![Fire-Lite Alarms MS-5024 Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/fire-lite-alarms/ms-5024/ms-5024_product-description_2291100058.webp)
History Mode
58
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
5.2
History Mode
All Normal Mode events are stored in a History file for future recall. Recall is possible via the 4-character display.
See the following page for a list and description of each event displayed.
The History file list is a first-in, first-out (FIFO). In this manner, only the most recent events may be called up from
memory. Old events will be overwritten (i.e. pushed out of the FIFO). The number of stored events is 32. This
History file is kept in E
2
memory. Complete power loss will not erase the list.
Pressing the
MODE
key followed by
4478
and then the
[ENTER/STORE]
key places the control panel into History
Mode.
This will not occur if there are any active alarm conditions present.
The event displayed is the most recent
event.
☛
4478
spells HIST on a Touch-Tone
®
phone.
Once in History Mode, the control panel will:
• Blink the trouble LED
• Activate the trouble relay(s) if programmed
• Disable the Notification Appliance Circuit(s)
• Disable the alarm relay(s) if programmed
• Display all events as they occurred since the last time the History file list was cleared. The most recent event
will be displayed first
• Ignore all other keys other than those mentioned in this section
• Transmit the 'off normal' message to the Central Station(s)
• Continue to communicate any events not previously acknowledged at the Central Station prior to entering His-
tory Mode
The Down arrow key moves the History file to show older (previous) events. The Up arrow key moves the History
file to show newer (most recent) events.
Shown below is the list of messages as they will appear on the display:
To erase the list from E
2
memory, press the Silence key twice before exiting the History Mode. A lack of keyboard
activity for a period of 10 minutes will cause the control panel to return to Normal Mode.
d__1
Zone 1 Disabled
d__2
Zone 2 Disabled
d__3
Zone 3 Disabled
d__4
Zone 4 Disabled
d__5
Zone 5 Disabled
E__1
Zone 1 Enabled
E__2
Zone 2 Enabled
E__3
Zone 3 Enabled
E__4
Zone 4 Enabled
E__5
Zone 5 Enabled
A__1
Alarm Zone 1
A__2
Alarm Zone 2
A__3
Alarm Zone 3
A__4
Alarm Zone 4
A__5
Alarm Zone 5
F__1
Trouble Zone 1
F__2
Trouble Zone 2
F__3
Trouble Zone 3
F__4
Trouble Zone 4
F__5
Trouble Zone 5
rES_
System Reset
F__A
Annunciator Fault
F__E
Earth Fault
Lo_b
Low Battery
no_b
No Battery
PH_1
Primary Central Station Number Comm. Fault
PH_2
Secondary Central Station Number Comm.
Fault
bEL1
Bell 1 Fault
bEL2
Bell 2 Fault
no_1
Primary Phone Line Fault
no_2
Secondary Phone Line Fault
SUP1
Supervisory Alarm Zone 1
SUP2
Supervisory Alarm Zone 2
SUP3
Supervisory Alarm Zone 3
SUP4
Supervisory Alarm Zone 4
SUP5
Supervisory Alarm Zone 5
_AC_
AC Power Loss
Содержание MS-5024
Страница 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...
Страница 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 7: ......
Страница 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 54: ......
Страница 56: ......
Страница 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Страница 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Страница 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...