание Panda 14.000 NE PVK-U
Страница 1: ...Generator type Panda 14 000 NE PVK U 400V 50 Hz 12kW Icemaster Fischer Panda...
Страница 28: ...The Panda Generator Page 24 Panda 14 000 NE PVK U S00420 Chapter A The Panda Generator...
Страница 62: ...Generator Failure Page 58 Panda 14 000 NE PVK U S00420 Chapter D Generator Failure...
Страница 92: ...Appendix Page VIII Panda 14 000 NE PVK U S00420 Chapter F Appendix...
Страница 94: ...Measurements Page X Panda 14 000 NE PVK U S00420 Chapter F Appendix F 7 Measurements...
Страница 96: ...Wiring diagram control panel Page XII Panda 14 000 NE PVK U S00420 Chapter F Appendix...