Document #50066 Rev. D2 12/03/02 P/N 50066:D2
61
Slave Communicator Configuration
CHAPTER 6
Slave Communicator Configuration
The MS-5024 may be used as a slave communicator to a host or master FACP (fire alarm control panel). All wiring
between the master and the slave communicator is supervised. 4.7K ohm End-of-Line resistors should be connected.
In slave configuration, the five zones become five channels that may be triggered by the relay outputs of any host
FACP. The inputs have the following functions in the slave configuration:
• Zone 1/Channel 1 is used for general alarm
• Zone 2/Channel 2 is used for general trouble
• Zone 3/Channel 3 may be programmed to match the FACP relay function used as an input
• Zone 4/Channel 4 is used for supervisory
• Zone 5/Channel 5 may be programmed to match the FACP relay function used as an input
The factory settings for Zone 2/Channel 2 alarm and restoral are altered as follows:
❒
If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, the report code for Zone 2 Alarm Code
(address 83, 199) is 'F', Zone 2 Restoral Code (address 111, 227) is 'E'
❒
If 1, A or C is entered for address 16 or 42, the report code for Zone 2 Alarm Code (addresses 84-85, 200-
201) is 'FF', Zone 2 Restoral Code (addresses 140-141, 256-257) is 'EF.'
The factory settings for Zone 4/Channel 4 alarm and restoral are altered as follows:
❒
If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, report code for Zone 4/Channel 4 Alarm
Code (address 85, 201) is '8', Zone 4 Restoral Code (address 113, 229) is 'E.'
❒
If 1, A or C is entered for addresses 16 or 42, the report code for Zone 4 Alarm Code (addresses 88-89, 204-
205) is 84, Zone 4 Restoral Code (addresses 144-145, 260-261) is 'E4.'
Location 56 must be programmed to a '1' to enable the control panel as a slave communicator.
Be certain to connect the slave communicator’s primary AC power to the same branch circuit as the host FACP.
Note that Alarm Presignal and Alarm Verification do not function in Slave Communicator Mode.
Содержание MS-5024
Страница 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...
Страница 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 7: ......
Страница 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 54: ......
Страница 56: ......
Страница 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Страница 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...