General operation
10.5.11
Panel Generator Control P6+ RE0703_Kunde_eng.R06.1 - Kapitel/Chapter 11: General operation Seite/Page 135
Notes:
Power rating of the output: max. 0,5A in continuous operation and briefly 1,0A.
The supply of all output currents may not exceed (less 0,2A power consumption) the rated current of the safety device of the control panel.
The output has a free wheeling diode, which short circuits negative voltages (related to GND).
The output has a Z-diode, which prevents a supply of positive voltage (related to GND) into the output.
11.4.3 Function of the jumpers
Fig. 11.4.3-1: Function of the solder jumper
11
AC-Fault (Fuel
Level) [former T-
Oil]
IN
Error generator AC input for NC-open-collector-sensor-switch to GND (N = no error). The input
loads the switch with
≥
2,5mA to +12V. (with 24V-operated internally generated). The occurrence
of an error is delayed, for analysis and displayed, around 100ms. Omission not. The input status
is indicated with red LED.
The input can be used alternatively for the signal “Fuel level” (must be adjusted by solder Jum-
per). The signal does not lead to switching off and is indicated with yellow LED.
The input can be used alternatively for the signal “error oil-temperature”. The input is adjustable
for NC/NO (N = no error) (must be adjusted by solder Jumper). The load of the sensor switch is
adjustable to
≥
10mA by +12V (must be adjusted by solder Jumper).
12
T-Winding
IN
Error “winding temperature”. Input for thermo-switch to GND. The input is adjustable for NC/NO
(N = no error) (must be adjusted by solder Jumper). The input loads the switch with
≥
22mA to
+12V (with 24V-operated internally generated). The occurrence of an error is delayed, for ana-
lysis and displayed, around 100ms. Omission not. The input status is indicated with red LED.
Jumper
Status
Description
J1
closed
during operation of the start button heat is along-operated
open
Function deactivated
J3
1-2
Dynamo excitation resistor 68R is switched on with Fuel-Pump (1)
2-3
Dynamo excitation resistor 68R is switched on with Panel-ON (1)
open
Dynamo excitation resistor is deactivated
J101
closed
12V - operation
open
24V - operation (optional)
J201
1-2
T-Engine-input, for contact, which opens in case of error (2)
2-3
T-Engine-input, for contact, which closes in case of error (2)
J202
1-2
Water leak-input / Replace air filter, for contact, which opens in case of error (2)
2-3
Water leak-input / Replace air filter, for contact, which closes in case of error (2)
J203
1-2
Oil-Press-input, for contact, which opens in case of error (2)
2-3
Oil-Press-input, for contact, which closes in case of error (2)
J204
1-2
AC-Fault-input / Fuel level, for contact, which opens in case of error (2)
2-3
AC-Fault-input / Fuel level, for contact, which closes in case of error (2)
J205
1-2
T-Winding-input, for contact, which opens in case of error (2)
2-3
T-Winding-input, for contact, which closes in case of error (2)
J206
1-2
Input Water leak has red LED and switches off
2-3
Input Water leak has yellow LED and does not switch off
J207
1-2
Input AC-Fault has red LED and switches off
2-3
Input AC-Fault has yellow LED and does not switch off
J208
1-2
DC-Control-Signal (-) = OK dynamo 12V at Kubota Z 482 / D 722 engines
2-3
DC-Control-Signal (+) = OK three-phase DC-alternator
Содержание 22-4 HD PVMV-N
Страница 8: ...Seite Page 8 Kapitel Chapter 2 10 5 11 12 Measurements 153 12 1 Hole pattern 153 ...
Страница 25: ...General Instructions and Regulations 10 5 11 Chapter 1 General Instructions and Regulations Page 25 ...
Страница 52: ...Seite Page 52 10 5 11 Leere Seite Intentionally blank The Panda Generator ...
Страница 94: ...Seite Page 94 Panda 8000 42NE PVMV N R01 10 5 11 Leere Seite Intentionally blank Maintenance Instructions ...
Страница 154: ...Seite Page 154 Panel Generator Control P6 RE0703_Kunde_eng R06 1 10 5 11 Leere Seite Intentionally blank Measurements ...