S2000 15017 Rev H 10/08/96 P/N 15017:H
44
6.8
T
EE
-T
APPING
One Tee-Tap will be allowed on Style Y notification appliance circuits if a 10 K End-of-Line Resistor (Part # 71274) is used
on each branch as shown in Figure 6-4.
Note: This application is not recommended by Factory Mutual (FM).
Figure 6-4: Tee-Tapping Notification Appliance Circuits
Standard
Style Y
IC-4F Notification Circuit
Module or ICE-4F Expander
Tee-Tapped
Notification Appliance
Circuit
4.7K ELR
(Part # 71252)
Listed
10K ELR
(Part # 71274)
Listed
10K ELR
(Part # 71274)